Drinking Water Supply and Sanitation Government Departments Closing in 16 days TDR #56451168

Tender For Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Naraini Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Banda Under Amrut 2.0 Programme On

Issued by Government Departments · Banda, Uttar Pradesh
Tender Value
31.54 Crore
Estimated cost
Bid Submission
31 Jul 2026
16 days left
EMD
31.54 Lakhs
Bank guarantee accepted
Document Fee
23600
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Banda → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Naraini Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Banda Under Amrut 2.0 Programme On Turn-Key Basis

BOQ

Name of Work:- Surveying,Soil investigation, Engineering, Design, Supply of all materials, labour, T&P etc. required for completion of following works of Naraini Nagar Panchayat Re-organisation Water Supply Scheme Dist. Banda under AMRUT 2.0 Programme on turn-key basis
Sl. No. Item Description
1CIVIL WORKS
2INTAKE WELL
3Detailed hydrological and geological survey, Site Survey, Testing for bearing capacity of soil, Design, obtaining necessary approvals and Construction of INTAKE structure / well (Capacity 10.50 MLD) Cum Pump House and Approach bridge ,Dewatering arregement, well sinking, Approach Channel Shoring for Coffer Dam including removal of coffer dam. Cost includes all material, Tools & Plants and labour complete for construction of said intake well. Cost includes all necessary river protection works and all necessary arrangements to ensure required raw water intake in all seasons (especially for Dry weather flow) complete in all respect as directed by Engineer –in-charge.
4WATER TREATMENT PLANT
5Detailed Geographical and hydrological Survey, Site investigation, Testing for bearing capacity of soil, Designing, obtaining necessary approvals with Supply of all materials labour ,Tools & plants for Construction of Water Treatment Plant of 6 MLD capacity (Net out-put capacity i.e. excluding overloading,add 20 % overloading i.e 7.2 MLD) water treatment plant with PLC-SCADA based automation with space saver/ compact and efficient modern treatment technology with construction of MCWR 500 KL capacity. The Treatment Plant as per approved hydraulics essentially consists of the units for : Inlet Chamber, Pre-Sedimentation Unit, Settling Tank ,Venturi Flume ,Flash Mixer, Alum Solution, Tank Chemical House, high to ultra highrate clarifiers, Clarifloculator, high rate filtration unit, Rapid Graity Filters Back Wash Tank Air Blower Post Chlorination Inlet, Outlet , Back Wash Gutter , Troughs , Weirs Reuse of Back Wash Water Thickened Sludge Sump & Pump House Filterate Sump & Pump House Clear Water Sump for Backwash,Clear Water Outlet Chamber Sludge Drying Beds. All other required units. Cost includes all necessary Civil , E&M and SCADA works as per approved by competent authority complete in all respect as directed by Engineer –in-charge.
6OVER HEAD TANK
7Design, Supply of all materials, labour, T&P etc required for construction of Intz type RCC Over Head Tank including various works like - soil testing, Ventilator and Water level indicator, Lightening conductor, C.I. D/F Verticle pipes (Inlet Pipe, Outlet Pipe, Overflow Pipe & Washout Pipe), duck foot bend, puddle collers and bell mouths, Sluice valve on inlet, outlet & washout pipe and Valve Chamber, Bye-pass arrangement of OHT, Flooring, Apran & Drain (100 mm thick PCC of 1:2:4 & 100 mm thick RCC of 1:1.5:3), Floor shall be 30 cm above the finished ground level of Campus, Two coat apex painting over one coat primer of approved colour after finishing of RCC surface with grinder, repair of pin holes, unevenness., Railings - G.I. Pipe railing around stair case (both sides), balcony & top dome periphery, S.S ladder from opening of top dome to bottom dome, Stair case (Seperate two column based RCC staircase and 1 m wide balcony with arrangement of M.S Gate and Jali), Food grade epoxy coating of FOSROC / Ciba-Geigy or reputated brand on inside surface area of water container after testing for water tightness, of capacity and staging mentioned as under: For bidding purpose, bearing capacity of soil shall be considered as 8t/sq.m. Working design shall be based on the SBC determind after soil investigation / 8 tonne/sqm whichever is less complete in all respect as directed by Engineer –in-charge.Note :- The bid price of Over Head Tanks is to be submitted considering net safe allowablebearing capacity as 8 t/m2, keeping the minimum foundation depth to be 2.5 m below existing ground level at the site of work.The successful bidder will be required to investigate the soil bearing capacity. If net safe allowable bearing capacity is found to be equivalent or more than 8 t/m2, the design of OHT will be based on 8 t/m2 capacity. However, in case the net safe allowable bearing capacity is found to be below 8 t/m2, then the design of OHT will be based on the actual bearing capacity.To accommodate for the additional cost required, in the eventuality of net safe allowable bearing capacity falling below 8 t/m2, the payment shall be made as extra item of work.
8CPT TANK 50 KL, 22 M staging
9OHT of 1350 KL Capacity, 25 m staging (Zone 2) Inlet 250mm, Outlet 350mm, Over flow 250mm, Washout 100mm
10OHT of 500 KL Capacity, 25 m staging (Zone 3) Inlet 200mm, Outlet 250mm, Over flow 200mm, Washout 100mm
11Repairing of Existing 500 KL/16M Staging OHT including work of Sepage free, painting etc. complete in all respect as directed by Engineer –in-charge.
12COMMON CLEAR WATER RESERVOIR CUM PUMP HOUSE
13Design, supply of all material, labour, T&P etc. required for construction of Circular, R.C.C Clear Water Reservoir cum pump house including various works like soil testing, 1 m wide stair case with stainless steel hand railing to go inside reservoir, sump below the pump house area, stainless steel railing over the R.C.C slab of reservoir, Granular texture finish on exterior surface of pump house, gantry beam, food grade epoxy coating of FOSROC / Ciba-Geigy or reputated brand on inside surface area of water container after testing for water tightness, of capacity complete in all respect as directed by Engineer –in-charge.Note : The bid prices of Clear Water Reservoir / Pumping Stations are to be submitted considering the depth of excavation may extend up to 6 m BGL.
14600 KL Capacity.
15Construction of Master Control Room as per type design (Size - 8.0m x 5.0m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
16Construction of HT panel Room as per type design (Size - 5.0m x 4.5m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
17Construction of LT panel Room as per type design (Size - 5.0m x 4.5m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
18Construction of Meter Room as per type design (Size - 4.0m x 3m x 3m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
19Supply of ISI mark DI K-9 and K-7 S&S pipes (push on joints) of following class and Rubber gasket of EPDM Quality and including Supply of D.I. S/S or flanged Specials conforming to I.S. 8329/2000 Suitable for above D.I. S/S F.O.R. destination and all statutary duties and taxes, third party inspection charges, transit insurance, freight, transportation to store/ site of work, unloading, stacking etc. complete as directed by Engineer –in-charge.
20D.I. Pipe Class-K9
21300mm dia
22200mm dia
23350mm dia
24400mm dia
25D.I. Pipe Class-K7
26200mm dia
27250mm dia
28300mm dia
29350mm dia
30Supply of High Density Polyethelene Pipes (HDPE (PN-6)/PE-100), conforming to IS 4984 / 14151 / 12786 / 13488 in coils/ standard lengths and inluding Supply of HDPE Specials & jointing material like electro-fusion coupler, flanged joint, conforming to I.S.- 4984/2016 with solvent cement suitable for above HDPE pipe F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation chaloading & stacking the same etc. complete as directed by Engineer –in-charge.
31160 mm dia HDPE Pipe PN-6
32140 mm dia HDPE Pipe PN-6
33110 mm dia HDPE Pipe PN-6
3490 mm dia HDPE Pipe PN-6
35Excavation for pipe line in ordinary soil (loam, clay, sand) with lift up to 1.5 m and lead up to 50 m and including filling back, watering and ramming of excavated earth into the trenches and removal and disposal of surplus earth within 50 meters.(Dia+0.5)
36In ordinary soil
370 - 1.5
38Carting, lowering, laying and jointing with SBR ruber gaskets D.I. K-7/ D.I. K-9 pipes of following dia & pressure including all specials, to site of work, lowering them into trenches, laying true to alignment and gradient, in proper position, cutting of pipes, making of joints including cost of jointing materials and rubber rings, labour, T&P, including hydraulic testing etc. complete as directed by Engineer in-charge. It includes provision for making of alignment on city roads, making trial pits to investigate location of various under grounds services like telephone cables, electric cable, existing pipe lines and sewer lines etc. arrangements for diversion of traffic and associated works etc. with supply of all necessary equipment, materials, labour and T&P etc. complete required for completion of work. The trenches shall be properly barricaded and fenced off wherever necessary. Red flags and caution boards during day and red lights during night shall be displayed so as to avoid any accidents and updating survey of laid pipe on Gati Shakti Portal and or directed by Engineer-in-Charge.Note : Only SBR Rubber gaskets to be used as per IS-5382 and IS- 12820.
39D.I. Pipe Class-K9
40200mm dia
41300mm dia
42350mm dia
43400mm dia
44D.I. Pipe Class-K7
45200mm dia
46250mm dia
47300mm dia
48350mm dia
49Lowering, laying and jointing of HDPE pipe in proper position using electrofusion specials including supply of all Electrofusion specials & hydraulic testing as per relevent IS Code complete with all accessories like Electrofusion machine, power arrangements, hydraulic testing arrangements, labours, material etc. complete and updating survey of laid pipe on Gati Shakti Portal and or directed by Engineer-in-Charge.
50160 mm dia HDPE Pipe PN-6
51140 mm dia HDPE Pipe PN-6
52110 mm dia HDPE Pipe PN-6
5390 mm dia HDPE Pipe PN-6
54Supply of following types of C.I. valves confirming to the I.S. specification inclusive cost of jointing materials (Rubber gasket of EPDM Quality) including all statutary duties and taxes, third party inspection charges, transit insurance, freight, transportation to store/ site of work, unloading, stacking etc. complete as directed by Engineer –in-charge.
55300 mm dia
56250 mm dia
57200 mm dia
58150 mm dia
59100 mm dia
60Carting of CI Sluice valves of Following sizes to the site of works Lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete
61300 mm dia
62250 mm dia
63200 mm dia
64150 mm dia
65100 mm dia
66Supply of all materials, labour, T & P etc. required and construct thrust blocks at the bends and below the Valves.
67Supply of the following sizes of C.I. Double flanged scour valves as per I.S. 780 class-1 working pressure 10 kg/Sqcm F.O.R Destination including all taxes and insurance.complete in all respect as directed by Engineer –in-charge.
6880 mm dia
69Carting of scour valves to the site of works lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
7080 mm dia
71Supply of 25 mm dia screwed down type air valve with gun metal seat at site stone including all taxes in all respect as directed by Engineer –in-charge.
72Carting of 25 mm dia screwed down air valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
73Supply of underground sluice valves type fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site including all taxes in all respect as directed by Engineer –in-charge.
74Carting of 80 mm dia flanges fire hydrant of the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
75Dismantling of following type of road surfaces for laying of pipe line and house connection work including sorting out of serviceable materials and disposal of unserviceable materials including supply of all materials, labour, T&P etc. required for proper completion of the work.
76B.O.E. ROAD
77BITUMINOUS ROAD
78C.C. ROAD
79INTERLOCKING TILES
80Permanent re-instatement of following type of road surfaces after laying of pipe line including supply of all materials, labour, T&P etc. required for completion of work. It also includes necessary excavation required for preparation of trench for reinstatement of road, disposal of surplus unserviceable material, watering, ramming, cleaning of surface for proper completion of the work as per directions of engineer-in-charge.
81BOE (Brick on Edge) RoadConstruction of BOE road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-Ist class brick shall be used for reinstatement of BOE road. Sand = 25mm thick local sand layer for preparation of surface
82Bitumen road TYPE AConstruction of bitumen road as per UPPWD specification including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-GSB G-1 (One coat) (90-40 mm) = 12.5 cm G -2 (one coat) (45-63 mm) = 7.5 cmG - 3 (one coat) (22.5 - 53 mm) = 7.5 cm BM (One coat) = 7.5 cmSDBC (One coat) = 2.5 cm
83Cement Concrete RoadConstruction of Cement Concrete road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm)CC =100 mm, 1:2:4 (cement, coarse sand & stone ballast of 16-20 mm)
84C.C. Interlocking Tiles Road Type AConstruction of C.C. Interlocking Tile road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm) Sand = 50 mm thick local sand lair for preparation of surfaceNote : 100 mm thick rubber moulded interlocking tile shall be used for construction of interlocking tile road.
85Supply of all materials, labour T&P etc. required and construct surface box/masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete in all respect as directed by Engineer –in-charge.
86Surface box type
87Masonry type
88Supply of all materials, labour T&P Etc. required and construct 350 x 350 x 500 mm size air valve chamber as per type design including supply and fixing the 500 mm dia CI manhole cover complete in all respect as directed by Engineer –in-charge.
89Supply of all materials, labour T&P Etc. required and construct 750 x 450 mm size fire hydrant chamber as per type design including supply and fixing the 500 mm dia CI manhole cover complete in all respect as directed by Engineer –in-charge.
90Provision for crossing of Nalas (0.5m to 2.0 m width) for laying of pipe line including necessary specials, T&P and arrangement of diversion of water, baricatings etc required, with dismantelling of drains and reconstruction of same as per type design of the existing drain complete in all respect as directed by Engineer –in-charge.
910.0 - 3.5 m
923.5 - 7.0 m
933.5 Culvert Crossing
94Providing and making NEW water supply house connection from distribution pipe line of following diameters using 20 mm dia pipe (HDPE pipe (PE 100/ PN 12.5) below ground and medium class GI pipe above ground), saddle (electro-fusion tapping saddle for making connection with HDPE distribution pipeline, DI strap saddle, ferrule, for making connection with distribution pipeline other than HDPE), compression fittings (FTA, MTA etc.), ball valve, specials, including supply of all materials, labour, T&P etc. required for proper completion of the work. It also includes excavation, refilling of pit required for making house connection and updating data on Gati Shakti Portal as per direction Engineer-in-charge.
95for 90 mm - 110 mm dia.
96for 125 mm -160 mm dia.
97for 180 mm -250 mm dia.
98for 300 mm dia.
99Providing and shifting EXISTING water supply house connections from newly laid distribution pipe line of following diameters using 20 mm dia pipe (HDPE pipe (PE 100/ PN 12.5) below ground and medium class GI pipe above ground), saddle (electro-fusion tapping saddle for making connection with HDPE distribution pipeline, DI strap saddle, ferrule, for making connection with distribution pipeline other than HDPE), compression fittings (FTA, MTA etc.), ball valve, specials, including supply of all materials, labour, T&P etc. required for proper completion of the work. It also includes excavation, refilling of pit required for making house connection and updating data on Gati Shakti Portal as per direction Engineer-in-charge.
100for 90 mm - 110 mm dia.
101for 125 mm -160 mm dia.
102for 180 mm -250 mm dia.
103Construction of compound wall comprising of RCC Columns @ 3.0m c/c distance with beam atplinth and top, brick work in 1:4 of as per type design including supply of all material, labour, T& P etc complete.
104Supply and fixing 3.60 m wide MS main gate & 1.0 m wide a wicket gate with RCC Columns as per type design & drawing including primer and painting, meterial, labour, T&P etc all complete as per direction Engineer-in-charge.
105Providing and laying in position reinforced cement concrete (mix 1:2:4) for construction of Square drain, size 250 mm x 250 mm, over PCC 1:4:8, including batching, mixing, placing, vibrating, curing, formwork, finishing, including cost of all material and labor, tools and plants required with transportation, steel, loading, unloading, etc., complete for all leads and lifts and as perspecifications etc required for proper completion of the work as per direction Engineer-in-charge.
106Construction of following types of Road/ flooring for development of CWR / OHT campus and Provide all materials, labour T&P etc. required for proper completion of work and construct Interlocking Road approach road in water works campous at WTP, Intake well to WTP and Zone 2 & 3 required as per site condition as per direction Engineer-in-charge.
107Aproch C.C. Interlocking Tiles RoadConstruction of C.C. Interlocking Tile road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm) Sand = 50 mm thick local sand lair for preparation of surfaceTiles = 100% newNote : 100 mm thick rubber moulded interlocking tile shall be used for construction of interlocking tile road.
108Cement Concrete RoadConstruction of Cement Concrete road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm)CC =100 mm, 1:2:4 (cement, coarse sand & stone ballast of 16-20 mm)
109Providing and laying in position reinforced cement concrete (Mix 1:1.5:3) for construction of thurst block at bends of feeder main, rising main & distribution system including batching, mixing, placing, vibrating, curing, formwork, finishing, including cost of all material and labor, tools and plants required with transportation, loading, unloading, etc., complete for all leads andlifts etc required for proper completion of the work.
110Providing H.Y.S.D steel reinforcement for reinforced cement concrete work including straightening, cutting, bending, hooking, placing in position, lapping and/ or welding wherever required, tying with binding wire and anchoring to the adjoining member wherever necessary asper design, including cost of materials and labor complete as per drawings.
111Construction of Staff Quarter (RCC framed structure), as per type design and drawing each for pump operators & other staff including structural design and drawing, supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in-charge.
112Staff Quarter Half Set
113Dismantling of 125 KL/16 M OHT & Disposal of unserviceable in outskirt of city upto 10 km from site and staking of serviceable material including etc complete required for proper completion of the work as per the directions of Engineer-in-charge.
114EM WORKS
115PUMPING PLANT AND ACCESSORIES FOR INTAKE WELL
116SITC of Vertical type self-oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 27 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
1172300 LPM / 54 Mtr. HEAD / 50 HP MOTOR (2w+1s)
118SITC of DI/DF 200mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 200mm common Header upto 1 m. outside the pump house along with 250 x 200 x 250 mm DI/AF Tee (04 Nos) ,150 mm DI/DF bend (03 Nos ), 250 mm DI/DF bend (01 Nos), 250 mm blind flange (01 Nos), DI/DF Enlarger 150 x 200mm( 3 Nos), DI/DF Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe, DI mechanical joints (04 Nos) and valve etc. complete in all respect as per site conditions.
119DI/DF Butterfly valves as per IS 13095/ BS 5155 Standard drilled to IS 1538 Rated to PN 1.6, Body and disc in DI IS 1865 GR 500/7 , EPDM Rubber seat ,SS410 shaft ,Flange drilling- IS:1538, Electrical Actuator(On/off) duty with Integral starter,415 V 3 Phase 50 hz
120200mm for pumps
121Motor operated actuator with sluice valve :- SITC of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
122250mm for common header
123Non return valve :- SITC of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
124200 mm Dia for pumps
125250 mm Dia for common header
126CE/UL Certified Electromagnetic flow meter :- SITC of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
127Size 250mm for common header
128SITC OF ELECTRICAL ITEMS:-
129Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 25 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
130SITC OF MOTOR CONTROL CENTER (MCC) PANEL :-Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting ofINCOMMING SECTION400A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION100 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 4 No, Spreader Links & Extended ROH for MCCB - 4 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A
131SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 50 HP / 37 KW
132SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 50 KVAR
133SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
134400 Amp Rating
135CE/UL Certified level transmitter for Intake well :- SITC of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
136CE/UL Certified Pressure transmitter for pumps and common header :- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
137SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
138SITC of 3Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
139Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness
140Supply and fixing of Cable trench Chequerred plate
141SITC of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
142SITC of Internal & External electrification of pumping station :-
143Indoor Lighting
144Surface Mounting
145Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
146Suspended Mounting / Surface Mounting
147High Power LED Flood Light 100W
148Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
1491200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
150Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
151450mm sweep (900/1400 RPM)
152Outdoor Lighting
153Supply and fixing of all in one solar LED light fixture with integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system.
154Compact Solar LED Street Light- 90W(MONO) 18V / 12.8V 42Ah /60W
155Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
156High Mast Light System
157SITC of solar street light 110 watt all in one wall/ pole mounted battery capacity 12.8 v/42 ah ( Lethium iro battery solar panel 12 v /120 watt ( mono crystalline module (with 5 year repair replacement warranty
158SITC of 12.5 mtr High mast two section top 150mm dia bottom 410mm dia 4.3mm thick without motor with fabricated bucketer system for 04 No. solar light bracket foundation bucket movement up and down for maintenance through manual gear system ( Octagonal in shape GI plated 85 micron hot dip plated with bottom plate thickness 25mm and 08 No. foundation bolt appropriate sizer.
159SITC Solar light with rcc foundation structure 1500 mm x 1500 mm x200mm base colmn size 75 mm x750 mm 900 mm with 08 no 24 mm x 750 mmstud with grouting plate
160SITC of Light arrestor with earthing complete
161160 KVA SUB STATION AT INTAKE WELL
162Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.(d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
163Supply of 50 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
164Supplying of 160 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x150sqmm XLPE cable of 33 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
165Supplying of cubicall type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-(I) Incoming : 2 Nos 400 Amps MCCB of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB. (a) Independent manual spring closing mechanism- 1 No.B10(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set.(c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II) Bus Couplers :1Nos. 630Amps MCCB of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 as amended upto date complete with following accessories for each ACB:(a) Independent manual spring closing mechanism- 1 No.(b) Breaker ‘ON’ indicating light with back up 2 A HRC fuse test terminal block, fuses, circuits contactors for positive electrical interlocking of breakers, etc. as required- 1 set.
166(III) Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.(IV) Interlocking :Electrical through advance contacts in MCCB’s (incomers & bus couplers) and mech- anical (castel key) interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(V) Outgoing :-(a) 1 Nos. 400Amp 4 Pole MCCB Microprocessor based (Ics = kA upto 433 V)/SFU with HRC fuse (BC : 80 kA)(b) CT’s of ratio 10/5Amps 4Nos.4Set (1 set of 2 Nos.)(c) Analog 96 mmsq/Digital* type ammeter (0-100Amp) with selector switch set.
167Supply and laying of 650/1100 volt grade 240 sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T panel and outgoing to MCC panel (1x3½x240 sq mm)
168Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
169Installation and commissioning of 11 KV/0.4 KV substations including HT Panels and L.T. main control panel including all labor T&P complete in all respect.
170Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
171Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core for 11 KV H.T. XLPE cable
172Provision for routine testing of equipments such as transformer, HT Panels and main LT Panel at manufacturer’s works.
173NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
174PUMPING PLANT AND ACCESSORIES FOR MCWR AT WTP TO CPT
175SITC of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical hollow shaft . Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
1762200 LPM / 37 Mtr. HEAD / 30 HP MOTOR (2w+1s)
177SITC of DI/DF 200mm Main piping complete with suitable size and quantity required for delivery side, bye pass arrangement and 250mm common Header upto 1 m. outside the pump house along with 250 x 200 x 250 mm DI/AF Tee (3 Nos), 250 mm DI/DF bend (01 Nos), 250 mm blind flange (01 Nos), DI/DF Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04Nos) etc. complete in all respect as per site conditions.
178DI/DF Butterfly valves as per IS 13095/ BS 5155 Standard drilled to IS 1538 Rated to PN 1.6, Body and disc in DI IS 1865 GR 500/7 , EPDM Rubber seat ,SS410 shaft ,Flange drilling- IS:1538, Electrical Actuator(On/off) duty with Integral starter,415 V 3 Phase 50 hz
179200mm for pumps
180SITC of Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
181Actuator with Sluice Valve of size :- 250mm for common header
182Actuator with Sluice Valve of size :- 400mm for MCWR inlet
183SITC of Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
184200 mm Dia for pumps
185250 mm Dia for common header
186SITC of CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
187Size 250mm for common header
188Size 400mm for MCWR inlet
189SITC OF ELECTRICAL ITEMS:-
190Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
191SITC OF MOTOR CONTROL CENTER (MCC) PANEL :-Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting ofINCOMMING SECTION315A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION63 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 3 No, Spreader Links & Extended ROH for MCCB - 3 Nos., 63A TPN MCCB microprocessor based 35KA - 2 Nos. Terminal 63A
192SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 30 HP / 22 KW
193SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 72 KVAR
194SITC of Auto Phase reversal unit inbuilt time delay & enclousure ( conform to IEC:60947-1 & IEC:60947-b-1)
195160 Amp Rating for WTP & MCWR
196SITC of CE/UL Certified level transmitter for CWR :- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
197SITC of CE/UL Certified Pressure transmitter for pumps and common header :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
198SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
199SITC of 3Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
200Supply ang fixing of rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness
201Supply and fixing of cable trench chequerred plate
202SITC of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
203SITC of Internal & External electrification of pumping station as follows:-
204Indoor Lighting
205Surface Mounting
206Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
207Suspended Mounting / Surface Mounting
208High Power LED Flood Light 100W
209Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
2101200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
211Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
212450mm sweep (900/1400 RPM)
213Outdoor Lighting
214Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system. ( For MCWR )
215Compact Solar LED Street Light- 90W(MONO) 18V / 12.8V 42Ah /60W
216High Mast Light System
217SITC of solar street light 110 watt all in one wall/ pole mounted battery capacity 12.8 v/42 ah ( Lethium iro battery solar panel 12 v /120 watt ( mono crystalline module (with 5 year repair replacement warranty
218SITC of 12.5 mtr High mast two section top 150mm dia bottom 410mm dia 4.3mm thick without motor with fabricated bucketer system for 04 No. solar light bracket foundation bucket movement up and down for maintenance through manual gear system ( Octagonal in shape GI plated 85 micron hot dip plated with bottom plate thickness 25mm and 08 No. foundation bolt appropriate sizer.
219SITC Solar light with rcc foundation structure 1500 mm x 1500 mm x200mm base colmn size 75 mm x750 mm 900 mm with 08 no 24 mm x 750 mmstud with grouting plate
220SITC of Light arrestor with earthing complete
221Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
222160 KVA SUB STATION AT ( MCWR+WTP )
223Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.(d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
224Supply of 50 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
225Supplying of 160 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x150sqmm XLPE cable of 33 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
226Supplying of cubicall type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-(I) Incoming : 2 Nos 400 Amps MCCB of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB. (a) Independent manual spring closing mechanism- 1 No.B10(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set.(c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II) Bus Couplers :1Nos. 630Amps MCCB of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 as amended upto date complete with following accessories for each ACB:(a) Independent manual spring closing mechanism- 1 No.(b) Breaker ‘ON’ indicating light with back up 2 A HRC fuse test terminal block, fuses, circuits contactors for positive electrical interlocking of breakers, etc. as required- 1 set.(III) Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.
227(IV) Interlocking :Electrical through advance contacts in MCCB’s (incomers & bus couplers) and mech- anical (castel key) interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(V) Outgoing :-(a) 2 Nos. 160Amp 4 Pole MCCB Microprocessor based (Ics = kA upto 433 V)/SFU with HRC fuse (BC : 80 kA)(b) CT’s of ratio 10/5Amps 4Nos.4Set (1 set of 2 Nos.)(c) Analog 96 mmsq/Digital* type ammeter (0-100Amp) with selector switch set.
228Supply and laying of 650/1100 volt grade 240sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T Panel (1x3½x240 sq mm)
229Supply and laying of 650/1100 volt grade 95sq mm 3½ core PVC Armoured Aluminium cable from L.T Panel to MCC Panel at WTP (1x3½x95 sq mm)
230Supply and laying of 650/1100 volt grade 70sq mm 3½ core PVC Armoured Aluminium cable from L.T Panel to MCC Panel at MCWR (1x3½x70 sq mm)
231Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
232Installation and commissioning of 11 KV/0.4 KV substations including HT Panels and L.T. main control panel including all labor T&P complete in all respect.
233Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
234Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core for 11 KV H.T. XLPE cable
235Provision for routine testing of equipments such as transformer, HT Panels and main LT Panel at manufacturer’s works.
236NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
237PUMPING PLANT AND ACCESSORIES FOR CCWR TO OHT ZONE-I
238SITC of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
2391250 LPM / 33 Mtr. HEAD / 20 HP MOTOR (1w+1s)
240SITC of DI/DF 150mm Main piping complete with suitable size and quantity required for delivery side, bye pass arrangement and 150mm common Header upto 1 m. outside the pump house along with 150 x 150 x 150 mm DI/AF Tee (2 Nos), 150 mm DI/DF bend (01 Nos), 150 mm blind flange (01 Nos), DI/DF Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (03Nos) etc. complete in all respect as per site conditions.
241DI/DF Butterfly valves as per IS 13095/ BS 5155 Standard drilled to IS 1538 Rated to PN 1.6, Body and disc in DI IS 1865 GR 500/7 , EPDM Rubber seat ,SS410 shaft ,Flange drilling- IS:1538, Electrical Actuator(On/off) duty with Integral starter,415 V 3 Phase 50 hz
242150mm for pumps
243Motor operated actuator with sluice valve :- SITC of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
244Actuator with Sluice Valve of size :- 150mm for common header
245Actuator with Sluice Valve of size :- 350mm for CCWR inlet
246Non return valve :- SITC of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
247150 mm Dia for pumps
248150 mm Dia for common header
249CE/UL Certified Electromagnetic flow meter :- SITC of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
250Size 150mm for common header
251Size 350mm for CCWR inlet
252ELECTRICAL ITEMS:-
253Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 10 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
254SITC OF MOTOR CONTROL CENTER (MCC) PANEL :-Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting ofINCOMMING SECTION100A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION63 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 2 No, Spreader Links & Extended ROH for MCCB - 2 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A
255SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 20 HP / 15 KW
256SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 17 KVAR
257SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
258100 Amp Rating
259CE/UL Certified level transmitter for CCWR :- SITC of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
260CE/UL Certified Pressure transmitter for pumps,common header:- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
261SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
262SITC of 3Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
263Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness
264Supply and fixing of Cable trench Chequerred plate
265SITC of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
266SITC of Internal & External electrification of pumping station :-
267Indoor Lighting
268Surface Mounting
269Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
270Suspended Mounting / Surface Mounting
271High Power LED Flood Light 100W
272Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
2731200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
274Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
275450mm sweep (900/1400 RPM)
276Outdoor Lighting
277Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system. ( For MCWR )
278Compact Solar LED Street Light- 90W(MONO) 18V / 12.8V 42Ah /60W
279High Mast Light System
280SITC of solar street light 110 watt all in one wall/ pole mounted battery capacity 12.8 v/42 ah ( Lethium iro battery solar panel 12 v /120 watt ( mono crystalline module )
281SITC of 12.5 mtr High mast two section top 150mm dia bottom 410mm dia 4.3mm thick without motor with fabricated bucketer system for 04 No. solar light bracket foundation bucket movement up and down for maintenance through manual gear system ( Octagonal in shape GI plated 85 micron hot dip plated with bottom plate thickness 25mm and 08 No. foundation bolt appropriate sizer.
282SITC Solar light with rcc foundation structure 1500 mm x 1500 mm x200mm base colmn size 75 mm x750 mm 900 mm with 08 no 24 mm x 750 mmstud with grouting plate
283SITC of Light arrestor with earthing complete
284Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
285160 KVA SUB STATION AT CCWR
286Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.(d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
287Supply of 50 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
288Supplying of 160 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x150sqmm XLPE cable of 33 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
289Supplying of cubicall type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-(I) Incoming : 2 Nos 400 Amps MCCB of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB. (a) Independent manual spring closing mechanism- 1 No.B10(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set.(c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II) Bus Couplers :1Nos. 630Amps of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 as amended upto date complete with following accessories for each ACB:(a) Independent manual spring closing mechanism- 1 No.(b) Breaker ‘ON’ indicating light with back up 2 A HRC fuse test terminal block, fuses, circuits contactors for positive electrical interlocking of breakers, etc. as required- 1 set.
290(III) Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1Sec .(IV) Interlocking :Electrical through advance contacts in MCCB’s (incomers & bus couplers) and mech- anical (castel key) interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(V) Outgoing :-(a) 1 Nos. 160Amp 4 Pole MCCB Microprocessor based (Ics = kA upto 433 V)/SFU with HRC fuse (BC : 80 kA)(b) CT’s of ratio 10/5Amps 4Nos.4Set (1 set of 2 Nos.)(c) Analog 96 mmsq/Digital* type ammeter (0-100Amp) with selector switch set (VI) Outgoing :- (a) 2 Nos. 100 Amp 4 Pole MCCB Microprocessor based (Ics = kA upto 433 V)/SFU with HRC fuse (BC : 80 kA)(b) CT’s of ratio 10/5Amps 4Nos.4Set (2 set of 2 Nos.)(c) Analog 96 mmsq/Digital* type ammeter (0-100Amp) with selector switch set
291Supply and laying of 650/1100 volt grade 240sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T panel (1x3½x240 sq mm)
292Supply and laying of 650/1100 volt grade 25sq mm 3½ core PVC Armoured Aluminium cable from L.T panel to MCC Panel at Zone-1,3 (1x3½x25 sq mm)
293Supply and laying of 650/1100 volt grade 50sq mm 3½ core PVC Armoured Aluminium cable from L.T panel to MCC Panel at Zone-2 (1x3½x50 sq mm)
294Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
295Installation and commissioning of 11 KV/0.4 KV substations including HT Panels and L.T. main control panel including all labor T&P complete in all respect.
296Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
297Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core for 11 KV H.T. XLPE cable
298Provision for routine testing of equipments such as transformer, HT Panels and main LT Panel at manufacturer’s works.
299NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
300PUMPING PLANT AND ACCESSORIES FOR CCWR TO ZONE-II
301SITC of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
3023300 LPM / 39 Mtr. HEAD / 50 HP MOTOR (1w+1s)
303SITC of DI/DF 200mm Main piping complete with suitable size and quantity required for delivery side, bye pass arrangement and 200mm common Header upto 1 m. outside the pump house along with 200 x 200 x 200 mm DI/AF Tee (2 Nos), 200 mm DI/DF bend (01 Nos), 200 mm blind flange (01 Nos), DI/DF Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (03Nos) etc. complete in all respect as per site conditions.
304DI/DF Butterfly valves as per IS 13095/ BS 5155 Standard drilled to IS 1538 Rated to PN 1.6, Body and disc in DI IS 1865 GR 500/7 , EPDM Rubber seat ,SS410 shaft ,Flange drilling- IS:1538, Electrical Actuator(On/off) duty with Integral starter,415 V 3 Phase 50 hz
305200mm for pumps
306Motor operated actuator with sluice valve :- SITC of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
307Actuator with Sluice Valve of size :- 200mm for common header
308Non return valve :- SITC of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
309200 mm Dia for pumps
310200 mm Dia for common header
311CE/UL Certified Electromagnetic flow meter :- SITC of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
312Size 200mm for common header
313ELECTRICAL ITEMS:-
314Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
315SITC OF MOTOR CONTROL CENTER (MCC) PANEL :-Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting ofINCOMMING SECTION160A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION100 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 2 No, Spreader Links & Extended ROH for MCCB - 2 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A
316SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 50 HP / 37 KW
317SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 28 KVAR
318SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
319160 Amp Rating
320CE/UL Certified Pressure transmitter for pumps,common header:- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
321SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
322Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness
323Supply and fixing of Cable trench Chequerred plate
324PUMPING PLANT AND ACCESSORIES FOR CCWR TO ZONE-III
325SITC of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
3261200 LPM / 48 Mtr. HEAD / 25 HP MOTOR (1w+1s)
327SITC of DI/DF 150mm Main piping complete with suitable size and quantity required for delivery side, bye pass arrangement and 150mm common Header upto 1 m. outside the pump house along with 150 x 150 x 150 mm DI/AF Tee (2 Nos), 150 mm DI/DF bend (01 Nos), 150 mm blind flange (01 Nos), DI/DF Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (03Nos) etc. complete in all respect as per site conditions.
328DI/DF Butterfly valves as per IS 13095/ BS 5155 Standard drilled to IS 1538 Rated to PN 1.6, Body and disc in DI IS 1865 GR 500/7 , EPDM Rubber seat ,SS410 shaft ,Flange drilling- IS:1538, Electrical Actuator(On/off) duty with Integral starter,415 V 3 Phase 50 hz
329150mm for pumps
330Motor operated actuator with sluice valve :- SITC of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
331Actuator with Sluice Valve of size :- 150mm for common header
332Non return valve :- SITC of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
333150 mm Dia for pumps
334150 mm Dia for common header
335CE/UL Certified Electromagnetic flow meter :- SITC of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
336Size 150mm for common header
337ELECTRICAL ITEMS:-
338Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 10 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
339SITC OF MOTOR CONTROL CENTER (MCC) PANEL :-Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting ofINCOMMING SECTION100A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION63 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 2 No, Spreader Links & Extended ROH for MCCB - 2 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A A
340SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 25 HP / 18.5 KW
341SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 18 KVAR
342SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
343100Amp Rating
344CE/UL Certified Pressure transmitter for pumps,common header:- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
345SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
346Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness
347Supply and fixing of Cable trench Chequerred plate
348Automation For Intake Well
349CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
350GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
351CE/UL Certified Intelligent energy meters
352CE/UL Certified Surge protector for control panel
353CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
354CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
355Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
356Cable
357(i) Complete cabling upto 3 Pumps
358Security Survelliance IP Camera with recorder (optional)
359Installation, commissioning & testing
360Local Control Station at WTP
361CE/UL & BIS Certified industrial grade LED Monitor 65\\" with latest configuration as per specification
362Desktop / PC with i5/i7 processor for as per technical bid documents
363CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
364Full development version of required TAGS SCADA Software with customization of software for LCS as per requirement as per spec. mentioned in technical bid documents.
365CE/UL certified local control room PLC with redundant CPU & power supply at LCS in IP 54 enclouseras per spec. mentioned in technical bid documents.
366GSM based wireless/Broadband/Equivalent communication system for PLC capable to transfer & received data & gather from remote sites to control station, all accessories included signal enhancer anternna along with running expenses till DLP
367CE/UL Certified firewall for network protection
368Air conditioner 1.5 ton capacity 5 star rating with automatic voltage stabilizer
369SURGE PROTECTOR FOR ETHERNET communication protection.
370Furniture for LCS room as per requirement
371CE/UL certified industrial grade Ethernet Swtich
372Cannon/HP or equivalent Laser printer 1018 or equivalent
373Security Survillance IP Camera with recorder (Optional)
374Installation, Commissioning & testing including required furniture, A/C etc.
375AUTOMATION FOR MCWR AT WTP
376CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
377GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
378CE/UL Certified Intelligent energy meters
379CE/UL Certified Surge protector for control panel
380CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
381CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
382Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
383Turbidity Analyzer at CWR
384PH Analyzer
385Chlorine Analyzer
386Cable
387(i) Complete cabling upto 3 Pumps
388Security Survelliance IP Camera with recorder (optional)
389Installation, commissioning & testing
390AUTOMATION FOR CCWR
391CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
392GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
393CE/UL Certified Intelligent energy meters
394CE/UL Certified Surge protector for control panel
395CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
396CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
397Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
398Turbidity Analyzer at CWR
399PH Analyzer
400Chlorine Analyzer
401Cable
402(i) Complete cabling upto 3 Pumps
403Security Survelliance IP Camera with recorder (optional)
404Installation, commissioning & testing
405INSTRUMENTATION AGAINST ZONE-1 ( DMA-1 Nos ) EX. OHT 500 KL
406Supply of Motor operated actuator with sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater with sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
407250 mm dia
408Supply of flow control valve with electric actuator for flow controling, pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
409250 mm ( DMA-1 )
410Supply of Isolation valve with electric actuator for flow controling, pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
411250 mm ( DMA-1 )
412Supply of DI mechanical joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia at DMA inlet.
413250 mm ( DMA-1, Ex.OHT Outlet )
414Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
415Supply of CE/UL Certified Electromagnetic flow meter at DMA inlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make for remote places of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable and also interfacing with PLC panel.
416250 mm ( DMA-1 )
417Supply of CE/UL Certified Pressure transmitter at DMA inlet :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
418Supply of Dosing System at DMA inlet :-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )
419Supply of Residual chlorine analyser / meter at DMA inlet :-Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator andgives 2 outputs one to Local display & other to PLC including Mounting arrangement.Overall Range : 0 - 8 mg/l (ppm)Accuracy : 2% of full scaleSupply Voltage : 230 V ac+B7Output : 4-20 mAMembrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.
420Installation, cabling of OHT including all equipments with all power and control cable,testing and commissioning complete in all respect.
421INSTRUMENTATION AGAINST ZONE-2 ( DMA- 3 Nos ) NEW OHT 1350 KL
422Supply of Motor operated actuator without sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater without sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
423350 mm dia
424Supply of flow control valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
425300 mm ( DMA-1 )
426250 mm ( DMA-2 )
427200 mm ( DMA-3 )
428Supply of Isolation valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
429300 mm ( DMA-1 )
430250 mm ( DMA-2 )
431200 mm ( DMA-3 )
432Supply of DI mechanical joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia at DMA inlet.
433300 mm ( DMA-1 )
434250 mm ( DMA-2 )
435200 mm ( DMA-3 )
436Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
437Supply of CE/UL Certified Electromagnetic flow meter at DMA inlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
438300 mm ( DMA-1 )
439250 mm ( DMA-2 )
440200 mm ( DMA-3 )
441Supply of CE/UL Certified Pressure transmitter at DMA inlet :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
442Supply of Dosing System at DMA inlet :-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )
443Supply of Residual chlorine analyser / meter at DMA inlet :- Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator andgives 2 outputs one to Local display & other to PLC including Mounting arrangement.Overall Range : 0 - 8 mg/l (ppm)Accuracy : 2% of full scaleSupply Voltage : 230 V acOutput : 4-20 mAMembrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.
444Installation, cabling of OHT including all equipments with all power and control cable,testing and commissioning complete in all respect.
445INSTRUMENTATION AGAINST ZONE-3 ( DMA- 2 Nos ) NEW OHT 500 KL
446Supply of Motor operated actuator without sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater without sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
447250 mm dia
448Supply of flow control valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
449200 mm ( DMA-1,2 )
450Supply of Isolation valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.
451200 mm ( DMA-1,2 )
452Supply of DI mechanical joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia at DMA inlet.
453200 mm ( DMA-1,2 )
454Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
455Supply of CE/UL Certified Electromagnetic flow meter at DMA inlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
456200 mm ( DMA-1,2 )
457Supply of CE/UL Certified Pressure transmitter at DMA inlet :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
458Supply of Dosing System at DMA inlet :-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )
459Supply of Residual chlorine analyser / meter at DMA inlet :- Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator andgives 2 outputs one to Local display & other to PLC including Mounting arrangement.Overall Range : 0 - 8 mg/l (ppm)Accuracy : 2% of full scaleSupply Voltage : 230 V acOutput : 4-20 mAMembrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.
460Installation, cabling of OHT including all equipments with all power and control cable,testing and commissioning complete in all respect.
461ESTIMATE FOR AUTOMATION OF DMA
462CE & UL Certified PLC/RTU in IP 54 enclosure suitable to Communicate with GSM based modem unit with CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
463GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
464CE/UL Certified Intelligent energy meters
465CE/UL Certified Surge protector for control panel
466CE/UL Certified 1 KVA UPS with batteries as per technical bid documents
467CE/UL Certified 7\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
468Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
469Cable
470(i) Complete cabling
471Security Survelliance IP Camera with recorder (optional)
472Installation, commissioning & testing
4733 Month Trial run for intake well,MCWR,CCWR and CWR including operation and chemical charges. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56451168
AUTHORITY Government Departments
TENDER VALUE 31.54 Crore
LAST DATE 31-07-2026
Authority
Authority Name Uttar Pradesh Jal Nigam
Work Description Tender for Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Naraini Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Banda Under Amrut 2.0 Programme On Turn-Key Basis
Basic Detail
Tender No 965/F-03/129 Dated 09.07.2026
Bidding Type Tender
Location
City Banda
State Uttar Pradesh
Key Dates
Publish Date 14 Jul 2026
Submission Date 31 Jul 2026
Open Date 31 Jul 2026
Finance
Tender Value 31.54 Crore
Tender Fee 23600
EMD 31.54 Lakhs
Exemption Not Available
Document List
1722b318-fb28-4cd5-8092-ebf1e22c4708.html
BOQ_2193646.xls
NarainiTD2ND.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 14, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 31, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 16 days
Jul 31, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 16 days

Tender Documents

Download All (ZIP) ↓
html

1722b318-fb28-4cd5-8092-ebf1e22c4708.html

xls

BOQ_2193646.xls

pdf

NarainiTD2ND.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders