Housing Urban and Rular Development Government Departments Closing in 1 days TDR #56468752

Tender For Supply, Erection, Testing And Commissioning Of 1 No Silent Dg Set 400 Kva Without Amf Panel For Light Load In Jcc Seven Storey Old Building And 1 No Silent Dg Set 125 Kva Without Amf Panel For Light Load In Two Storey Old Building Judicial

Issued by Government Departments · Ludhiana, Punjab
Tender Value
82.64 Lakhs
Estimated cost
Bid Submission
24 Jul 2026
1 days left
EMD
1.65 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ludhiana → Punjab
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Supply, Erection, Testing And Commissioning Of 1 No Silent Dg Set 400 Kva Without Amf Panel For Light Load In Jcc Seven Storey Old Building And 1 No Silent Dg Set 125 Kva Without Amf Panel For Light Load In Two Storey Old Building Judicial Court Complex Ludhiana

BOQ

Name of Work:- Supply, Erection, Testing and Commissioning of 1 no Silent DG Set 400 Kva without AMF Panel for Light load in JCC seven Storey Old Building And 1 no Silent DG Set 125 KVA without AMF Panel for Light load in Two storey old Building Judicial Court complex Ludhiana
Sl. No. Item Description
1Cost of Silent DG Silent 400 Kva & their accessories
2PVC INSULATED PVC SHEATHED FR ROUND FLEXIBLE COPPER CONDUCTOR CABLE:
3Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-
4Overall size 1.5sq.mm (Un-sheathed)
5Overall size 2.5sq.mm (Un-sheathed)
6Overall size 4sq.mm (Un-sheathed)
7Overall size 10sq.mm (Un-sheathed)
8Overall size 16sq.mm (Un-sheathed)
9PVC, HDPE PIPES & PVC FLEXIBLE PIPES:
10Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:-
11Heavy Gauge PVC Conduit Pipe 25mm dia. (On Surface)
12MINIATURE CIRCUIT BREAKERS:
13Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:-
14MCB Single Pole 6-32amp. (10kA, Curve-C)
15MCB Triple Pole 50, 63amp. (10kA, Curve-C)
16SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's:
17Supply and erection of sheet metal double door vertical distribution boards IP 43-IK09 metal door (dust protected) as per IS:8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars for each phase, 2 Nos. shrouded neutral bars, 2Nos. earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting MCCB's as incomer and outgoings SP/TP miniature circuit breakers in the distribution board as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:-
18TP&N Double Door Vertical DB's 4 way each (With provision of FP MCCB upto 125amp)
19MCCB's (MOULDED CASE CIRCUIT BREAKER):
20Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader links and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-
21MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
22XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
23Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
24Overall size 50sq.mm (3½ Core) Un-armoured (Loose)
25Overall size 500sq.mm (3½ Core) Un-armoured (Loose)
26DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:
27Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
28Double Walled Corrugated HDPE Pipe 63/ 51mm (Outer/ Inner dia.)
29COPPER EARTHING (Upto 14 metre in Length):
30Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
31Earthing with 25mm x 5mm Copper Tape (upto 14Metre in Length)
32COPPER EARTHING STRIP (As Additional Length):
33Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
34Additional Length 25mm x 3mm thick Copper Tape
35ON LOAD CHANGEOVER SWITCH (With Sheet Enclosure):
36Supply and erection of On Load Change over Switch with advance neutral UNIT in sheet enclosure on the existing surface. (Confirms to IS 13947 (Part-3). complete with G.I. Bolts, Nuts etc. according to the size of holes in the body of the enclosure & Connections on both sides of switch with suitable size of thimbles as per PWD General Specifications:-
37On Load Change Over Switch Four Pole 400amp., 415volts (With Sheet Enclosure)
38Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:-
39Aluminium thimble cable Core size 500sq.mm
40Supply, Erection, Testing and Commissioning of Water Cooled Silent DG Set 400KVA/320KW without AMF Panel, Three Phase, 415Volts, 50Hz, 1500 RPM Silent (Sound Proof) Diesel Generator Set. It should be Water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard).ENGINE: The Diesel engine developing minimum 594 BHP for giving a power rating as per ISO 8528- Part-1 (With CPCB-IV Norms upto date amendments) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements.
41ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication.ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled
42Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use.ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet. It should be Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal parts should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack .The acoustic lining should be made up of high quality insulation material i.e. Rockwool / glass/ mineral wool / PU foam of appropriate thickness & density for sound absorption.The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc. Warranty period for DG Set shall be for a period of two year date of commissioning.
43MANUAL CONTROL PANEL: Manual control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-42 degree of protection & front operated, composite meter for digital display. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shorcircuit, instantenous, earth fault protection) should be used. Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH meter, Ammeter, Frequency meter,battery charger complete in all respect as desired by engineer at site 5 critical part of Engine (Cylinder) head, cylinder head, cylinder block,Cam shaft,crank shaft,connecting road) shall be warranted for 5 year from date of disspatch.
44Making of Cement concrete foundation of size 20' X 10' X 2' high for DG Set. The foundation start with Earth work in excavation 16' x 10' in foundations, Cement Concrete 1:5:10 with 40mm gauge stone agreegate mixing by mechanical means using concrete mixer volumetric type of size 22'x12'x0.75' , First class burnt brick work laid in cement sand mortar 1:4 in foundation and plinth size 20'x1.125'x 2' , Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating lead upto 30 metres sizes 19.75'x8.75'x2', Shuttering for faces of concrete foundations and foundations, Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth. sizes 20'x10'x0.5', Cold twisted deformed (Ribbed/for Steel Bar) Bar Fe 500 grade as per IS 1786-2008 complete in all respect as per site requirement and as desired by the Engineer in charge.
45Cost of Silent DG Silent 125 Kva & their accessories
46XLPE INSULATED UN-ARMOURED CABLES (LOOSE):
47Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-
48Overall size 95sq.mm (3½ Core) Un-armoured (Loose)
49DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:
50Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-
51Double Walled Corrugated HDPE Pipe 63/ 51mm (Outer/ Inner dia.)
52COPPER EARTHING (Upto 14 metre in Length):
53Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-
54Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length)
55COPPER EARTHING STRIP (As Additional Length):
56Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-
57Additional Length 25mm x 3mm thick Copper Tape
58ON LOAD CHANGEOVER SWITCH (With Sheet Enclosure):
59Supply and erection of On Load Change over Switch with advance neutral UNIT in sheet enclosure on the existing surface. (Confirms to IS 13947 (Part-3). complete with G.I. Bolts, Nuts etc. according to the size of holes in the body of the enclosure & Connections on both sides of switch with suitable size of thimbles as per PWD General Specifications:-
60On Load Change Over Switch Four Pole 160amp., 415volts (With Sheet Enclosure)
61Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:-
62Aluminium thimble cable Core size 95sq.mm
63Supply, Erection, Testing and Commissioning of Water Cooled Silent DG Set 125KVA/100KW without AMF Panel, Three Phase, 415Volts, 50Hz, 1500 RPM Silent (Sound Proof) Diesel Generator Set. It should be Water cooled naturally aspirated/ turbo charged/ turbo charged after cool (As per manufacturer standard).ENGINE: The Diesel engine developing minimum 155.1 BHP for giving a power rating as per ISO 8528- Part-1 (With CPCB-IV Norms upto date amendments) in KVA at the load terminals of alternator at 1500 rpm at actual site conditions. The engine shall confirm to IS 10000/ ISO 3046/ BS: 649/ BS 5514 amended up to date have dynamically balanced Fly wheel, air cleaner (dry/ oil bath type) as per manufacturer standard. A mechanical/ electronic governor of TYPE A1 AND A2 to maintain engine speed at all conditions of load, daily fuel service tank of minimum 8 hours running capacity as per manufacturer standard, Dry exhaust manifold with suitable exhaust residential grade silencer to reduce the noise level.suitable self-starter for 12 V/ 24 V DC ,battery charging alternator unit and voltage regulator, Lubrication oil cooler,Lubrication oil filters with replaceable elements.
64ENGINE CONTROL PANEL: Engine control panel fitted and having digital display i.e Start/stop key switch/push button, Battery charging indication,Engine Hours indications, Over speed indication, High water temperature indication, Lubricant oil pressure indication,) RPM indication.ALTERNATOR: The alternator should be designed as per (IS4722 and IEC:34 ) standard. Rated Power Factor : 0.8 (lag), Rated voltage : 230/415 volt, SPDP (Screen Protected Drip Proof), Degree of protection: IP-23, Ventilation : Self ventilated air cooled
65Alternator should have 40 degree maximum class H insulation, Automatic voltage regulator unit should be provided as per standard practice of manufacturer. Its voltage dip shall not exceed more than 20% of the rated voltage at any step load or transient load as per ISO 8528 (Part-1). Its efficiency at full load 0.8 power factor, 10% overload one hour in every 12 hrs of continuous use.ACOUSTIC ENCLOSURE: The enclosure shall be fabricated out the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet. It should be Suitable for outdoor installation exposed to weather conditions, noise level up to 75 dB (A). All sheet metal parts should be processed through 7-tank pre treatment process and batteries accommodated in the battery rack .The acoustic lining should be made up of high quality insulation material i.e. Rockwool / glass/ mineral wool / PU foam of appropriate thickness & density for sound absorption.The inside of enclosure should be provided with at least one no. 28 W-T5 fluorescent tube light/ LED 10Watt luminaries controlled by a 5A switch for adequate lighting during servicing etc. Warranty period of DG set shall be for a period of two years from the date of commissioning
66MANUAL CONTROL PANEL: Manual control panel shall be fabricated out of 1.6 mm sheet steel, totally enclosed, dust, damp and vermin proof wall mounted/ free standing floor mounted type with IP-42 degree of protection & front operated, composite meter for digital display. MCCB (Fixed Thermal and Adjustable Thermal protection)/ ACB (Over cuurent/ overload, shorcircuit, instantenous, earth fault protection) should be used. Battery charger complete with voltage regulator, Voltmeter and Ammeter for charging the battery from external mains. This will be in addition to the battery charging alternator or dynamo fitted on the engine.All the components in the control panel shall be properly mounted, duly wired and labeled. Suitable terminals are to be provided for panel incoming and outgoing connections. System opeartion facility provided shall afford the following operational requirements. Necessary instruments and accessories such as voltmeter, power factor meter, KW meter, KWH meter, Ammeter, Frequency meter,battery charger complete in all respect as desired by engineer at site 5 Critical part of Engine (Cylinder head,cylinder block, cam shaft,, crank shaft, connecting rod) shall be warranted for 5 year from date of dispatch.
67Making of Cement concrete foundation of size 15' X 8' X 2' high for DG Set. The foundation start with Earth work in excavation 16' x 10'x0.75' in foundations, Cement Concrete 1:5:10 with 40mm gauge stone agreegate mixing by mechanical means using concrete mixer volumetric type of size 16'x10'x0.75' , First class burnt brick work laid in cement sand mortar 1:4 in foundation and plinth size 16'x1.125'x 2' , Earth filling under floors with surplus ordinary soil or soil containing gravel or kankar upto 40% excavated from outside the building plinth in 15 cm layers including ramming, watering and consolidating lead upto 30 metres sizes 15.75'x5.75'x2', Shuttering for faces of concrete foundations and foundations, Reinforced cement concrete M-20 mechanically batch mixed using batch type concrete mixer as per IS:1791 and vibrated by needle vibrator but excluding steel reinforcement centring and shuttering in foundation and plinth. sizes 15'x8'x0.5', Cold twisted deformed (Ribbed/for Steel Bar) Bar Fe 500 grade as per IS 1786-2008 and Cost of shed included as Plinth size to cover DG with the material of Fiber/iron sheets, angle, Channels, or iron pipes complete in all respect as per site requirement and as desired by the Engineer in charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56468752
AUTHORITY Government Departments
TENDER VALUE 82.64 Lakhs
LAST DATE 24-07-2026
Authority
Authority Name Public Works Department
Work Description Tender for Supply, Erection, Testing And Commissioning Of 1 No Silent Dg Set 400 Kva Without Amf Panel For Light Load In Jcc Seven Storey Old Building And 1 No Silent Dg Set 125 Kva Without Amf Panel For Light Load In Two Storey Old Building Judicial Court Complex Ludhiana
Basic Detail
Tender No Bid No.4 dt 14.07.2026
Bidding Type Tender
Location
City Ludhiana
State Punjab
Key Dates
Publish Date 15 Jul 2026
Submission Date 24 Jul 2026
Open Date 27 Jul 2026
Finance
Tender Value 82.64 Lakhs
Tender Fee 5000
EMD 1.65 Lakhs
Exemption Not Available
Document List
BOQ_349574.xls
d06c9645-318e-4110-acf7-8286e6f5f8a6.html
Tendernotice_1 (10).pdf
Tendernotice_2 (6).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 15, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Jul 27, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 4 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_349574.xls

html

d06c9645-318e-4110-acf7-8286e6f5f8a6.html

pdf

Tendernotice_1 (10).pdf

pdf

Tendernotice_2 (6).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders