Tender For Repair/Maint Of Lt Cables, Lt Panels And Allied Work And Repair / Maintenance Of Street Light/ Security Light/ Permeter Light In Domestic Area And Technical Area At Air Force Station Jaisalmer

Issued by Statutory Bodies & Commissions/Committees · Jaisalmer, Rajasthan
Tender Value
49.67 Lakhs
Estimated cost
Bid Submission
31 Jul 2026
10 days left
EMD
99340
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Jaisalmer → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maint Of Lt Cables, Lt Panels And Allied Work And Repair / Maintenance Of Street Light/ Security Light/ Permeter Light In Domestic Area And Technical Area At Air Force Station Jaisalmer

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 18-Jul-2026 Amendment BOQ 31-Jul-2026

BOQ

Name of Work:- REPAIR/MAINT OF LT CABLES, LT PANELS AND ALLIED WORK AND REPAIR / MAINT OF STREET LIGHT/ SECURITY LIGHT/ PERMETER LIGHT IN DOMESTIC AREA AND TECHNICAL AREA AT AIR FORCE STATION JAISALMER
Sl. No. Item Description
1Excavation in trenches in soft/loose soil , not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc complete all as sepecified and directed.
2Returning filling in, soil including spreading, levelling, watering and well ramming in layers n.exc 25 cm.
3Removing surplus excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point.
4M&L tibba sand for cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge. (Note:- punned thickness shall be measured only)
5Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm all as specified and directed.
6M&L for drilling hole under hard standing /road in different locations as per site requirement (between 03 mtr to 12mtr maximum) for laying of pipe, for protection of cable etc by means of mannual bookle and without disturbing the top surface and making good the disturbed surface if any complete all as specified.
7M&L for cutting of black top cover of existing road upto 0.6 mtr depth and upto 45cm wide for laying of UG cable and pipe line, refilling and making good after laying UG cable and pipe line with PCC 1:3:6 upto 30cm from top of the road surface complete all as specified and directed by Engr - in-charge
8M&L for GI Tubes, of following size, light grade ,galvanised , with clamp of 25x3 flat iron welded to pipe fixed to wall/pole/ceiling or laid in floors or under road etc complete all as specified and as directed.(a) 40 mm bore
9(b) 50 mm bore
10(c) 80 mm bore
11Taking down of old unserviceable LT cables of size 10 sqmm 2 core to 16 sqmm 4 core for schedule of credit/ relaying complete all as specified and directed
12Taking down of old unserviceable LT cables of size 25sqmm 4 core to 50 sqmm 3.5 core for schedule of credit/ relaying complete all as specified and directed
13Taking down of old unserviceable LT cables of size 70 sqmm 3.5 core for schedule of credit/ relaying complete all as specified and directed
14M&L for Relaying the same after, jointing or necessary repair work and testing XLPE insulated PVC outer seathed and PVC inner sheath, galvanised steel strips armoured, and reconnecting the cable from same location and panel suitable for rated voltage of 1100 Volts grade 25 sqmm to 240 sqmm 4/3.5 Core and laid in treches/ducts/pipe or on read/pole all as required and directed at site. Note: excavation and earth work joints will be measured and paid seperately
15Supplying , laying , passing through trench, pole wall, pipe, connecting and testing UG cable XLPE insulated ,armoured heavy duty electric cable with aluminium conductor ,1100 volts grade of the following cross section area including suitable size lugs all as sprcified and directed. (Note:- Excavation , Earth Work pipe etc will be measured and paid sepretaly) (a) 10 Sqmm 2 core
16(b) 10 Sqmm 4 core
17(c) 16 Sqmm 4 core
18(d) 25 Sqmm 4 core
19(e) 35 Sqmm 3.5 core
20(f) 50 Sqmm 3.5 core
21(g) 70 Sqmm 3.5 core
22Taking down existing rusted/worn out MS cross arm, angle, clamps, nuts, bolts and washers and supply and fixing new MS Cross arms, bracings, supports, clamp and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any type, shape or as indicated and directed inclusive of one coat of red oxide primer and one coat of aluminium paint complete all as specified and directed by Engr in charge.
23Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
24Servicing and repair / maintenance of LT panel Board including checking of MCCB,s, Bus bar , cable lugs, voltmeter, ammeter and CTcoil etc for healthy operation and repairs / replacement of MCCB, BUS bar, Voltmeter, Ammeter ,Current Transformers (CTs) and replacing of defective control wiring if any replacement of defective cable lugs and complete for Indoor type / Outdoor type LT Panel of various capacity including necessary addition/ alternation of panel including cutting/welding/hinges of front and back side of panel board /feeder to match the existing panel board/feeder Note:- Major spares like MCCB, Volt meter, Ammeter, Busbar and CT's, Epoxy insulator will be measured and paid seperately.
25S&F in repair of MCCBs thermal magnetic including necessery fixing arrangement complete all as specified and directed, of capacity 100 Amps, 4 Pole, breaking capacity 25KA, Ics=100% of Icu as per IEC 60947..
26All as per item No 17 above but 160 Amps, 4 Pole, breaking capacity 36 KA, Ics=100% of Icu as per IEC 60947.
27All as per item No 17 above but 200 Amps 4 Pole breaking capasity 36 KA, Ics=100% of Icu as per IEC 60947.
28All as per item No 17 above but 250 Amps, 4 Pole, breaking capacity 36 KA, Ics=100% of Icu as per IEC 60947.
29All as per item No 17 above but 400 Amps, 4 Pole, breaking capacity 50 KA, Ics=100% of Icu as per IEC 60947.
30All as per item No 17 above but 630 Amps, 4 Pole, breaking capacity 50 KA,Ics=100% of Icu as per IEC 60947.
31S&F LT volt meter (0-500) digital square, flush type of size 96x96 mm including necessary addition/ alternation of panel including cutting/welding of front side of panel board /feeder to match the existing panel board/feeder including taking out of unserviceable Volt meter complete all as specified and directed. MAKE:- AE/L&T/Havells/Crompton.
32S&F 1100 Volts grade LT Ammeter (0 - 500 A) digital square, flush & CT type including necessary addition/ alternation of panel including cutting/welding/hinges of front and back side of panel board /feeder to match the existing panel board/feeder taking out of unserviceable Ammeter complete all as specified and directed. MAKE:- AE/L&T/Havells/Crompton.
33S & F of LT epoxy insulator for suitable on load of busbar including nut and bolts complete all as specified and directed
34Supply and fixing of CT coil (100/5 Amp rating)
35Supply and fixing complete with 1100volt grade PVC insulated unsheathed multistranded 4 sqmm single core copper conductor cable confirming to IS 694 FRLS fixed on control wiring of LT panel including provision of copper/Aluminium lugs, Copper brass,nut bolts etc all as specified and directed. Make: Plaza/Polycab/Finolex/Havells
36Supply and fixing of copper strip of any size for earth conductor, bus bar conductor fixed with on insulator
37M&L for Spray painting to existing LT panel board/Feeder pillar with two coats of synthetic enamel high glow paint Ist grade including preparation/cleaning of steel surfaces all as specified and directed.
38Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 3.25 meter below ground level) connected to galvanised iron strip of size 25 x 4mm main earthing lead by means of galvanized bolts, uts and washers with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) for earth pit with 40 x 40 x 6 mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded stone aggregate) 40mm thick cover reinforced with 8 mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel,wire mesh all as shown in electrical plate no. 3 of SSR Part I of 2009 and 15 mm dia GI light grade pipe earth lead protection complete all as specified and directed.
39M&L for GI strip of size 25 x 4 mm for Earth continuity conductor or main earthing lead fixed on wall on insulator or PVC pipe or chases or burried in ground or fixed to poles or any other indicated situation for loop earthing etc as directed .
40Supply, installation, commissioning and testing of cubical, outdoor type CPRI approved LT bus bar Box totally enclosed weather and vermi proof, fully compartmentalised made out of 3.15 mm thick CRCA sheet for load bearing and 2 mm thick for non load bearing portions, protection of enclosure IP-66 complete with two coat synthetic enamel paint over one coat of red oxide primer, locking arrangement, front size and rear side opening arrangement of suitable size, mounted on angle iron stand of angle size 50x50x6mm having min height 45cm from floor level, excavation and earth work, PCC foundation ( mini 45 cm hight from GL) , making all incoming and out going connection with suitable size copper cable including cable lugs , cable gland etc with consisting the following items:-. (a) 4 Nos bus bar of equal size made by copper conductor with PVC insulated coloured heat shrinkabal type sleeves , rating bus bar 400 Amps , mounted on non cracking resin type insulator - 1 Set with suitable capacity of CT,s , Ammeter , volt meter , frequincy meter, selector switch and indication lamp , LED indication lamps for ON, OFF & RYB, etc(b) MCCB ,3 phase and neutral, 415 V thermal magnetic type, 4 poles, rating 250 Amps , with rupturing capacity 36 KA - 1 No (incoming).
41Supply, fixing and connecting elastomer insulated, flat,sheathed, multicore, industrial flexible cable with bright annealed copper conductor, 1100 volts grade cable of size1.5sqmm, 3 core, confirming to IS 694-1990 complete all as specified and directed
42S&F in replacement 3 Layer PPR Pipes, UV stabilised having thermal stability upto 93 degree centrigrade complete and fixed with the pole by providing FI clamps, nuts and bolts of size 25x25x3mm with nuts & bolts for protection of connecting wires, connection from junction box to light fittings, complete for outer dia 20 mm (PN-16)
43Supply only cable junction box with new pole mounted polycarbonate cable Junction box for steet light with IP-67 protection with cable gland, halogen free and weather proof with metric knockouts for cable entry for outdoor installation of approx size 225 mm x 295mm x 122 mm with front door opening system including terminals for one incoming and two outgoing cables of size 16/35 sqmm 4 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed . Make of junction box - Hensel / Legrand / Schinder
44Supply and fix cable junction box with new pole mounted polycarbonate cable Junction box for steet light with IP-65 protection with cable gland, halogen free and weather proof with metric knockouts for cable entry for outdoor installation of approx size 300mm x 450mm x 170 mm with front door opening system including terminals for one incoming and two outgoing cables of size 50/70 sqmm 3.5 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed . Make of junction box - Hensel / Legrand / Schinder Please Enable Macros to View BoQ information
45Supply and fix cable junction box with new pole mounted polycarbonate cable Junction box for steet light with IP-65 protection with cable gland, halogen free and weather proof with metric knockouts for cable entry for outdoor installation of approx size 300mm x 450mm x 170 mm with front door opening system including terminals for one incoming and two outgoing cables of size 50/70 sqmm 3.5 core, one MCB SP 3 to 6 Amp 240V AC with mounting clamp of flat iron, nut, bolt and washers complete all as specified and directed . Make of junction box - Hensel / Legrand / Schinder Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56428574
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 49.67 Lakhs
LAST DATE 31-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint Of Lt Cables, Lt Panels And Allied Work And Repair / Maintenance Of Street Light/ Security Light/ Permeter Light In Domestic Area And Technical Area At Air Force Station Jaisalmer
Basic Detail
Tender No 8445/GE/E8
Bidding Type Tender
Location
City Jaisalmer
State Rajasthan
Key Dates
Publish Date 18 Jul 2026
Submission Date 31 Jul 2026
Open Date 01 Jan 0001
Finance
Tender Value 49.67 Lakhs
Tender Fee 500
EMD 99340
Exemption Available
Document List
8445Tendedocu.pdf
BOQ_871440.xls
Tendernotice_1 (6).pdf
3abb408f-cc64-4b2b-8b21-17d196311d79.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 18, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 31, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 10 days
Jul 31, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
pdf

8445Tendedocu.pdf

xls

BOQ_871440.xls

pdf

Tendernotice_1 (6).pdf