Tender For Provision And Repalcement Of Existing Overhead Lt Line Into Underground Cable Network Alongwith Allied Infra (Ph-I) At Hq Sect repair renovation Under Age (I) Cif (K)
Tender Value
43.05 Lakhs
Estimated cost
Bid Submission
04 Aug 2026
18 days left
EMD
86106
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Srinagar → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision And Repalcement Of Existing Overhead Lt Line Into Underground Cable Network Alongwith Allied Infra (Ph-I) At Hq Sect repair renovation Under Age (I) Cif (K)
BOQ
| Sl. No. | Item Description |
| 1 | Excavating in trenches in any type of soil, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for foundation etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exceeding 10 sq m on plan and getting out complete all as specified and directed. |
| 2 | Removing surplus excavated material to a distance not exceeding 50 Mtr and deposting where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 3 | Returing filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each complete all as specified and directed. |
| 4 | Supply and laying brick of conventional size 230x115x75mm locallly available as protection of cable in trenches complete all as specifed and as directed. |
| 5 | M&L sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm thick after laying, consolidated and compacted with clean dry sand complete all as specified and directed.Note : Punned thickness shall be measured for payment purpose. |
| 6 | Supply, laying, jointing and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed. |
| 7 | Supply, laying, jointing and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed. |
| 8 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed. |
| 9 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified and directed. |
| 10 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and directed. |
| 11 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core complete all as specified and directed. |
| 12 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 3.5 core complete all as specified and directed. |
| 13 | Supply, laying, jointing and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 sq mm 2 core complete all as specified and directed. |
| 14 | M&L LT indoor/outdoor end joint (Heat Shrinkable) for under ground PVC insulated and PVC sheathed armoured heavy duty cables with aluminium conductor including jointing kit, including making joints for the cable of size 240 to 300 sqmm x 3.5 core including testing and commissioining complete all as specified and directed. |
| 15 | S&F GI Pipe medium grade for protection of cable for road crossing and supporting to cable and fixing with panel, wall, pole complete all as specified size 150 mm complete all as specified and directed. |
| 16 | S&F GI Pipe medium grade for protection of cable for road crossing and supporting to cable and fixing with panel ,wall ,pole complete all as specified size 100 mm complete all as specified and directed. |
| 17 | S&F GI Pipe medium grade for protection of cable for road crossing and supporting to cable and fixing with panel ,wall ,pole complete all as specified size 80 mm complete all as specified and directed. |
| 18 | S&F GI Pipe medium grade for protection of cable for road crossing and supporting to cable and fixing with panel ,wall ,pole complete all as specified size 50 mm complete all as specified and directed. |
| 19 | S&F GI Pipe medium grade for protection of cable for road crossing and supporting to cable and fixing with panel ,wall ,pole complete all as specified size 25 mm complete all as specified and directed. |
| 20 | Supply, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made IP65/54, FR Material, Anti-Corrosive Motor Starter Panel. The Motor Starter panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURE including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4:, anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The Panel with dew guard moisture absorber feature. The manufacturer / supplier of panel shall submit a copy of ASTA CPRI TEST REPORT IN POLYCARBONATE , Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and panel assembled by OEM, channel partner or sister concern assembly will not be accepted also submitted IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing] also submit complete all as specified and directed. INCOMINGa) 315 Amp, 4 pole MCCB, 35 KA 415V Adj. Thermal & Fixed Magnetic Released with Rotary Handle - 01 Nob) VAF DigitalMeter - 01 No c) Set of LED type indicating lamps - 01 No d) Copper Bus Bar 400Amp TPN OUTGOING a) 200 Amp, MCCB FP 36KA 415 V, with Rotary Handle - 01 No.b) 160 Amp, MCCB FP 25KA 415 V, with Rotary Handle - 02 Nos. c) 100 Amp, MCCB FP 16KA 415 V, with Rotary Handle - 02 Nos. d) Suitable size platform for the panel with PCC 1:4:8 type D-2 with (using 40mm graded crushed stone aggregate) as in 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B' old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) on top and grouting bolts etc for panel. The Platform shall be such that it is of a height 45cm above the nearest ground level.Note : Cost of platform and all other accessories shall be deemed to be included in the rate quoted. |
| 21 | Supply, installation , commissioning and testing Polycarbonate ASTA CPRI approved OEM made IP65, FR Material, Anti-Corrosive Bus Bar Feeder Pillar. The Bus Bar Feeder Pillar shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURE including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: , anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The Bus Bar Feeder Pillar with dew guard moisture absorber feature. The manufacturer / supplier of panel shall submit a copy of ASTA CPRI TEST REPORT IN POLYCARBONATE , Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and panel assembled by OEM, channel partner or sister concern assembly will not be accepted also submitted IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The Bus Bar Feeder Pillar shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing] also submit complete all as specified and directed. INCOMINGa) Copper Bus Bar TPN 100A with color Coding, Suitable Holes and Provided the Provision for Mini. Entry Cables 1 Incoming 185Sq.mm and 4 Nos output upto 95Sq.mm. Provided Proper suitable Glands for Entry and outputs.b) Set of LED type indicating lamps - 01 No c) Feeder Pillar floor Mounting Type with Canopy and Stand.d) Suitable size platform for the panel with PCC 1:4:8 type D-2 with (using 40mm graded crushed stone aggregate) as in 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B' old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) on top and grouting bolts etc for panel. The Platform shall be such that it is of a height 45cm above the nearest ground level.Note : Cost of platform and all other accessories shall be deemed to be included in the rate quoted. |
| 22 | Supply, installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made IP66, made of high quality Polycarbonate (shock proof, rust free, corrosion free, acid and chemical resistant, fire retardant, self-extinguishing, having high impact, made of halogen and silicon free recyclable material conform to RoHS directive 2002/95/EC ). The DB shall have high grade gasket made of Polyurethane ( PUR ) VTPN DB 8WAY. The VTPN DB with Transprant Door. Environmental conditions for distribution boards according to IEC 61439-3: -5 °C up to 35 °C, max. + 40 °C; humidity: 50% at 40°C, 100% at 25 °C for empty enclosures: - 25°C up to + 70 °C. Enclosure should be totally insulated, protection class II. And rated insulation voltage should be 690V AC as per IEC 60664. The manufacturer / supplier of VTPN shall submit. Weather proof: UV resistant according to IEC 61439-1, clause no 10.2.4: The material is examined for UV resistance IEC 60 695-2-11: should withstand glow wire test at 9600C UL subject 94, should be flame retardant and self-extinguishing in nature. IEC 61 439-3: Intended to be operated by ordinary person. Toxic behaviour: silicone- and halogen-free Chemical resistance: resistant against acid, lye, benzene and mineral oil a) MCB 125A TPN 10A C-CURVE - 1 No. (Incomer)b) MCB 40A TP 10KA C-Curve - 06 Nos (Outgoing) c) DB Wall Mounting Type IP 66 |
| 23 | S&F Sheet metal enclousre for DBs double door single pole and neutral with 200 amps rated bus bar of 4- way, 240 volts complete all as specified and directed. |
| 24 | S&F Sheet metal enclousre for DBs double door single pole and neutral with 200 amps rated bus bar of 8- way, 240 volts complete all as specified and directed. |
| 25 | S&F MCB single pole and nuetral 32 Amps, 240 volts , B-series complete all as specified and directed. |
| 26 | S&F MCB single pole 6 to 32 Amps, 240 volts , B-series complete all as specified and directed. |
| 27 | M&L earthing complete with galvanised steel earth plate electrode 600mmx600mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to earth test point/MCB DBs all as specified and indicated complete with funnel, charcoal, dust, salt etc and GI protection pipe, medium grade 15mm bore and GI watering pipe 20mm bore light grade, 40mm thick precast RCC M-15 (nomial mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover, PCC M-15 (Nominal mix) pit, excavation and earth work in any type of soil and connected, complete all as specified and directed including testing on completion.Note:- 1. Cost of earth lead & protection pipes length upto & including 7.50 metre is deemed included in the unit rate quoted by the contractor.2. Soil should be free from stone, boulders, aggregate, gravels etc |
| 28 | M&L earthing with steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20mm dia GI medium grade watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetable soil to the remaining 10%,removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6mm fixed to wall all as specified in electrical plate No 3 of SSR Part-I complete all as specified and directed including testing on completion. Note:- (i) Rate quoted for Item includes the cost of 7.5 metre GI pipe for protection of earth lead. (ii) Rate quoted for Item includes the cost of 7.5 metre GI earth lead. |
| 29 | S&F Street light bracket made out of GI tubing 32/40mm dia, light grade of approx length 1.2mtr long bend to shape suitable for security light fittings with necessary MS clamps -02 Nos with one coat of anti corrosive primer and two coats of aluminium paint including nuts, bolts, washers etc complete all as specified and directed. |
| 30 | Supply, installation, commissioning and testing Junction boxes made of Lid PC and base is polystyrene Hensel reference : KG series suitable . Junction Boxes Size 217 x 253 x 115 mm in Grey RAL 7035 colour. Junction Box IP 65 Thermoplastic PS Polystyrene weatherproof Junction Box with multi level knockouts for cable glands in different sizes. The pre-moulded knockouts shall be available on top and bottom of the junction box to enable cable entries from both direction. The junction box shall have an optional cable entry at the bottom up Cable Size 25 Sq mm of the box via pre-moulded knockout to enable pole mounting option. Lid fasteners self closed will be tool operated. it will be sealable with accessories. The junction box shall have elongated holes inside them for wall/pole mounting provision. The junction box with 4 Pole Terminal Strip and MCB SP 6Amp 10 KA C Curve for LED light. In the event of formation of condensed water, the junction box shall have a minimum of two condensation knock-outs inside to ensure optimum safe performance complete all as specified and directed. The junction box shall fulfill the following standards :-a) Weatherproof : Rainwater proof, temperature resistant.b) IEC 60670-22 : Particular requirements for connecting boxes and enclosures.c) IEC 60695 – 2 – 11 : Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 750 deg C.d) IEC 60529 : IP 65 degree of protection.e) UV Resistant in accordance with IEC 61 439-1, Clause no 8.4.4f) The Junction Box with Suitable Glands 3 Nos with each and chromium plated clamps, nut bolts complete all as per manufacturer’s instructions. |
| 31 | S&F precast cement concrete solid building blocks or slabs 10cm thick Type B1 (1:2:4) (with plain or interlocking joints as directed) setting in mortar in Road, Path complete all as specified and directed. |
| 32 | Providing cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in bed plates, coping and including weathering, slightly rounded or chamfered angles and throating and providing form work for rough finished surfaces and finishing all exposed surfaces of concrete complete all as specified and directed. |
| 33 | M&L Road cutting for cable crossing and cutting with machine not wide 45 X depth 0.90 meter with skilled labour and direction and making good as per existing complete all as specified and directed. |
| 34 | S&F HT/LT Cable Route indicator /marker Dia-150/100 mm & thickness-3mm round shape with corrosion resistant made by Stainless steel, complete all as specified and directed. |
| 35 | Dismantling and taking down carefully old ACSR conductor/GI wire of any size from HT/LT overhead line after unbinding from insulator complete all as specified. Note : Old materials to be deposited in MES store yard of AGE (I) CIF (K) complete all as specified and directed. |
| 36 | M&L dismantling cross-arms of M.S. channel or angle sections etc. from poles complete all as specified and directed. Note : Old materials to be deposited in MES store yard of AGE (I) CIF (K) complete all as specified and directed. |
| 37 | Dismantling of insulators of any type, any size all as directed. Note : Old materials to be deposited in MES store yard of AGE (I) CIF (K) complete all as specified and directed. |
| 38 | Dismantling stay assembly complete including excavation for taking out PCC block breaking of PCC block for taking out MS plate and removing unserviceable item i.e iron items or PCC from site complete all as specified and directed.Note : Old materials to be deposited in MES store yard of AGE (I) CIF (K) complete all as specified and directed. |
| 39 | Dismantling unserviceable steel poles of any size complete and removing from site complete all as specified and directed. Note : Old materials to be deposited in MES store yard of AGE (I) CIF (K) complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 14, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 04, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysAug 06, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender