Tender For Repair And Maintenance Of Ht Oh Line, Ug Cable, Earthing, Ht Cable Joint, Insulator, Lightening Arrester And Allied Works In North Area And Bhagat Line Area Under Age E/M (E/S) At Ge (U) Meerut Cantt
Tender Overview
Project Description
Tender for Repair And Maintenance Of Ht Oh Line, Ug Cable, Earthing, Ht Cable Joint, Insulator, Lightening Arrester And Allied Works In North Area And Bhagat Line Area Under Age E/M (E/S) At Ge (U) Meerut Cantt
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 18-Aug-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 24-Aug-2026 |
| 2 | 11-Aug-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 18-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply laying & testing in replacement of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminum conductor,11000 volts grade, of size 3 core 95 Sqmm including taking out of old HT cable from trenches all as specified and directed. |
| 2 | All as per item No-01 above 120 Sqmm 3 core |
| 3 | All as per item No-01 above 150 Sqmm 3 core |
| 4 | All as per item No-01 above 185 Sqmm 3 core |
| 5 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for laying cables / poles foundation / stay assembly and getting out in soft soil all as specified and directed. |
| 6 | Removing excavated material not exceding 50 m and depostingwhere directed at a level not exceding 1.5 m above the starting point complete all as specified and directed. |
| 7 | Returning filling in including spreading levelling watering and well ramming in layers n.exc 25cm complete all as specified all as directed. |
| 8 | Material and labour for Sand cushioning to under ground cable providing with a layer 8cm thick before laying the cable and 15 cm thick after laying the cable complete all as specified and as directed.Note:- Only punned thickness will be measured for the purpose of payment. |
| 9 | M & L for Un-reinforced pre cast concrete covers class HV type 300mmx 180mm x 40mm size factory made for cable protection complete all as specified and directed. |
| 10 | Supply and fixing in replacement of GI tubing light grade galvanised with all fittings laid in trenches/ on pole/ wall/ floor etc for protection of cable complete all as spd and directed of following sizes:- |
| 11 | 100 mm bore |
| 12 | 80 mm bore |
| 13 | M & L for boring in any type of soil under road 1.5 Mtr below the top surface of road by convential method complete for passing through 80mm to 100mm dia GI pipe and filling earth after laying of pipe including disposal of surplus soil complete all as specified and directed. Note :- Pipe will be measured and paid for separately . Any damage to existing cables of any type and road will made good by the tenderer without any extra payment. |
| 14 | Material and labour for finding out the cable fault of any size of cable upto 11 KV underground cable (HT and LT and of any capacity of cable with the help of cable fault loacator mounting on vehicle and with nessary disconnection of cable from two ends and making connection by jointing after repairs and having the following items with electrician at site to find fault of up to length of 10 KM cable complete all as specified and directed by Engr-in-Charge with help of the following accessores- (a) Surge Generator with accessories(b) Head Phone(c) Pin Point Set T-505 with accessories(d) Earthing cable with clamp (e) Cable fault Locator T-905 with accessories (f) TC-808 with accessories (g) Soldering Iron/wire/capacitor unit/capacitor connecting cables/ power cable/nose plier. Notes:- Excavation for the cable fault shall be done by the contractor by his own arrangement. |
| 15 | Supply and fix cable jointing kit 11 KV cable for indoor termination heat shrink type joint complete joint material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 50 to 95 Sqmm complete all as specified and directed. |
| 16 | Supply and fixed cable jointing kit 11 KV cable for outdoor termination heat shrink type joint complete joint material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 50Sqmm to 95 Sqmm complete all as specified and directed. |
| 17 | Supply and fix cable jointing kit 11 KV cable for indoor termination heat shrink type joint complete joint material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 120 to 185 Sqmm complete all as specified and directed. |
| 18 | Supply and fixed cable jointing kit 11 KV cable for outdoor termination heat shrink type joint complete joint material and accessories suitable for 3 core XLPE armoured AL conductor cable of size 120Sqmm to 185 Sqmm complete all as specified and directed. |
| 19 | Supply and fix cable jointing kit for 11 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 Sqmm to 185 Sqmm, Indoor/Outdoor type complete all as specified and directed. |
| 20 | Supply and fix cable jointing kit for 11 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 Sqmm , Indoor/Outdoor type complete all as directed. |
| 21 | Earthing complete with galvanised iron plate electrode 600 x 600 x 6.00mm thick GI earthing lead burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with the top edge of the plate at a depth not less than 1.5 mtr from below normal GL, connected to and including Galvanised iron strip 32x6 mm as earthing lead by means of nuts, bolts, washers, checknuts of galvanised iron and connected to earthing test point all as shown in electric plate No. 3 of SSR Part l of 2010 and as specified or indicated and testing on completion including excavation / earth work in any type of strat PCC (1:3:6) type C1 earthing chamber, precast slab 50 mm thick in cement cioncreat (1:2:4) type B1 (Reinforced with welded steel wire fabric (XPM)) weight not less than 4 Kg/sqm,cast iron frame, funnel with wire mesh, including GI earth strip with GI protection pipe of 40mm medium grade 7.5 meter long etc complete and testing on completion all as specified and directed.Note: 1. Rate quoted shall deemed to include cost of excavation in any type of strata, RFR and removal upto 50metre, PCC pit, funnel and RCC cover plate.2. GI strip above 7.5m will be measured and paid seperately.3. Earth resistance not exceeding 5 ohm. |
| 22 | Treeming of trees branches both side 3.0 meters wide of LTover head line and HT over head line. During the treeming first take proper shutdown by informing the engr-in-charge. |
| 23 | M & L for Restreaching tightening and fixing in position, the existing OH ACSR conductor LT/HT Line of any wire by loosing and taking down existing binding wire from the insulator of any size of ACSR conductor and bring it to required sag including new binding wire and tightning of cross arm on each pole including trimming of tree branches. Note:- Span length(between pole to polr (any Nos of wires) of conductor shall be measured in running meter unit combined. |
| 24 | M&L for replacement of cross arms, bracings, supports, clamps and back plates fabricated from strucural steel sctions including, nuts, bolts, washers, welding, bending cold or hot, driling holes for bolts, in any shape or sizae as indicated or directed and inclusive of one primer coat , one under coat and one finishing coat of paint complete all as specified and directed. |
| 25 | Supply streatching and fixing in replacement of Alluminium conductor steel reinforced (ACSR) of any size for OH lines of LT/HT poles including Al winding wire 14SWG, jumper and line taps etc complete all as specified and directed. |
| 26 | M&L for replacement of pin type porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 Volts complete all as specified and directed. |
| 27 | S & F in replacement of disc insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type brown complete with GI washers ,nut and bolts suitable for working pressure 11000 Volts complete all as specified and directed. |
| 28 | M & L for compelte Stay assembly of 20 mm dia complete with accessories on existing pole all as specified and directed by Engr-in- charge as shown in electrical plate No. 1. Note :- Loop type insulator, stay clamps, excavation and concrete measured separately. |
| 29 | Supply in replacement, installation, commissioning and testing of switch air break gang operated HT 11000 V grade triple pole with 9 insulators, 200 A capacity current rating complete with drop out fuse assembly with fuse carrier, fuse elements, mounted on insulators and steel frame mechanically operated mechanism worked from ground level consisting of operating rod 25 mm bore, GI pipe, light grade of suitable length worked from ground level and with locking arrangement with flat iron clamps 50 x 6 mm including MS channel of suitable size and length for fixing GO/DO including nuts, bolts and washers complete all as specified and directed. |
| 30 | M&L for replacement of PG clamps, parallel grove clamps, tee clamps & GI nut, bolts of required size other connectors for connecting ACSR dog conductors for jumpring all as required at site complete all as specified and directed. |
| 31 | Cutting bushes, levelling the area around E/M installation, sub stations, pole structure etc including surface excavation in soft soil not exceeding 30 cm deep and avearaging 15 cm deep and getting out roots etc and throw away not less than 50 mtr from the site and making good all as specified and directed. |
| 32 | Removal old broken (U/S) Earthing pits at site and M & L for PCC (1:3:6) type C-1 (using 20 mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate), rainforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle etc.for construction of damaged earth pits etc. complete all as specified & directed. |
| 33 | Material & labour for earth pit cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate), 320mm x 320mm x 40mm thick, cover reinforced with 8mm dia TMT bars 3 Nos both way with 08mm dia MS round bar handle with and including necessary form work complete all as specified & directed. |
| 34 | S & F in replacement of danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts, nuts of approved size for HT 25x20 cm size including dismantling old one. |
| 35 | Dismantling old defective/peeled of Insulating Mat and M&L for Elastomer Insulating Mats for Electrical Purposes Class A/voltage grade upto 11 KV (AC) as per IS : 15652:2006 with ISI mark of thickness 2.5 mm+ 10% of approx of size (2 x 1 mtr )along with suitable adhesive /chemibound resin waterproofing compound and sealing material all as per SSR Part -I clause 19.23 A1 to 19.23 A-7 including dismatling of old difective / peepled of insulating material complete all as specified and directed. |
| 36 | M&L for painting with two coats of synthetic aluminium paint on complete steel structure after scrapping the old paint from steel structures of 33 KV Roorkee road and Bhagat line MRS (33/11 KV Sub Stn) structure complete all as specified and directed. |
| 37 | M&L for cutting of black top cover of existing road up to 1 mtr depth and 60 cm wide for laying of UG cable and pipe line, refilling and making good after laying UG cable and pipe line with PCC 1:3:6 uptp 30 cm from top of the road surface complete all as specified and directed. |
| 38 | Supply and fix in replacement for feeder pillers box factory made -out door type made out of MS sheet (CRCA) of thickness not less that 3 mm. of size 150x65x90cm with Aluminium bus bar strip 3 Nos of size 130 cm in length 4 cm in width and 05mm in thickness suitable for 11000 volt mounted on HT porcelain insulator front opening door two leaf braced with hinged, mounted on 4 Nos of angle iron 50x50 mm duly welded with box and grouted in PCC block of size 30cmx30cmx 15cm in concrete 1: 3 : 6. Top of box MS sheet duly bent in/slope, tapper with projection of 30 mm on all side, weather/vermin proof with high quality of rubber beeding on panel door, cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with smoke grey stove enameled paint 2 coat over a primer coat all as directed by Engr-in-Charge. |
| 39 | Supply and lay Graded coarse aggregate of size 20 mm dia in outdoor sub-station yards completed all as specified and directed. |
| 40 | Dismantling the existing unserviceable mild steel swaged poles/ strut from ground after necessary excavation etc and removing including making good disturbed ground complete all as specified & directed. Note:- Excavation and earthwork shall be deemed included in the unit rate quoted by bidder. |
| 41 | Supplying, transporting, erecting and fixing Steel tubular swaged poles type 410 SP-55 ( 11 metres long) complete with cast iron / Mild steel base plate, CI finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work in soft/ loose soil , PCC 1:3:6 type C2 in foundation and around poles and PCC 1:2:4 type B1 as in plinth block duly finished even and smooth without using extra cement, disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting exposed surafces steel tubular poles with two coats of aluminium paint over one coat of red oxide primer and and black bituminous paint on steel surafces embedded in concrete and providing 300 mm wide bands (5 bands/ straps with fluorescent synthetic enamel paint in alternate colour of black and white from plinth block and numbering of poles , painting embedded portion of poles with one coat of bituminous paint complete all as specified and shown in drg No.TD/EM/1 and directed.. PCC and earth work shall be measured and paid seperately. |
| 42 | M & L for PCC (1:3:6) type C2 (using 40mm graded stone aggregated) as in foundation, filling and mass concrete using necessary form work complete all as specified and directed. |
| 43 | M & L for PCC (1:4:8) type D2 (using 40mm graded stone aggregated) as in foundation, filling and mass concrete using necessary form work complete all as specified and directed. |
| 44 | All as per item srl No 05 above but in depth beyond 1.5 Mtr and n. exc 3.00 Mtr and taking out in any type of soil complete all as specified and directed. |
| 45 | S & F in replacement of HT lightening arrestor metal oxide type (gap less) heavy duty triple pole for 33 KV overhead line ,36 KV rated highest system voltage, long duration distribution discharge class type, IP 55 Degree of protection, 100(kVp) at 65 kA High current impulse withstand with normal discharge current of 10 KA complete with all fittings conforming to IS: 3070 part-3 effectively connected with earthing system complete all as specified and directed. |
| 46 | Supply , install, testing and commissioning in replacement of existing unsv outdoor type, 33 KV gang operated switch, rotary type, double break of current rating upto 400 Amps, triple pole each pole consisting of galvanised steel base, HT insulators as per IS, non ferrous knife and spray, loaded contacts, arching horns of adequate section to break magnetizing current of the transformers, horizontal pipe of adequate length for phase seperation adequate length of GI pipe for operation from ground level and operating handle with locking arrangement complete in both ON and OFF position. All ferrous parts hot dipped galvanised and non ferrous heavily tinned to with stand weather suitable for vertical mounting complete all as specified and directed. |
| 47 | Earthing complete with copper plate electrode 600 x 600 x 3.15 mm thick copper earthing lead burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with the top edge of the plate at a depth not less than 1.5 mtr from below normal GL, connected to and including copper strip 20 x3 mm as earthing lead by means of nuts, bolts, washers, checknuts of galvanised iron and connected to earthing test point all as shown in electric plate No. 3 of SSR Part l of 2010 and as specified or indicated and testing on completion including excavation / earth work in any type of strat PCC (1:3:6) type C1 earthing chamber, precast slab 50 mm thick in cement cioncreat (1:2:4) type B1 (Reinforced with welded steel wire fabric (XPM)) weight not less than 4 Kg/sqm,cast iron frame, funnel with wire mesh, including copper earth strip with GI protection pipe of 40mm medium grade 7.5 meter long etc complete and testing on completion all as specified and directed.Note: 1. Rate quoted shall deemed to include cost of excavation in any type of strata, RFR and removal upto 50metre, PCC pit, funnel and RCC cover plate.2. Copper strip above 7.5m will be measured and paid seperately.3. Earth resistance not exceeding 5 ohm. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
TodayCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender