Tender For Repair /Maint Of Fire Hydrant System And Other Misc Connected Work And Repair/ Maintenance Of Standby Dg Set, Panels, Control Cables And Associated Work At Sewage Pumping Station, Stp And Water Supply Installations Under Ge (Af) Jaisalmer
Tender Overview
Project Description
Tender for Repair /Maint Of Fire Hydrant System And Other Misc Connected Work And Repair/ Maintenance Of Standby Dg Set, Panels, Control Cables And Associated Work At Sewage Pumping Station, Stp And Water Supply Installations Under Ge (Af) Jaisalmer
BOQ
| Sl. No. | Item Description |
| 1 | Supply and fixing in replacement of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard. |
| 2 | Supply and fixing in replacement of Foot valve conforming to IS 4038, supplied and installed complete of size 150 mm (6\\") dia. |
| 3 | Supply and fix in replacement of Yard hydrant Post / Stand Post 80mm Dia GI / MS both flanged type 1.5m Height with all accessories complete all as specified and directed. |
| 4 | Supply and fixing in replacement of Fire brigade inlet connection 2 way complete all as specified and directed. |
| 5 | Supply and fixing in replacement of Hydrant valve double headed complete all as specified and directed. |
| 6 | Supply and fixing in replacement of Hose reel drum 36m long complete all as specified and directed. |
| 7 | Supply and fixing in replacement of complete re-wiring and interlocking of Fire panels, repair/servicing of pump starters, cleaning of contactors terminals, checking of sensors and testing on completion complete all as specified and directed. |
| 8 | Comprehensive maint and servicing of Jockey pump of capacity 15 HP complete all as specified and directed. |
| 9 | Comprehensive maint and servicing of electrical operated fire pump of capacity 60-75 HP & Dismantling of 75 HP motor electric from foundation and pump opening the same and only serviceing of motor by cleaning internally and externally, varnishing of winding, checing of stator, greasing of bearing, fittings allignment, connecting electrically re-fixing and testing the job shall be done at plant only complete all as specified and directed. |
| 10 | M&L for rewinding of electric motor of 3 Phase, 415 Volts, Cap 75 HP,2850 LPM & 70 m head after dismantling the stator and rotor, removing burnt windings, cleaning the slots, rewinding the motor with super enamelled quality hermatic grade copper winding wire of proper gauge and number of turns as per the existing windings including numex paper, glass paper, thimble, glass sleevs, main lead, back doll, Varnish and drying in oven including fitments of thermostate protection relay and bearing of specified type, including required nut bolts (stainless steel) reassembling and air testing to ensure leak lightness of the joints complete all as specified and directed. Note :- Spares / parts to be replaced shall be measured & paid secretly under respective items. |
| 11 | Comprehensive maint and servicing of deisel engine driven fire pump including of diesel engine of capacity 60-75 HP with and including replacement of following parts :-(a) Replacement of fuel filter(b) Replacement of oil filter(c) Replacement of Engine oil(d) Replacemnt of oil seals(e) Testing of diesel engine after servicing |
| 12 | Supply and fixing in replacement of Valves, Sluice, flanged of class 1.6 PN supplied and installed complete, size 150 mm (6”) dia |
| 13 | Supply and fixing in replacement of Valves, Sluice, flanged of class 1.6 PN supplied and installed complete, size 100 mm (4”) dia |
| 14 | Supply and fixing in replacement of Valves, Sluice, flanged of class 1.6 PN supplied and installed complete, size 80 mm (3”) dia |
| 15 | Supply and fixing of Non Return butterfly Valve 150 mm bore complete all as specified and directed. |
| 16 | Supplied and laid in replacemnt of MS ERW pipe heavy grade including taking down old unsv complete including fittings 150 mm (6\\" dia). |
| 17 | Supplied and laid in replacemnt of MS ERW pipe heavy grade including taking down old unsv complete including fittings 100 mm (4\\" dia). |
| 18 | Supplied and laid in replacemnt of MS ERW pipe heavy grade including taking down old unsv complete including fittings 80 mm (3\\" dia). |
| 19 | Supply and fixing in replacement of MCCB 4 pole adjustable 200 Amps, 36 KA complete all as specified and directed. |
| 20 | Supply and fixing in replacement of MCCB 4 pole adjustable 160 Amps, 16 KA complete all as specified and directed. |
| 21 | Supply and fixing in replacement of MCCB 4 pole adjustable 63 Amps, 16 KA complete all as specified and directed. |
| 22 | Earthing complete with galvanised steel earth plate electrode60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead using galvanised iron strip 32×6mm as earthing lead and connected by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed. |
| 23 | M & L for fire hose reels 15 Mtr length 63 mm dia male female coupling duly ISI marked or ISI specification complete all as specified and directed. |
| 24 | M & L for fire hose reels 20 Mtr length 20 mm dia male female coupling duly ISI marked or ISI specification complete all as specified and directed |
| 25 | Supply and fixing in replacement of maintenance free battery with cat eye showing charged conditions OF Battery of capacity 150 `EXIDE XPRESS’ model no.FXPO MHD1500/XP1500 of exide make fully charged complete all as specified and directed. |
| 26 | S & F of diesel Pipe of disel engine as per existing pump all as specified and directed. |
| 27 | M&L for cleaning sump/ raw water tank located on the top of 15 AFH Admin block for fire fighting purpose of any capacity by taking out silt mud and vegetable growth etc in shape of sludge including residual water and disposal of the same n.exc 50 mtr away scrapping of internal surface of walls, floors with wire brush , brooms jute, appliying one coat of lime wash internally complete all as specified and directed. |
| 28 | Cleaning of 15 AFH Fire fighting SWT including bailing out stored water and removing sludge by means of man and machines, including two coat of white washing including labour for the job complete all as specified and directed. |
| 29 | 28. Testing of entire fire hydrant system in the presence of user rep team & AGE E/M (AF)/GE (AF) Jaisalmer every quaterely and complete satisfaction report of the entire system shall submit by the user to the GE (AF) Jaisalmer complete all as specified and directed.Note : Entire arrangement shall be done by the contractor for testing carried out at the periodicity of quaterely.Cost includes everything nothing shall be paid extra on this account. |
| 30 | M&L for 'B' check of DG Setsof capacity 7.5KVA to 62.5/63KVA complete as per following :-(i)Draining out engine/lubricant oil flushing including filling fresh oil afterdrain out old oil by skilled trademan of DG set including replacement of oil pan /chamber gasket .(ii)S& F in replacement lubricant oil filter element .(iii)S&F in replacement fuel filter element.(iv)S&F bypass filter element.(v)checking and applying grease to battery terminals and checking its specific gravity including topping of distilled water /acid as required. (vi) General cleaning of oil/fuel spills, grease spots etc.(vii) Checking of belt tension and adjusting as per requirment. |
| 31 | All as per Srl item No 30.00 but DG Set Cap 100KVA to 160KVA. |
| 32 | M&L for 'C' check of DG Sets of capacity 7.5KVA to 62.5/63KVA complete as per following :-(i)Draining out engine/lubricant oil flushing including filling fresh oil afterdrain out old oil by skilled trademan of DG set including replacement of oil pan /chamber gasket .(ii)S& F in replacement lubricant oil filter element .(iii)S&F in replacement fuel filter element.(iv)S&F bypass filter element.(v)checking and applying grease to battery terminals and checking its specific gravity including topping of distilled water /acid as required. (vi) General cleaning of oil/fuel spills, grease spots etc.(vii) Checking of belt tension and adjusting as per requirment.(viii) Check all electrical conditions(ix)Check pollution level(X) Check water separator and radiator cleaning with chemical.(x) Change hydraulic governor oil,Change aneroid oil, check aneroid adjustment, Replace aneroid breather.(xi) Clean radiator externally, Check fan hub/Idler and water pump/idler.(xii)Inspect units, Check Alternator/Generator,Starter etc, Check air cleaner if required(Amount of air filter will be paid separately), Evacuator valves change if required. |
| 33 | All as per Srl item No 32.00 but DG Set Cap 100KVA to 160KVA. |
| 34 | Taking out the self starter 24 Volt of DG Set capacity 100KVA to 160 KVA DG Set and shifting to workshop for rewinding of armature including replacement of unserviceable,bushes & minor parts & reinstalling the same after testing complete as specified. NOTE:-Spares replaced will be measured and paid seperatly under relevent item here in after as supply only |
| 35 | Taking out the self starter 12 Volt of DG Set Cap 7.5 KVA to 62.5/63 KVA and shifting to workshop for rewinding of armature including replacement of unserviceable,bushes & minor parts & reinstalling the same after testing complete as specified.NOTE:-Spares replaced will be measured and paid seperatly under relevent item here in after as supply only |
| 36 | Taking out the charging alternator of DG Set capacity 100 KVA to 160 KVA and shifting to workshop for rewinding of armature including replacement of rewinding unserviceable, bushes & minor parts & reinstalling the same after testing complete as specified.NOTE:-Spares replaced will be measured and paid seperatly under relevent item here in after as supply only. |
| 37 | Taking out the charging alternator of DG Sets 7.5KVA to 62.5/63 KVA DG Set and shifting to workshop for rewinding of armature including replacement of unserviceable, bushes & minor parts & reinstalling the same after testing complete as specified. |
| 38 | Servicing of radiator assembly of DG Sets 100 KVA to 160 KVA and replacement of minor parts to make it operational including descaling of tubes with solution and chemicals and compressed air blast including transportation to workshop and back and re fixing after testing complete and making it leak proof completeincluding replacement of worned out tubler hoses alongwith clip etc all as specified and directed. |
| 39 | Servicing of radiator assembly DG Sets 7.5 KVA to 62.5/63 KVA and replacement of minor parts to make it operational including descaling of tubes with solution and chemicals and compressed air blast including transportation to workshop and back and re fixing after testing complete and making it leak proof complete all as specified. |
| 40 | S&F in replacement of air cleaner filter for DG Set capacity 100 KVA to 160 KVA complete all as specified. |
| 41 | S&F in replacement of air cleaner filters for DG Set Cap 7.5 KVA to 62.5/63 KVA complete all as specified. |
| 42 | Opening the coupling of DG Set of capacity 100 KVA to 160 KVA dismantling the outer cover & taking out the fly wheel ring and shifting to workshop for repair in and including replacement of fly wheel ring by pressing machine and reinstalled the same after repair to make it fully fuctional complete all as specified. Make -Kirloskar |
| 43 | Opening the coupling of DG Set of capacity 7.5 KVA to 62.5/63 KVA, dismantling the outer cover & taking out the fly wheel ring and shifting to workshop for repair in and including replacement of fly wheel ring by pressing machine and reinstalled the same after repair to make it fully fuctional complete all as specified. |
| 44 | Servicing of fuel pump /hand pump assembly to make it fully fuctional and fixing it to its original position of DG Set in any capacity including replacement necessary element completes all as specified. |
| 45 | Repair and maintenance of FIP including replacement of Plunzers, Governer kit with pin, Nozzles P type,Head ball guide kit, Head sheet (set of 12 piece) Rock rod,Rollar bearing,Oil seal, Piston pin,Gasket kit and sleeves complete as specified and directed DG Set of 100 KVA to 160 KVA. |
| 46 | Repair and maintenance of FIP including replacement of Plunger, Governer kit with pin, Nozzles P type,Head ball guide kit, Head sheet (set of 12 piece) Rock rod,Rollar bearing,Oil seal, Piston pin, Gasket kit and sleeves complete as specified and directed DG Set of 7.5 KVA to 62.5/63KVA |
| 47 | .M&L for calibration of fuel injector assembly of DG Set of 100 KVA to 160 KVA capacity at authorised workshop including replacement of cup, barrel and plunger injector washer etc, complete all as specified. |
| 48 | M&L for calibration of fuel injector assembly of DG Set of 7.5KVA to 62.5/63KVA capacity at authorised workshop including replacement of cup, barrel and plunger injector washer etc, complete all as specified. |
| 49 | M&L cleaning of diesel tank of DG Set of any capacity including replacement of worn-out pipe line and measuring scale and fixing in original position and make it leak proof with necessary clamps complete all as specified and directed. |
| 50 | M&L in replacement of AVR complete all as specified and as directed for DG Set of capacity 100 KVA to 160 KVA. |
| 51 | S&F in replacement of AVR complete all as specified and as directed for DG Set of capacity 7.5KVA to 62.5/63KVA. |
| 52 | S&F in replacement of high pressure oil pipe ss as per sample of DG Set of any capecity |
| 53 | S&F in replacement of Bentex wheel complete suitable for self starter |
| 54 | S&F in replacement of Battery Terminals Copper.(Positive & Nagative) complete. |
| 55 | S&F in replacement of Battery Copper cable Red with plug of size 35 sqmm complete. |
| 56 | Supply & pouring in replacement of K cool super plus-50-50 PREMIX of 1 Ltrs sealed Packing all as specified. |
| 57 | Supply & pouring in replacement of engine oil for DG sets 20W/40 grade CRB plus into the oil sump complete. |
| 58 | S&Fin replacement of Fuel pipe / Hose pipe for DG Set complete all as specifed. |
| 59 | S&F in replacement fan belt set suitable for DG Set of any capacity of existing size complete all as specified and directed by Engineer –in-charge |
| 60 | S&F in replacement hinges suitable for DG Set of any capacity of existing size complete all as specified and directed by Engineer –in-charge |
| 61 | S&F in replacement Battery of 12V-180AH complete all as specified and directed by Engineer –in-charge. |
| 62 | S&F in replacement Battery of 12V-130AH complete all as specified and directed by Engineer –in-charge. |
| 63 | S&F in replacement Battery of 12V-90AH complete all as specified and directed by Engineer –in-charge. |
| 64 | S&F in replacement water pump assembly complete all as specified and directed by Engineer –in-charge. |
| 65 | S&F in replacement fan assembly along with hub suitable for DG Set of any cap complete all as specified and directed Engineer–in-charge |
| 66 | Earthing complete with galvanized steel earth electrode of size 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of the plate not less 1.5 metre below normal ground level connecting to galvanized earth lead of size 32x6 mm GI strip by means of bolts, nuts, check nuts and GI washers etc. earth plate shall be surrounded by packed layers of coal dust and common salt 30 cm thick all around bottom and top and watering pipe 20 mm dia light grade including earth chamber of using sub class 'B' bricks in CM 1:4, 12mm thick cement plaster in CM 1:4 and angle iron frame 40x40x6mm and MS plate cover 6mm thick with locking arrangement all as shown on drg. Earthing strip shall be protected by 40 mm dia GI light grade pipe upto a distance not exc 3m from top of earthing pit . The earth strip shall be tested after carefully completion as per IS specifications and as shown in electric plate No 3 of SSR Part-I of 2009. |
| 67 | S&F in replacement of change over switch Capacity 200Amps,415 Volts,FP,50HZ ,manually Operated Complete al as specified and directed. |
| 68 | S&F in replacement of change over switch Capacity 160Amps,415 Volts,FP,50HZ ,manually Operated Complete al as specified and directed. |
| 69 | S&F in replacement of change over switch Capacity 100Amps,415 Volts,FP,50HZ ,manually Operated Complete al as specified and directed. |
| 70 | S&F in replacement of change over switch Capacity 63Amps,415 Volts,FP,50HZ ,manually Operated Complete al as specified and directed. |
| 71 | Disconnecting the battery 12 Volts 180 AH from the DG set shifting to workshop for further dismantling for repair/replacement of cells, plates, reconditioning, filling of electrolyte of required specific gravity and charging the battery, after repair shifiting the batteries from workshop to E/M installation fixing to the DG set testing complete all as directed by Engineer-in-charge. |
| 72 | Disconnecting the battery 12 Volts 130AH from the DG set shifting to workshop for further dismantling for repair/replacement of cells, plates, reconditioning, filling of electrolyte of required specific gravity and charging the battery, after repair shifiting the batteries from workshop to E/M installation fixing to the DG set testing complete all as directed by Engineer-in-charge. |
| 73 | Disconnecting the battery 12 Volts 90 AH from the DG set shifting to workshop for further dismantling for repair/replacement of cells, plates, reconditioning, filling of electrolyte of required specific gravity and charging the battery, after repair shifiting the batteries from workshop to E/M installation fixing to the DG set testing complete all as directed by Engineer-in-charge. |
| 74 | M & L for cleaning of DG sets including removing of oil grees and etc spot washing carefully with soda water preparation of old painted surface and painting to the DG sets of capacity 7.5 KVA to 160KVA with two coat of spray painting of approved make and colour of first grade paint and making SM/MES No all as specified and directed. |
| 75 | Supply only distilled water for lead acid battery all as directed |
| 76 | Supply and Fixing in replacement power contactor 415volt,50 cycles,3 phase,type MCX33 complete all as specified and directed by Engineer-in-charge. |
| 77 | Supply and Fixing in replacement MCCB 160Amps, 4 pole ,415volt,50 cycles, breaking capacity 36KA, thermal magnetic release complete all as specified and directed by Engineer-in-charge. |
| 78 | Supply and Fixing in replacement MCCB 63Amps, 4 pole ,415volt,50 cycles, breaking capacity 36KA, thermal magnetic release complete all as specified and directed by Engineer-in-charge. |
| 79 | Supply and Fixing in replacement three phase Volt Meter of size 96x96x80mm, flush mounting on panel 0 to 500 Volts, digital type, with built in selector switch complete all as specified and directed by Engineer-in-charge. |
| 80 | Supply and Fixing in replacement three phase Amps Meter of size 96x96x80mm, flush mounting on panel 0 to 200 Amps, digital type, with built in selector switch complete all as specified and directed by Engineer-in-charge. Please Enable Macros to View BoQ information |
| 81 | Supply and Fixing in replacement three phase Amps Meter of size 96x96x80mm, flush mounting on panel 0 to 200 Amps, digital type, with built in selector switch complete all as specified and directed by Engineer-in-charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 12 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender