Tender For Strengthening / Stabilization Of 33 Kv Batote Assar Line By Way Of Replacement Of Old Used Worn-Out Outlive Acsr Dog Conductor With New 100 Mm² Dog Conductor And Insertion Of 11 Mtr St Poles Under Longer Spans At Various Locations & Rev In
Tender Overview
Project Description
Tender for Strengthening / Stabilization Of 33 Kv Batote Assar Line By Way Of Replacement Of Old Used Worn-Out Outlive Acsr Dog Conductor With New 100 Mm² Dog Conductor And Insertion Of 11 Mtr St Poles Under Longer Spans At Various Locations & Rev Ing/Stabilization Of 10+6.3 Mva Rxstn Ch A Batotescheme Code : Pddss2627100651important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.
BOQ
| Sl. No. | Item Description |
| 1 | Survey, Supply, Installation , Testing and Commissioning for Strengthening/Stablisation of 24CKM 33KV Batote Assar line by way of replacement of old used, wornout , outlived ACSR DOG conductor with new 100mm2 Dog conductor and insertion of 11mtr ST poles under longer spans at various locations for providing smooth power supply |
| 2 | 100mm2 ACSR Dog conductor |
| 3 | 13 Mtr. Long Pole(ST-410 SP69) |
| 4 | 11 Mtr. Long Pole(ST-410 SP56) |
| 5 | GI V cross-arm with top Bracket including clamp |
| 6 | GI Channel X-arm including clamps and braces |
| 7 | PG Clamps for 100 mm² ACSR Conductor |
| 8 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 9 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm (alongwith 33KV Dog fitting) |
| 10 | Galvinized Nuts and Bolts |
| 11 | Danger Plates |
| 12 | Anti-Climbing Device with Clamps |
| 13 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 14 | Red Oxide |
| 15 | Aluminium Paint |
| 16 | Aluminium Jointing Sleeves |
| 17 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 18 | Guard netting |
| 19 | Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job. |
| 20 | SITC for Revamping/Stabilization of (10+6.3) MVA, 33/11KV Receiving Station Champa (Batote) for Smooth Power Supply |
| 21 | 33kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec ,etc . |
| 22 | 33KV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter,Ammeter,Annunciation Windows with annunciation relays, 3-phase Trivectometer-5Amps DLMS Compliant with RS-485 Port |
| 23 | 33KV Isolator with earthing blade 36KV,1250Amp, Outdoor 3-Pole 25kA |
| 24 | 33KV Current Transformer (33KV ,1-phase, multi ratio multi core outdoor 1 no per phase) |
| 25 | 33KV Voltage Transformer (33KV/110V,1-phase, multi core outdoor 1 no per phase) |
| 26 | 33KV Lightening Arrestor (30 kv,10kA, Station Class,ZnO,Polymer)gap less |
| 27 | 11 KV VCB Panel Board Incomer of Make (Electricfield)/Megawin (12 KV, 1250A, 25 KA, Outdoor) with O/C , E/F relays (IEC61850), Mimic Diagram, Voltmeter,Ammeter,Annunciation relays, 3 Phase Trivector meter-5Amp, DLMS Complaint with RS-485 Port and with CT ratio 600/300/150/5A |
| 28 | 11 KV 3-core 185 mm2 Cable, FRLS |
| 29 | 185mm2 11 KV Heat Shrinkable Cable Termination Kit ( Indoor) |
| 30 | 185mm2 11 KV Heat Shrinkable Cable Termination Kit ( outdoor) |
| 31 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) |
| 32 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip |
| 33 | Galvanised Iron of sorts |
| 34 | a) Battery bank 30 Vm 100 AH of 15 No. cells of 2V each, sealed maintenance free VRLA type, High Impact Polyprophelene copolymer container flame retardant. b) 30 V, 100 AH, Float-Cum-Charger with full wave rectification for 220 V, 1 Phase 50 Hz AC Input Supply |
| 35 | Control Cables |
| 36 | 12 Core 2.5 mm2 Control Cable copper Armoured, 1.1 KV Grade ISI, FRLS |
| 37 | 4 Core 2.5 mm2 Control Cable copper Armoured, 1.1 KV Grade ISI, FRLS |
| 38 | 2 Core 2.5 mm2 Control Cable copper Armoured, 1.1 KV Grade ISI, FRLS |
| 39 | 200 mm2 ACSR Conducttor Panther |
| 40 | T Clamps |
| 41 | Polymeric composite Disc Insulator 36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN |
| 42 | Rubber Mat 1mx2m 19mm thick |
| 43 | Fire Extinguisher Co2 type of 4.5kg capacity of control rool |
| 44 | Civil Works |
| 45 | 33 KV Yard Concreting with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick. |
| 46 | 33 kV Yard Lighting with 4 nos 9 mtr ST poles each having 2 x 100 Wt LEDs street lights of reputed brand complete with earthing , cement bottoming GI brackets,cable etc . All the lights should be controlled from the control room with installation of control panel and having separate SPN for each light |
| 47 | Painting of All Equpiment structures /Gantry structures installed in the outdoor yard |
| 48 | Providing and laying cement concrete in retaining walls 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) (along 11KV outgoing structures) |
| 49 | Ceramic glazed tiles Fixing 1st quality ceramic glazed tiles conforming to IS:13753 of minimum thickness 5 mm of approved make like NITCO , ORIENT ,, SOMANY, KAJARIA or equivlant make in all colours , shades except begundy,bottle green , black of any size as approved by Engineer - in - charge in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3( 1 cement : 3 coarse sand ) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. |
| 50 | Applying white cement based putty of average thickness 2 mm,of approved brand and manufacture,over the plastered wall surface to prepare the surface even and smooth complete. |
| 51 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade New work ( Two or more coats) over and including priming coat with cement primer |
| 52 | Exterior Finsihsing : Finishing walls with water proofing cement of required shade: Old work (two or more coats on existing cement paint surface applied @ 3.28ltr/10sqmNew work( Two or more coats) applied @ 3.84 kg/10 sqm |
| 53 | Construction of bathroom with complete fitting Size : 8'0\\"x6'0\\"= 48.00 sqft @ 2000 / sqft (MR) |
| 54 | Providing and placing terrace polyethylene water tank 1000 lt @ 7.70/lt |
| 55 | Construction of 1 No. Septic tank and water tank (8'0\\"x 8'0\\")x2= 128 sq ft@1500/sq ft (MR) |
| 56 | Laying 1/2 inch size heavy duty GI pipe\\" B class\\" underground as per PHE norms for supply of water from already existing PHE Water supply pipes to collection/ storage point at receiving station yard including all fitting accessories like elbow , tees , nipples, unions, and regulating valves etc. complete job (200 RM). |
| 57 | Painting of All Equpiment structures /Gantry structures installed in the outdoor yard |
| 58 | Safety Tool kit |
| 59 | Crimping Tool Kit complete set for cable of different sizes upto 630 sqmm |
| 60 | Conventional Earthing -GI Plate Earthing with 600mm X 600 mm X 6 mm, GI Plate, GI Flat 50 x 6 mm, GI Pipe, 40 mm Dia with Charcoal salt & good earth 10 ft deep pit etc. as per REC standards . Complete job |
| 61 | 33 KV Hand Gloves(set of 2) |
| 62 | RainCoats |
| 63 | Safety Belt |
| 64 | Safety Helmet for electrician |
| 65 | Digital Meggar 5000 mega Ohm |
| 66 | Emergency light/ Torch 5 Watt chargeable |
| 67 | Earthing Rod (set of 3) |
| 68 | Dismentaling of Old ACSR Dog Conductor along with allied acessories and deposit it to the R/Stn. Champa (Batote) Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender