Tender for Electrification Work In Regional Office & Laboratory Building For Pollution Control Board At Bundi
BOQ
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 2 | Short point (up to 3 mtr.) |
| 3 | Medium point (up to 6 mtr.) |
| 4 | Long point (up to 10 mtr.) |
| 5 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 6 | On board |
| 7 | Short point (up to 3 mtr.) |
| 8 | Medium point (up to 6 mtr.) |
| 9 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 10 | 20 mm |
| 11 | 25 mm |
| 12 | 32 mm |
| 13 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 14 | 1 x 1.5 sq.mm |
| 15 | 1 x 2.5 sq.mm |
| 16 | 2 x 1.5 sq.mm |
| 17 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 18 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 19 | 4 x 6.0 sq.mm |
| 20 | 1 x 4.0 sq.mm |
| 21 | 2 x 10.0 sq.mm |
| 22 | 1 x 6.0 sq.mm |
| 23 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 24 | 50 mm x 50 mm |
| 25 | Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. |
| 26 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 27 | 6/16 A shuttered socket |
| 28 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 29 | RJ-45, Cat 6 computer jack with shutter |
| 30 | Modular MCB 6 A to 32 A DP |
| 31 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 32 | 5 step fan regulator 2 Module |
| 33 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 34 | 1/2 Module |
| 35 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 36 | 1-2 Module |
| 37 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 38 | Single pole MCB (With B / C curve tripping characteristics) |
| 39 | 6 A to 32 A rating |
| 40 | Double pole MCB (With B / C curve tripping characteristics) |
| 41 | 6 A to 32 A rating |
| 42 | Triple pole MCB (With B / C curve tripping characteristics) |
| 43 | 6 A to 32 A rating |
| 44 | 40 A rating |
| 45 | Four pole MCB (With B / C curve tripping characteristics) |
| 46 | 6 A to 32 A rating |
| 47 | 40 A rating |
| 48 | 50/63 A rating |
| 49 | 80 A rating |
| 50 | P&F 240/415 V AC Change Over Miniature circuit breaker with three positions (I-O-II) which allows supply change over from one source to second source & vice- versa, conforming to IS/ IEC 60947-3 in existing board/sheets including making connections, testing etc. as required. |
| 51 | Double Pole |
| 52 | 25 Amp, 2 Module |
| 53 | Providing & Fixing of 240/415 V Residual current circuit breaker (RCCB) conforming to (IS:12640-1)/ IEC 61008 -1 , rated 4 KV impulse withstand voltage truly current operated and shall operate on CBCT mechanisum, provision for pad lock, min. Electrical operation 10,000 upto 63 A rating and 5000 for 100 A rating and minimum phase termination capacity of 25 sq.mm. rigid wire , IP 20 contact protection with existing distribution board / sheet including making connections, testing etc. as required. |
| 54 | Two pole 100/300mA sensitivity |
| 55 | 40 A rating |
| 56 | Providing & Fixing of Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with din rail making internal DB terminations with copper lugs, detachable gland plate, including making connections, testing etc. as required. |
| 57 | Suitable for Two / Three / Four module for MCB |
| 58 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 59 | Metal door (Three phase) Per phase isolation, Horizontal IK-09 and IP-43 with Metal end box |
| 60 | 8Way. {8 Incomer + 6 Sub Incomer (2+2+2) + 24 out going } |
| 61 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB/ RCBO up to 63 Amp and SP / TP MCB upto 32 Amp. as outgoing ,made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with insulated 100 A rating copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 62 | Double door IK-09 & IP-43 with Metal end box |
| 63 | 8 Way (8 Incomer +24 Outgoing) |
| 64 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB up to 63 Amps. as outgoing ,made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with insulated 125/160/200/250 Amp. copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 65 | Double door IP-43 & IK-09 with Provision of Incomer MCCB up to 125 A Rating with Metal end box |
| 66 | 4 Way |
| 67 | Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required. |
| 68 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 69 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 70 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 71 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 72 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 73 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 74 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 75 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 76 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 77 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 78 | Resin cast wound type CT |
| 79 | C T Class 1, Ratio up to 150/5, Burden 5 VA |
| 80 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 81 | 4 pole MCCB With Thermal Magnetic release |
| 82 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 83 | Providing & Fixing of on load change over switch, front handle operated, four pole 415 V confirming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating. |
| 84 | With OEM fabricated sheet steel enclosure, powder coated, door locking system allow opening of door in OFF position only with 2 nos external earthing points. |
| 85 | 125 A |
| 86 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 87 | 6.0 Sq. mm |
| 88 | 4 core |
| 89 | 16.0 Sq. mm |
| 90 | 4 core |
| 91 | 50.0 Sq. mm |
| 92 | 3.5 core |
| 93 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 94 | 3.5 x 50.0 sq.mm |
| 95 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 96 | 110 mm |
| 97 | labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.: |
| 98 | All kind of Soils |
| 99 | SITC of Strip in Pipe Earthing using hot-dip galvanized 'B' class G.I. pipe, as secondary conductor. The system shall incorporate a crystalline conductive compound between the primary and secondary conductors to enhance conductivity and long-term stability. of following size and length and as per point mentioned (a), (b), [c), (d), (e) (f) as below |
| 100 | (a) Bore a hole of dia. 150 mm of required length, Place the rod in the centre of Hole |
| 101 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 30 kg for 3000 mm. 20 Kg. for 2000 mm The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 102 | © Connect the Strip Terminal (110 mm long) with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 103 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 104 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 105 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 106 | Outer Pipe - 76 mm dia GI pipe , Inner Conductor- Copper strip 25x3 mm Length 2 meter.Terminal 50x6mm Copper. |
| 107 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 108 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 109 | Making of hole in wall (brick/stone) of required and placing NP-2 RCC pipe ring of required size for housing exhaust fan and making good the same, with cement plaster required of following size. |
| 110 | Up to 457 mm size |
| 111 | Supply & Fixing of phenolic laminated board of 6.0 mm thick for fresh air fan/exhaust fan up to size of 300 mm on existing window frame including cost of board, cutting of hole , Nut bolts etc. as required. |
| 112 | Providing & Fixing BLDC technology step regulator compatible ceiling fan, with aluminium body & aluminium blade, power factor not less then 0.9 , following service value (CMM/W) , with following air delivery , speed 350 RPM ( tolerance as per IS:374 2019 ) THD less then 10%, copper winding with class of Insulation 'F' complete with with secondary support safety cable ( steel rope), down rod up to 30 cm, cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. |
| 113 | 1200 mm sweep with Air delivery >/= 230 CMM and Service Value 8.20 |
| 114 | P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required. |
| 115 | Providing & Fixing of ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. |
| 116 | 250 mm sweep Minimum Air Delivery 750 Cum / hour |
| 117 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. |
| 118 | 230 mm sweep, Minimum air delivery 750 Cum / hour |
| 119 | 300 mm sweep Minimum air delivery 1600 Cum / hour |
| 120 | P & F of Wall cowl with Bird Screen Suitable for Outside Wall of Exhaust Fan Opening of following size and made out from 24 SWG GI sheet as per instructions of Engineer in charge including fixing with suitable fasteners etc. as required. |
| 121 | Suitable for 300 mm sweep Exhaust Fan |
| 122 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 123 | 1170mm(+/-10%) LED batten with min. lumen output 4400 lm |
| 124 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 125 | Recessed Mounting |
| 126 | Minimum lumen output 1950 lm |
| 127 | Surface Mounting (with extruded alumn. Housing ) |
| 128 | Minimum lumen output 1600 lm |
| 129 | Minimum lumen output 1950 lm |
| 130 | SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 131 | Recessed Mounting |
| 132 | Minimum lumen output 4320 lm |
| 133 | Surface Mounting (Driver should be Inside the Luminaire) |
| 134 | Minimum lumen output 4320 lm |
| 135 | Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, U/UTP (Unscreened/Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected by LSZH Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies ranging from 250 to 500 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack & ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. |
| 136 | Supply, Installation, Testing and Commissioning of Rack mounted 19\\" 1U, 24 Port loaded, CRS chasis, powder coated, sheet steel, High-impact, flame retardant, thermoplastic, UL Listed, Modular Patch Panels with Rear Cable management system and mounting hardware to mount the patch panel. Should have port identification numbers printed/engraved on front of the panel. Etc. as required. All as per pre approved by Engineer in charge. |
| 137 | Modular Patch Panel Loaded with Cat -6 I/O |
| 138 | Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP). |
| 139 | Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord |
| 140 | 1 Mtr |
| 141 | Supply & Installation of IP-20 & IK-08 , Wall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with 'U'Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19\\" angles with wall mounting provision on wall. Accessories like: 1 No of 19\\" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19\\" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastner etc as required. |
| 142 | 12 U Rack with Width 600 mm & Depth 400 mm + 100 mm |
| 143 | Supplying, installation, Testing and commissioning of following capacity 8 port PoE Layer 2 Indoor Network Switch having features and specifications etc. as mentioned here under: At least 8 X RJ-45 PoE/PoE+ Gigabit Ethernet Ports and additional 4 X 1G SFP Ports with non-blocking architecture by having Switching capacity of min. 24Gbps and packet forwarding rate of 17Mpps or higher, console port, 16K MAC table, IPv4 and IPv6 ready, IGMP snooping v1, v2, v3, DHCP,DHCP Relay, NTP/SNTP, SNMPv1, v2 C v3, TELNET/ SSH, LACP, STP, RSTP, MSTP, ERPS. VLAN: Port based, Mac based, IP subnet based, tag based, protocol based. Ǫ- in Ǫ, L2/L3 ACL, 1588v2 Precision Time Protocol HW- Based E2E Transparent clock, SNTP, TFTP, SNMP, Radius, Syslog. Dual DC Power input, IP30 rated, DIN Rail, -5° to 70° C operating temperature. Certificate: UL, CE, FCC, NEMA-TS2, IEC/MIL-STD for Shock , Vibration & Drop Certificate. OEM Should have Certificate for Industrial Cyber Security Capability IEC- 62443-4-1:2018, ISO 45001, ISO 27001 and ISO 14001 Certified or Equivalent Indian Certificate. OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required. |
| 144 | Supply , Installation, Testing and Comissioning of Unmanaged Switch Plug-and-play - easy setup with no configuration or no software needed, following Port fast ethernet - 8 port 10/100/1000 MBPS auto-negotiation RJ45 ports, IEEE 802.3x flow control ,supports auto-MDI/MDIX, eliminating the need for crossover cables including making connection etc as required complete in all respect. |
| 145 | 24 Port |
| 146 | SITC of 1Phase Input, 1Phase Output Microprocessor control based Inverter with input voltage range of 180-260V and output voltage same as input 210V +/- 10%, output frequency of 50 +/- 0.1 Hz and 0.8 Output factor. Overall efficiency of upto 80%, Transfer time 15 msec & Sinewave output.Inverter should have LED/LCD Panel Display showing Mains ON, INV. ON, Charging/Charged.Inverter should have protection from Overload/Short Circuit Trip/Over Temperature and Low Battery Trip.Batteries should be Tubular Type for 60 min back up with Trolley/Rack and necessary cable for Inverter to Batteries Installation. |
| 147 | 2KVA (1/1) Inverter with 3200 VAH |
| 148 | SITC of IP Based 2MP Dome camera: 1/2.8\\" or larger Progressive Scan CMOS Sensor with resolution: (1920 x 1080) @30 fps of following lens size and IR Range. The camera should support H.264, H.265, MJPEG, Quad/Triple streaming profiles, Frame rate upto 1-30 fps,120dB WDR, 2DNR/3DNR, BLC. Camera should support Open standard to support ONVIF (PROFILE S, PROFILE G, PROFILE T), onboard storage upto 512 GB (SD card not included). The camera supports advanced Video Analytics (VA) including motion detection and alarm should be trigger on Tampering, Network disconnect, IP address conflict. CCTV should have password protection, privacy mask, IP address filtering, Metal Housing, Vandal-proof housing, IP67, IK10, DC 12V & PoE, Complete with Junction box for cable management. Operating Conditions within -20°C to 60°C or better. The MAC address of Camera/NVR must be registered in the name of OEM . Regulatory approvals include FCC, BIS/UL, CE. CCTV cameras must be BIS Registered, Cyber Security Certified by STQC as per IoTSCS and meet the Essential Requirement (ER) issued by MeitY for security. The CCTV OEM should have its service/ support center in Rajasthan. |
| 149 | 2.8/3.6/4 mm lens with 30 meter IR range |
| 150 | SITC of IP Based 2MP Bullet camera: 1/2.8\\" or larger Progressive Scan CMOS Sensor with resolution: (1920 x 1080) @30 fps, (As per site requirement). Should Support H.264, H.265, MJPEG, Quad/Triple streaming profiles, Frame rate upto 1-30 fps, 120dB WDR, 2DNR/3DNR, BLC. Camera should support Open standard to support ONVIF (PROFILE S, PROFILE G, PROFILE T), onboard storage upto 512GB (SD card not included). The camera supports advanced Video Analytics (VA) including motion detection and alarm should be trigger on Tampering, Network disconnect, IP address conflict. CCTV should have password protection, privacy mask, IP address filtering, Metal Housing, Vandal-proof housing, IP67, IK10, DC 12V & PoE, Complete with Junction box for cable management. Operating Conditions within -20°C to 60°C or better. The MAC address of Camera/NVR must be registered in the name of OEM. Regulatory approvals include FCC, BIS/UL, CE. CCTV cameras must be BIS Registered Cyber Security Certified by STQC as per IoTSCS and meet the Essential Requirement (ER) issued by MeitY for security. The CCTV OEM should have its service/ support center in Rajasthan. |
| 151 | 2.8/3.6/6/8 mm lens with 50 Meter IR OR Higher |
| 152 | SITC of 16CH NVR for 2/5 MP cameras with minimum 2 SATA HDD Support with minimum 20 TB Capacity (minimum 10TB Capacity per slot - Hard Disk Not Included), minimum 1 HDMI output port, Video comression - H.265/H.264/JPEG, 1/1 Audio In/Out. NVR should support minimum 160 Mbps throughput bandwidth (80 incoming bandwidth), ONVIF compliance (Profile S/G/T). Recording resolutions up to 4K/8MP, minimum 2 USB Ports, minimum 1 Ethernet Ports (RJ-45) 10/100/1000Mbps. The system shall operate in 0°C to +50°C or better with BIS, FCC, CE . The CCTV OEM should have its service/ support center in Rajasthan. |
| 153 | SITC of 3.5\\" 4TB internal HDD for cctv recording ,capable for 24x7 operation, hdd rpm capacity shoud be 7200 rpm or better, Buffer should be 512 MB as required of following size. |
| 154 | 10 TB |
| 155 | Supply , Installation, Testing and Commissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Min 5 year Original Equipment Manufacturer (OEM) warranty of both compressor and Printed Circuit Board (PCB). |
| 156 | Cooling capacity 6800-7000 Watt, ISEER not less then 3.8 |
| 157 | Supply , Installation, Testing and Commissioning of Inverter type Air Cooled Cassette type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), R-32/R410A Green Refrigerant, wireless Remote, inbuilt drain pump, suitable for 400/230V, +/- 10% 50 Hz ,1 /3 phase AC supply, capable of performing cooling, dehumidification, Air circulation, filteration & ventilation of following capacity with Scroll /rotary/twin rotary compressor etc. complete as required. |
| 158 | Cooling Capacity 6900-7000 Watt ISEER not less then 3.5 |
| 159 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 160 | 25 mm |
| 161 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. |
| 162 | Supply and laying PVC Insulated and PVC Round Sheathed Multi Core copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 163 | 1.5 sq.mm x 3 core |
| 164 | 2.5 sq.mm x 4 core |
| 165 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves (size as per item no. 22.43),7 mil Glass Cloth with 3 coats of anti UV paint (on area which is exposed to weather) chase cutting, supports, making good the same with sand cement plaster etc. as required. |
| 166 | Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity. |
| 167 | cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs |
| 168 | Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 169 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 170 | LED Street Light fixture with Minimum lumen output 8750 lm |
| 171 | Providing & Fixing of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures with knock out for cable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect of following sizes. |
| 172 | 250 x 200 x 115 mm |
| 173 | Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. |
| 174 | 32 mm Dia. |
| 175 | Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM must ensure that the cable is tested for complaince, either through their in house laboratory accrediated by NABL or by any Govt. laboratory accrediated by NABL and the laboratory's scope of accrediation should cover the requirements and testing procedure as per IS:10810. |
| 176 | Armoured |
| 177 | 2 core x 1.5 Sq.mm |
| 178 | Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling & heating, having 100% hermetically sealed inverter type twin rotary/Scroll Compressor(s) with and minimum two compressors , above 14 HP modules, microprocessor based Controller, Side / top discharge type condensing unit(s), with R-410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The EER/COP (W/W) at 100% load with AHRI conditions shall not be less than 3.8 etc. complete as required. |
| 179 | 6 HP to 8 HP |
| 180 | SITC of following minimum capacity one way wall/corner VRV/VRF Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump,grill,necessarysupports,vibration Isolation, etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement automatically. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) |
| 181 | 2.0 TR (Cooling Capacity 7000 Watt) |
| 182 | Supplying and installation of high-pressure grade required size OEM make copper connection Y or T Joints / refnet for liquid and suction line , complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system complete as required. |
| 183 | Add : GST 18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 09, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 20, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysJul 21, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer