Tender For Erection Of Estimate Is Prepared For Creation Installation Of New 33 11 Kv S S Capacity 1 5Mva Under Sstd Scheme At Baloda Under Badnawar R Dc O M Division Badnawar Under Dhar Circle
Tender Value
Ref. Documents
Estimated cost
Bid Submission
21 Jul 2026
6 days left
EMD
20000
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Dhar → Madhya Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Erection Of Estimate Is Prepared For Creation Installation Of New 33 11 Kv S S Capacity 1 5Mva Under Sstd Scheme At Baloda Under Badnawar R Dc O M Division Badnawar Under Dhar Circle
BOQ
| Sl. No. | Item Description |
| 1 | Material Supply by Contractor |
| 2 | Concreting of for poles @ 0.3 cmt. for pole (Including muffing) |
| 3 | M.S.Nuts and Bolts |
| 4 | Stay insulator |
| 5 | 33 KV,10 KN PIN COMPOSITE POLYMER INSULATOR |
| 6 | 11 KV, 5KN PIN COMPOSITE POLYMER INSULATOR |
| 7 | 33 KV STRAIN (T&C TYPE) HARDWARE FITTINGS |
| 8 | 33 KV , 45 KN 16mm FRP with 25mm per KV Creepage DISC POLYMER LONG ROD TYPE T&C INSULATOR (FOR 11KV SIDE) |
| 9 | Supply of PTR Foundation as per attached drawing |
| 10 | 33 kV Lightning Arrestors Gapless type |
| 11 | 11 KV D.O. fuse unit |
| 12 | LED LAMP , 90 WATT (COMPLETE) |
| 13 | INDOOR HEAT SHRINKABLE CABLE END JOINTING KIT WITH LUGS FOR 11KV GRADE XLPE CABLE FOR 3 CORE 120 SQ MM |
| 14 | T CLAMP ALUMINUM FOR BUS BAR PANTHER RUN PANTHER TAP |
| 15 | 11KV Strain hard ware fitting |
| 16 | 11 KV (45KN) 16mm FRP with 25mm per KV creepage Disc Insulator Polymer |
| 17 | 33 KV COMPOSITE POLYMER STRAIN SET WITH HARD WARE SUITABLE FOR PANTHER CONDUCTOR (FOR 11KV SIDE) |
| 18 | Erection of Plinth per VCB- 33KV or 11KV [Pit digging-size(3x2x0.6) = 3.6 cu. Mtr,Base filling by Kopra in case of Black cotton soil-1.92 cmt., concreting, curing and back filling of pits ] |
| 19 | work execute by Contractor |
| 20 | Back Filling of Poles with Boulders |
| 21 | For Concreting (1:3:6) 0.36 H-Beam -7/9m & RSJ 9.3 m,PCC PoleDP/TP/4P of 140 kg.8m 200Kg.9m 280Kg 0.9m,0.56 for 11m,0.60 for 13m,0.67for 15m Per Pole include muff wid Pit digging,0.3per stay(20/25)etc |
| 22 | AAAC Conductor Raccoon with 3 % Sag |
| 23 | Anti climbing Device (Barbed Wire) GS 2.24 mm Dia (14 SWG) |
| 24 | PCC POLE 280 KG 9.1 MTRS -30FT- LONG |
| 25 | Errrection of 33 KV 'V' CROSS ARM 1.5 MTR (5FT)- CENTRE MADE FROM 75X75X6MM ANGLE |
| 26 | 33 KV TOP CLAMPS ANGLE TYPE |
| 27 | STAY SET WITHOUT STAY WIRE 20 MM. (PAINTED) |
| 28 | DANGER BOARD ENAMELED 33 KV |
| 29 | 33 KV,10 KN PIN COMPOSITE POLYMER INSULATOR |
| 30 | Stone Block/Pre cast block for base pedding 450x450x75mm |
| 31 | Red oxide paint |
| 32 | Aluminium paint |
| 33 | PCC POLE 140 KGS 8 MTRS LONG |
| 34 | Errection of 11 KV V CROSS ARM 65X65X6 MM. ANGLE TYPE |
| 35 | 11 KV TOP CLAMPS 65x65x6 mm ANGLE TYPE |
| 36 | STAY SET WITHOUT STAY WIRE 16 MM. (PAINTED) |
| 37 | Danger Boards Enamalled Type 11KV |
| 38 | 11 KV, 5KN PIN COMPOSITE POLYMER INSULATOR |
| 39 | DC.CROSS ARMS 5` (1.5 METER) CENTRE TO CENTRE 100X50X6MM CHANNEL |
| 40 | Errection Horizontal and cross bracing 5' centre |
| 41 | 33 KV , 45 KN 16mm FRP with 25mm per KV Creepage DISC POLYMER LONG ROD TYPE T&C INSULATOR (FOR 11KV SIDE) |
| 42 | Errection of PTR Foundation as per attached drawing |
| 43 | Direct Curent Distribution Board (DCDB) 24 Volts Indoor floor / wall mounted comprising of 1 no. 2P/100A DC MCCB 5A Switch Fuse Unit as incommer and 8 no. 2P/40A MCCB 5A |
| 44 | ACDB 415 V, along with three phase-neutral voltmeter, three phase ammeter and Selector switches, 1no. 200 Amps TPN switch fuse unit as incomer, 1no. 63 Amp. |
| 45 | BIS certified Energy Efficiency Level-III (Old)/Level-II (New) Convential 11/0.433KV, 100 KVA Distribution Transformer |
| 46 | 33 KV CT OUTDOOR TYPE 200-100 / 5AMP |
| 47 | 33 KV CTs.(out door oil filled type) 300-150/5 Amps |
| 48 | 11KV CT OUTDOOR TYPE 300-150 / 5-5 AMP |
| 49 | 33 KV PT OUTDOOR TYPE SINGLE - PHASE OIL IMMERSED |
| 50 | 11 KV SINGLE PHASE PTS OIL IMMERSED |
| 51 | Bi Metallic Clamp for Power Transformer of Brass Flat 50x50x10MM |
| 52 | 33 KV VCB, Outdoor Porcelain clad type with complete structure and accessories |
| 53 | 11 KV VCB, OUTDOOR PORCELAIN CLAD TYPE WITH COMPLETE STRUCTURE AND ACCESSORIES |
| 54 | Marshelling box with 10 no. connectors |
| 55 | 33 KV CONTROL & RELAY PANEL WITH STATIC RELAY FOR TRANSFORMER PROTECTION |
| 56 | 33 KV CONTROL & RELAY PANEL WITH STATIC RELAY FOR FEEDER PROTECTION |
| 57 | 11 KV control & relay panel with static relay for transformer protection |
| 58 | 11 KV CONTROL & RELAY PANEL WITH NUMERICAL STATIC RELAY FOR DOUBLE FEEDER PROTECTION (2F) |
| 59 | 11 KV ISOLATOR 800 A.(TURN & TWIST TYPE) |
| 60 | 33 KV ISOLATOR 600 A. (TURN & TWIST TYPE) |
| 61 | Supply of 11 KV AB Switch Polymer type 400 Amp with Complete fitting |
| 62 | 33 KV Lightening arrestor Gapless type |
| 63 | 9 KV Gapless type Metal oxide (10 KA) Polymer for 33/11 kv S/s type |
| 64 | 11 KV, LA POLYMER TYPE GAPLESS /METAL OXIDE 9 KV , 5 KA LINE TYPE |
| 65 | Distribution Box for 100 KVA Transformer (300 A.Isolator & 6 no J type Al hook.) made of SMC |
| 66 | 11 KV D.O. Fuse Unit Polymer type |
| 67 | Complete jumpering of DTR |
| 68 | LEAD ACID BATTERY SET 30 VOLTS 200 AH |
| 69 | RRRDS -BATTERY CHARGER 230 V AC INPUT 20 AMP, 30 V DC OUTPUT SOLID STATE TYPE |
| 70 | Mesh earthing for New33/11KV Sub-station inblack cotton soil as per Schedule G-3.1 |
| 71 | LED lamp 90 watt Complete set |
| 72 | Three phase 20-80 Amps.with L.S. & TOD Facility with box |
| 73 | For substation metering- 3 phase 4 wire 3x63.5 volts lb=5 amps Imax = 10 amp, HT trivector meter class of accuracy 0.5s, DLMS Compliant category A Meters along with GSM (GPRS compatible ) modems, |
| 74 | AAAC Rabbit conductor 0.05 sq. inch (55 sq.mm. Al.Eq.) |
| 75 | XLPE CABLE 11 KV ARMOURED 3X120 SQMM |
| 76 | 70 Sq.mm.,single core XLPE insulated un-armoured aluminium conductor cable |
| 77 | PVC CABLE 4 CORE UNARMOURED 16 SQMM ALUMINIUM CONDUCTOR |
| 78 | PVC CABLE 2 CORE ARMOURED 2.5 SQMM ALUMINIUM CONDUCTOR |
| 79 | COPPER CONTROL CABLE 2 CORE, 2.5 SQMM PVC UNARMOURED |
| 80 | COPPER CONTROL CABLE 4 CORE, 2.5 SQMM PVC UNARMOURED |
| 81 | COPPER CONTROL CABLE 8 CORE, 2.5 SQMM PVC UNARMORED |
| 82 | COPPER CONTROL CABLE 12 CORE, 2.5 SQMM PVC UNARMOURED |
| 83 | INDOOR HEAT SHRINKABLE CABLE END JOINTING KIT WITH LUGS FOR 11KV GRADE XLPE CABLE FOR 3 CORE 120 SQ MM |
| 84 | T CLAMP ALUMINUM FOR BUS BAR PANTHER RUN PANTHER TAP |
| 85 | H- BEAM 11 METER 152 X 152 MM 37.1 KG/METER |
| 86 | H- BEAM 9 METER 152 X 152 MM 37.1 KG/METER = 333.9 kg. FOR 11KV GANTRY STRUCTURE |
| 87 | H- BEAM 7 METER 152 X 152 MM 37.1 KG/METER = 259.7 kg. FOR 5' CENTER JUMPER SUPPORT FOR 33 & 11KV SIDE |
| 88 | R S JOIST 9.3 METER 175X85MM 19.6 KG/ METER |
| 89 | Errection D.C. CHANNEL 100X50X6MM 4.8 MTRS CENTER TO CENTER (set) |
| 90 | DC.CROSS ARMS 8` (2.4 METER ) CENTRE TO CENTRE 100X50X6 MM CHANNEL (set) |
| 91 | TRANSFORMER MOUNTING CHANNEL 100X50X6MM (set) |
| 92 | D.O.MOUNTING CHANNEL 75X40X6MM |
| 93 | ERRECTION OF HORIZONATAL & CROSS BRACING 8' CENTRE (wt of each X-BRACING-64.29 Kg (set) |
| 94 | 11 KV (45KN) 16mm FRP with 25mm per KV creepage Disc Insulator Polymer |
| 95 | Stringing of Each 33 KV Bus- upper and lower including drop jumpering, jointing with clamps, incoming DP/ ME to BUS |
| 96 | Stringing of Each 11 KV Bus-upper and lower bus including, drop jumpering and jointing with clamps,through outgoing VCB/ ME/ DP, upto station transformer |
| 97 | Earthing of DTR as per schedule G-1 (for black cotton soil)Earthing of DTR as per Schedule G-1.1- A (For black cotton soil) (Using -3 no pipe) |
| 98 | Errection of Stringing of All 33 KV & 11 KV Jumpers - from 33 KV gartry through 33 KV VCB to PTR to 11 KV gantry through 11 KV VCB |
| 99 | Erection of Plinth per VCB- 33KV or 11KV [Pit digging-size(3x2x0.6) = 3.6 cu. Mtr,Base filling by Kopra in case of Black cotton soil-1.92 cmt., concreting, curing and back filling of pits |
| 100 | ACSR Dog conductor 0.10 sq. inch (100 sq.mm. Al.Eq.), (6/4.72 + 7/1.57 mm) |
| 101 | H-Beams 152 X 152 mm., 37.1 Kg./Mtr.-13 mtr. Long = 482.3 kg |
| 102 | DC.CROSS ARMS 4` (1.2 METER) CENTRE TO CENTRE 100X50X6MM. CHANNEL |
| 103 | Bracing / Support Angle of 65x65x6mm 1.2 Mtr (4 feet) Center DP |
| 104 | AAAC Dog conductor 0.10 sq. inch (100 sq.mm. Al.Eq.) |
| 105 | Power Transformer Jumper Work |
| 106 | Crane charges for Handling & installation of Power Transformer with fitting of all radiaters (ii) 33/11 KV S/S above 50 km. . from crane availablity location |
| 107 | Total material supply by Contractor |
| 108 | Total Labour |
| 109 | GST Amount @ 18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysJul 22, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender