Tender For Installation Of 3X63kva Dts Along With Ht/Lt Network At ( Herpora Khiram Bala,Bonpora Khudpora Khiram Dargah,Wagay Mohalla Durpora Khiram Gujrat), Creation Of 1X100 Kva S Station At Astan Nard Amanpati Sheikh Pora Sallar, And Augmentation
Tender Overview
Project Description
Tender for Installation Of 3X63kva Dts Along With Ht/Lt Network At ( Herpora Khiram Bala,Bonpora Khudpora Khiram Dargah,Wagay Mohalla Durpora Khiram Gujrat), Creation Of 1X100 Kva S Station At Astan Nard Amanpati Sheikh Pora Sallar, And Augmentation Of 1X100kva By 1X200 Kva At Wanender Sirhama Andshifting Of Transformer 250Kva At Hergam Sirhama B
BOQ
| Sl. No. | Item Description |
| 1 | Installation of 3x63KVA DTs along with HT/LT Network at ( Herpora Khiram Bala,Bonpora Khudpora Khiram Dargah,wagay Mohalla Durpora Khiram Gujrat), Creation of 1x100 KVA S Station at Astan Nard Amanpati Sheikh Pora sallar, and Augmentation of 1x100KVA by 1x200 KVA at Wanender Sirhama andShifting of transformer 250KVA at Hergam Sirhama B |
| 2 | Dismantalling of existing substation stracture ,Loading and Shifting to place near by ,installtion and commissioning of existing 250 KVA DT(complete Job) |
| 3 | Supply,loading, unloading at site ,Carriage, Installation, testing & commisioing of 200 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Almunium Gland Plate |
| 4 | Supply,loading, unloading at site ,Carriage, Installation, testing & commisioing of 100 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Almunium Gland Plate |
| 5 | Supply,loading, unloading at site ,Carriage, Installation, testing & commisioing of 63 kVA,11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Almunium Gland Plate |
| 6 | Loading and carriage of existing 100 KVA DT from Waniander Sirhama to Divisional stores Bijbehara |
| 7 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 9mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards |
| 8 | Supply,loading, unloading at site Erection, testing & commissioning of S.T Pole 8mtr Long SP-15 with base plate & cap for LT. Strictly as per REC standards |
| 9 | Supply,loading , unloading at site ,Laying, stringing, tensioning & binding of ACSR 30mmsq (weasel) Conductor. |
| 10 | Supply/Fixing & commissioning of GI Channel/Angle/Flat of Sizes including clamps |
| 11 | Supply,loading , unloading at site ,Laying, stringing, tensioning & binding of ACSR 50mmsq (Rabbit) Conductor. |
| 12 | Supplying and fixing of GI Channel “V’ cross-arm (75 x 40x6mm) with GI Angle Pole Top Bracket (50x50x6 mm) including back clamps of 50X8 mm for fixing V-Cross arm and pole top bracket without making holes in the ST pole as per REC standard for single pole structure.@18 kg each |
| 13 | Supplying and fixing of pole Earthing Complete by Spike Earthing Rod 20mm 2.5 Mtr long with GI strip (25x3)mm to each LT and HT pole |
| 14 | Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened. |
| 15 | Supply,fixing, testing & commissioning of 11KV GO Set, AB Switch as per IS Standards |
| 16 | Supply,fixing, testing & commissioning of 11KV DO Fuse Set as per IS Standards |
| 17 | Supply,fixing, testing & commissioning of 11KV LA Set Gap less as per IS Standards |
| 18 | Supply,fixing, testing & commissioning of 11KV Pin Polymer Insulators with GI pins complete. |
| 19 | Cement bottoming 1:2:4 mix as per REC Standards 0.48cum/pole |
| 20 | Supply and fixing of 70 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type |
| 21 | Supply and fixing of 120 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type |
| 22 | Supply and fixing of 240 mm² Single-Core Cable, 1.1kV Grade, XLPE un armoured FRLS type |
| 23 | Providing & fixing of 11 kV polymeric composite disc insulator 12 kV , min failing load 45 kN, lighting impulse 75 kV positive and 80 kV negative, creepage distance 320mm |
| 24 | Providing & fixing of LT Shackles Insulator with GI mukhi clamps including Nuts & Bolts |
| 25 | Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm No.minal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 26 | Providing and Fixing of GI Nuts and Bolts. |
| 27 | Providing and Fixing of Wedge Connectors / PG Clamp |
| 28 | Supply, installtion of Danger Plates with Clamps |
| 29 | Providing and fixing of GI Barbed Wire for Anti Climbing |
| 30 | Cement bottoming 1:2:4 mix as per REC Standards 0.4cum/pole |
| 31 | Supply, Installation, Testing and commissioning of LT Fuse Unit as per the approved KPDCL Drawings Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
TodayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender