Tender For Work Of Installation Of Air Conditioning Plants In All The Court Rooms And Rest Rooms Of The District Judge And All The Additional District Judges (Except The 42 Court Rooms And Rest Rooms Already Established) In The District Court, Lucknow.
Tender Overview
Project Description
Tender For Work Of Installation Of Air Conditioning Plants In All The Court Rooms And Rest Rooms Of The District Judge And All The Additional District Judges (Except The 42 Court Rooms And Rest Rooms Already Established) In The District Court, Lucknow.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 14-Jul-2026 | BOQ Corrigendum Letter | Other | 30-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | PART-ASupplying, Installation, Testing and Commissioning of 2 ton capacity Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface/concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) , i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz, 1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll/rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS/International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 52 °C (out door ambient temperature). |
| 2 | Supplying, Installation, Testing and Commissioning of 1.5 ton capacity Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface/concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) , i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz, 1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll/rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 °C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply: Electrical cable IS 694 or IS 9968 temperature sensing control IS/International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 52 °C (out door ambient temperature). |
| 3 | SITC of suction/discharge pipe line in split A.C unit upto 2.0 ton capacity including brazing,nitrile,rubber insulation 6 mm thick class\\"O\\" etc.complete 3/8\\"(9.50 mm) and 5/8\\" (15.90mm) |
| 4 | SITC of suction/discharge pipe line in split A.C unit upto 1.5 ton capacity including brazing,nitrile,rubber insulation 6 mm thick class\\"O\\" etc.complete 1/2\\"(12.70 mm) and 1/4\\" (6.40mm) |
| 5 | Supply of wall mounted copper wounded Voltage stablizer 5 KVA Capacity |
| 6 | Supply of wall mounted copper wounded Voltage stablizer 4 KVA Capacity |
| 7 | Supply and laying of heavy duty PVC plastic braided 32mm OD flexible pipe for condensed water with dipping accessories complete |
| 8 | S/F of Inter connecting Electrical cable for A.C (2.5 Sq. mm 3 core) for Indoor to Stablizer connection |
| 9 | S/F of Inter connecting Electrical cable for A.C (2.5 Sq. mm 4 core) for Indoor to outdoor connection |
| 10 | Fabrication of M.S stand for Outer unit of A.C withfixing on wall with all material & labour complete in all respect |
| 11 | Supply & Fixing of Outdoor Cage for 1 ton/1.5/2 Ton A/C |
| 12 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required for A.C. |
| 13 | Modular type MCB protected socket with sheet steel enclosure for A.C. unit |
| 14 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 15 | 4 way (4 + 12), Double door |
| 16 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
| 17 | 4 way (4 + 12), Double door |
| 18 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 19 | Single Pole |
| 20 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 21 | 63 Amp. 4 Pole MCB |
| 22 | 100 Amp. 4 Pole MCCB |
| 23 | 63 Amp. TPMCB |
| 24 | Wiring for circuit/submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
| 25 | 2 X 6 sq. mm + 1 x 4 sq. mm earth wire |
| 26 | 4 X 10 sq. mm + 2 x 6 sq. mm earth wire |
| 27 | 4 X 16 sq. mm + 2 x 6 sq. mm earth wire |
| 28 | Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 29 | 70 sq. mm 3-1/2 core |
| 30 | 400 sq. mm 3-1/2 core |
| 31 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 32 | 70 sq. mm 3-1/2 core |
| 33 | 400 sq. mm 3-1/2 core |
| 34 | Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN MCCB's (Four Pole 36 KA with thermal magnatic release)Switches Complete and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage, current and other parameters(KVA,P.F,KW etc) in each phase with touch type selector switches for different readings, instrument fuses, current transformer etc. Incoming 400 Amp. MCCB-1 Nos.Outgoing 100 Amp. MCCB-3 Nos, 63 Amp MCCB-2 Nos. (1 No. for Raushandaulla Court and 1 No. for Family Court) |
| 35 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 36 | Supply and fixing 25 mmX 5 mm GI strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with GI nut, bolt, spring, washer etc as required. |
| 37 | Supply and laying of 1800mm x 900mm x 12mm thick chequered rubber matting of tested quality. |
| 38 | Supply and fixing of fire bucket, round bottom made of G.I. sheet 9-11 litres capacity duly painted as per fire brigade design, supported on hanging bracket chained and locked, initially filled with fine river sand, water as per directions of Engineer-in-Charge. |
| 39 | Supply and fixing of shock treatment chart (prescribed under I.E. rules) duly framed with glass and supported from back with hard board or soft board with supply of all material labour T&P for proper completion of work. |
| 40 | TOTAL RS. |
| 41 | Less 5% As Per Deducted By P.F.A.D. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 14 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender