Tender for Supply, Installation, Testing And Commissioning Of 750 Kva Dg Set And 2500 Kva 11/0.433 Kv Distribution Transformer For Utility-2 At Iim Indore.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, installation, testing and commissioning of distribution transformer of 2500KVA capacity (continuous loading) BEE 5 Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with Off Circuit Tap Changer (OCTC) on HV side, manual operation of OCTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking arrangement on LV side including supplying and laying of copper conductor multicore control cable from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions |
| 2 | as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise shall not exceed 35 ºC for oil and 40 ºC up to 200 KVA and 40 ºC for oil and 45 ºC for above 200 KVA for winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-Charge. Design ambient condition : a) air temperature 50 ºC, b) Relative |
| 3 | Humidity 90 % Max, c) Seismic Zone-III, d) Altitude as per location/site. Noise level Shall not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC 551 / NEMA standard. The transformer should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. Marking Each transformer shall be provided with rating plate made of anodized aluminium/ stainless steel material securely fixed on the outer body, easily accessible as per IS: 1180 Part3. The entries on the rating plate shall be indelibly marked.Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c) Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase transformers; |
| 4 | g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oil temperature indicator and winding temperature indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads (for transformer above 1 600 kVA); |
| 5 | t) Additional Neutral separately brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers. |
| 6 | Supply, Installation, Testing & Commissioning of 4000 Amps four pole horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu upto 433 V electrically operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to latest IS 1397-2 complete with following accessories for ACB:(a) Independent manual spring closing mechanism-1No.(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection-1 set.(c) Digital type Voltmeter (0-500 V), with selector switch and backup MCBs – 1 set |
| 7 | (d) Digital type Ammeter (0-4000 Amp), with selector switch and one set of 3 Nos. CT’s of ratio 4000/5A class I accuracy – 1 set(e) 3 Nos. Phase indication LED lamps with 2 Amp back up MCB, breaker ‘ON’, ‘OFF’, ‘trip’ indicating lights with required MCBs, test terminal block set, MCBs, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip, Under Voltage coil 220 V A.C. Note: The item includes provisioning of channels, plates, etc. in the existing MS cubicle in order to facilitate installation. It also includes fitting, Accessories & busbar rating compatible to existing busbar for connection between breaker and busbar. |
| 8 | Supply, Installation, Testing & Commissioning of 2000 Amps four pole horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu upto 433 V electrically operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to latest IS 1397-2 complete with following accessories for ACB:(a) Independent manual spring closing mechanism-1No.(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection-1 set.(c) Digital type Voltmeter (0-500 V), with selector switch and backup MCBs – 1 set |
| 9 | (d) Digital type Ammeter (0-2000 Amp), with selector switch and one set of 3 Nos. CT’s of ratio 2000/5A class I accuracy – 1 set(e) 3 Nos. Phase indication LED lamps with 2 Amp back up MCB, breaker ‘ON’, ‘OFF’, ‘trip’ indicating lights with required MCBs, test terminal block set, MCBs, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip, Under Voltage coil 220 V A.C. Note: The item includes provisioning of channels, plates, etc. in the existing MS cubicle in order to facilitate installation. It also includes fitting, Accessories & busbar, rating compatible to existing busbar for connection between breaker and busbar. |
| 10 | Supplying, Installation, Testing & Commissioning of ‘Silent Type 750 KVA Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,Geo- Tag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings:(A) Diesel Engine:Tour bocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 0C, 50% RH & at 1000 Meter MSL , capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528. |
| 11 | The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.(B) Engine mounted Instrument Panel fitted with and having digital dis Plate for following:(i) Start-stop switch with key(ii) Water temperature indication(iii) Lubrication oil pressure indication(iv) Lubrication oil temperature indication(v) Battery charging indication and Voltage indication(vi) RPM indication(vii) Over speed indication(viii) Low lubricantion Oil trip indication(ix) Engine Running Hours indication(x) Fuel Level(C) Alternator: |
| 12 | Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 0C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- Hinsulation.(D) Base Frame & Foundation:Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. |
| 13 | (E) FUEL TANK:Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.(F) Exhaust System:Dry exhaust manifold with hospital type exhaust silencer and catalytic convertor.(G) Starting System:12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set.(H) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the |
| 14 | temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications. (I) AMF Panel: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor,KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for |
| 15 | BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following: 1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip. 2. Auto/Manual/Test/Off selector switch 3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay). 4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering 5. Energy analyser unit to indicate current, Voltage( LN & L_L), kW, kVA (Phase & Total), Frequency, KWH, PF. 6. LED Indicating lamps for load on mains and load on set 7. Fuse/ MCB for instruments 8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment. 9. Main supply failure monitor |
| 16 | 10. Supply failure timer 11. Restoration timer 12. Control unit with three impulse automatic engine start/stop and failure to start lockout. 13. Impulse counter with locking and reset facility. 14. ON/OFF/Control circuit switch with indicator 15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning 16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories 17. Maintenance notification based on Engine Run Hour & due date. 18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring. |
| 17 | Providing and laying RCC foundation (with minimum M25 grade concrete and Fe 500D reinforcement steel) for installation of D.G. set as per the requirement of manufacturer. This includes all earthwork, materials, manpower, resources, etc. required for the purpose complete in all respect. |
| 18 | Providing & Erecting DG stack (height as per statutory regulation) and exhaust pipe (class, size, insulation, expansion bellow, etc. as per OEM’s requirement / BIS standard). Complete job as per the requirement of site and direction of Engineer-in-charge.Note: This item includes a. Designing, drawing, etc. of the structure as required to fulfil the intent of the item. b. SBC to be considered for designing is 25 Tonne/Sqm.c. Complete finishing viz. plastering, painting, etc. d. Vetting of Structural Design & Drawing from any of the IITs / NITs or the approved engineering colleges by the Engineer-in-charge. |
| 19 | Supply, Installation, Testing and Commissioning of Copper plate earthing (Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required). |
| 20 | Supply, Installation, Testing and Commissioning of G.I. Plate Earthing (Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required). |
| 21 | Supplying, laying and termination of 50 mm X 6 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolts & spring washers spaced at 50mm). |
| 22 | Supplying and laying and termination 50 mm X 6 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm). |
| 23 | Buy back offer: Dismantling from existing position & taking out of the existing operational transformer of Voltamp make 1600 KVA 11/0.433 KV as per the direction of Engineer-in-charge under buyback offer. |
| 24 | Buy back offer: Dismantling from existing position & taking out of the existing operational DG set of Cummins make 500 KVA 415 volt, 50 Hz frequency, as per the direction of Engineer-in-charge under buyback offer. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysJul 31, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender