Tender For Addn/Altn To Internal Wiring From Aluminium To Copper Wiring At Ofm, Ofs, C3 Ward, Gyane Dept, Medical V, Medical Vii And Offr Ward-Ii Pantry/ Dinning Hall And Provn Of Lt Panel And Amf Panel For Backup Supply In Polyclinic Through Dg Set
Tender Overview
Project Description
Tender for Addn/Altn To Internal Wiring From Aluminium To Copper Wiring At Ofm, Ofs, C3 Ward, Gyane Dept, Medical V, Medical Vii And Offr Ward-Ii Pantry/ Dinning Hall And Provn Of Lt Panel And Amf Panel For Backup Supply In Polyclinic Through Dg Set Installed In Echs At Bhdc Under Ge (East) Delhi Cantt-10
BOQ
| Sl. No. | Item Description |
| 1 | Taking down copper/aluminium point wiring (light, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc all as specified and as directed. |
| 2 | Taking down old and unserviceable sub main wiring and removing from the site and making good the disturbed surface complete all as specified and directed. |
| 3 | M&L for point wiring concealed type with 1.5 sq mm Nominal cross sectional area, single core, 1100 Volt grade, multi stranded, PVC insulated, unsheathed FRLS copper conductor cable and connected to common earth and earth dollywith suitable copper lugs and drawing into and including rigid non-metallic PVC Concealed conduit of 20mm dia or higher, medium grade complete with and including all PVC conduit accessories and modular metal flush box,modular white cover plate with frame, blanking plate etc suitable for upto required module etc complete and making good disturbed surfaces to match the existing for one light / bell / fan point controlled by one, one way switch 06 Amp, complete all as specified and as directed. |
| 4 | Description all as per item No. 3.00 here in before but for one three pin, 5 Amp, socket out let on same board complete all as specified and as directed. |
| 5 | Description all as per item No. 3.00 here in before but for one three pin, 5 Amp, socket out let on Independent board complete all as specified and as directed. |
| 6 | Description all as per item No. 3.00 here in before but point wiring with 2.5 Sqmm, multistranded, copper conductor cable, for 15 Amps socket outlet on independent board with 2.5 Sqmm size earth conductor complete all as specified and as directed. |
| 7 | Description all as per item No. 3.00 here in before but point wiring with 4 Sqmm, multistranded, copper conductor cable,on independent board with 4 Sqmm size earth conductor complete all as specified and as directed. |
| 8 | S&F in repalacement sheet metal enclosure with socket plug top, single pole and neutral enclosure with a two pin earth plug and socket complete with one MCB of capacity 20 Amps , 240 Volts complete all as specified and directed. |
| 9 | S&F modular Socket, 6Amp, 2/3 Pin, combined, 2 module complete all as specified and as directed. |
| 10 | S&F modular switch, 1 way, 6 Amp, 1 Module, complete all as specified and as directed. |
| 11 | S&F modular Socket, 16/6 Amp, 3/5 Pin, combined, 2 module complete all as specified and as directed. |
| 12 | S&F modular switch, 1 way, 16 Amp, 1 Module, complete all as specified and as directed. |
| 13 | S&F modular blanking plate, 1 Module complete all as specified and as directed. |
| 14 | M&L for sub main wiring with 2 runs of 10 sqmm single core, PVC insulated & unsheathed cable 1100 Volts grade with multi stranded, copper conductor drawn through concealed conduit including PVC rigid conduit 25 mm medium grade as per ISS and one run of 06 sqmm size earth wire PVC insulated copper conductor complete all as specified and directed.(Note Two runs of 10 sqmm copper FRLS cable & one run of 10 sqmm copper cable in and including 25 mm PVC conduit medium grade will be measured as one unit. |
| 15 | M&L for sub main wiring with 2 runs of 6 sqmm single core, PVC insulated & unsheathed cable 1100 Volts grade with multi stranded, copper conductor drawn through concealed conduit including PVC rigid conduit 25 mm medium grade as per ISS and one run of 06 sqmm size earth wire PVC insulated copper conductor complete all as specified and directed.(Note Two runs of 6 sqmm copper FRLS cable & one run of 06 sqmm copper cable in and including 25 mm PVC conduit medium grade will be measured as one unit. |
| 16 | S&F Ceiling rose, PVC/ polycarbonate, isolated body type, three terminal, 240 volt, fixed in position & connecting complete all as specified and as directed. |
| 17 | S&F in replacement Bldg security light fitting LED 25 Watt, highly efficient IP66 LED, high power having aluminium pressure die cast housing and PC cover in the front and high power lens for batwing light distribution with electric connection with suitable size of PVC insulated copper wire including GI bracket 1.5 Mtr with clamps and bolts complete all as specified and directed. |
| 18 | Supply, fixing and connecting in replacement of Slim LED Batten 10 watt with Surface/Wall Mounted integrated LED 2 feet Fitting Polycarbonate housing and diffuser with viewing angle of 120 degree used to enhance the luman output Height suitable for White Housing & Isolated Electronic Driver, with Output Short-circuit protection, Surge Voltage protection up to 2.5 KV . Total system Lumen of 10W Led should be 1000 or above in Cool day Light(6500K), Power factor>0.9, CRI (Ra) >80, System with Average life of 50000 Burning hours complete with all accessories as required complete all as specified and as directed. |
| 19 | Supply, fixing and connecting in replacement of Slim LED Batten 20 watt with Surface/Wall Mounted integrated LED 4 feet Fitting Polycarbonate housing and diffuser with viewing angle of 120 degree used to enhance the luman output Height suitable for White Housing & Isolated Electronic Driver, with Output Short-circuit protection, Surge Voltage protection up to 2.5 KV . Total system Lumen of 20W Led should be 2000 or above in Cool day Light(6500K), Power factor>0.9, CRI (Ra) >80, System with Average life of 50000 Burning hours complete with all accessories as required complete all as specified and as directed. |
| 20 | Supply, fixing and connecting in replacement recessed mounting back- lit LED 2'X2', 36 watt tile in CRCA housing with full opal diffuser suitable for Armstrong/ Grid Ceilings Type, size 595X595mm (Nominal),High lumen efficacy LED with viewing angle of 120 degree used to enhance the luman output Height suitable for White Housing & Isolated Electronic Driver, with Output Short-circuit protection, Surge Voltage protection minimum 2.5KV, safety & performance test as per IS:15885 Total system Lumen not less than 3600, in Cool day Light (6500K), Power factor>0.95, CRI (Ra) >80 with Average life of 50000 Burning hours complete with all accessories as required complete all as specified and as directed. Make : ORIENT/ Havells/ Philips |
| 21 | S & F in replacement Heavy Duty Metallic Ventillation Fan 300 mm sweep 240 Volt, 1325RPM , Air delivery 500 CMM connection with self closing louver frame flexible PVC copper wire from ceiling rose to exhaust fan including provn of opening of hole on brick wall and grouting nut and bolt of suitable size complete all as specified and directed. |
| 22 | S&F modular Fan step regulator, 120W - 2 module complete all as specified and as directed. |
| 23 | Supply & fixing of ceiling fan, 5 star rating (White colour) 230 V, 1200 mm sweep, speed 340 RPM, having rod length 300 mm complete all as specified and directed by Enggr in charge. |
| 24 | S&F in replacement load line, distribution board, double door type, VTPN 4 way, suitable for accomodating upto 125 Amps MCCB with incomming frame three pole, including 250 Amp copper bus bar, neutral link, blanking plates etc complete all as specified and as directed. Make : Legrand /Havells / L&T |
| 25 | M&L Earthing complete with galvanised Iron earth plate eletrode 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25mtrdeep below GL) with top edge of the plate not less than 1.5 metre below normal grond level, surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15cm all round the plate with using 4mm dia GI wire as earth wire electrode welded and revetted to earth plate at one end connected to main DBs of Building at another end GI earth wire encased in and including 15mm bore GI light grade pipe through upper end of earth plate upto main DB of bldg, with 20mm bore GI pipe light grade as water pipe from earth chamber to upper edge of earth plate, MS funnel with wire mesh fixed on water pipe including execvation earth work, Provn of PCC pit in PCC 1:2:4 type B-1 chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type BI duly reinforeced with MS bars 8mm dia @ 150 mm centre to centre, both ways complete with lifting handle all as shown in electrical plate No 3 of SSR of part-I complete all as specified and as directed. |
| 26 | S & F in replacement for distribution board double door type, SPN, 16 way, complete including 200 Amps rated bus bar, neutral link, blanking plates etc complete all as specified and directed. Make-Legrend/ Havells/ ABB |
| 27 | S & F in replacement for distribution board double door type, SPN, 12 way, complete including 200 Amps rated bus bar, neutral link, blanking plates etc complete all as specified and directed. Make-Legrend/ Havells/ ABB |
| 28 | Supply and Fixing of five star rated Geysers white blue in colour capacity 25 Ltr, Electric Driven, Single phase, 240 V, Storage vertical type and heating element 2 KW, inner shell made up of copper, automatic cutoff,manual tempreture setting , maintaining 8 bar pressue including electrical and water connection with hot and cold water connection pipe (PVC type) and fixed on the wall with mild steel fastner 150 mm long and 10 mm dia with pin and bolts complete all as specified and directed. |
| 29 | S & F in replacement MCCB 415 V, 125 Amps, 25 KA, 4 Pole complete all as specified and directed. |
| 30 | S & F in replacement MCB DP, 240 Volts, 63 Amps complete all as specified and directed. |
| 31 | S & F in replacement MCB SP, 240 Volts, 10 Amps complete all as specified and directed. |
| 32 | S & F in replacement MCB SP, 240 Volts, 16 Amps complete all as specified and directed. |
| 33 | S & F in replacement MCB SP, 240 Volts, 25 Amps complete all as specified and directed. |
| 34 | S & F in replacement MCB SP, 240 Volts, 63 Amps complete all as specified and directed. |
| 35 | Supply, Installation, Testing & Commissioning (SITC) of 50 KVA, Three-Phase AMF Panel with General Specifications Rating of suitable for a 50 KVA, 3-Phase, 4-Wire, 415 V,50Hz Diesel Generator (DG) set. Having enclosure floor-mounted, totally enclosed, dust, and vermin-proof CRCA Sheet Steel panel, minimum 14/16 {SWG}, with suitable stiffeners and a durable powder-coated finish. Ingress Protection: Minimum IP54 degree of protection.Busbar: High conductivity Copper Busbars of adequate size to handle the maximum continuous current 200 Amp rating and withstand with a specified short-circuit fault level for 1 second. Termination: Suitable gland plates and termination arrangement for incoming Mains cable, outgoing Load cable, and DG cable. Automatic Transfer Switch (ATS) and Changeover: Electrically and mechanically interlocked 4-Pole Contactors or Motorized Changeover Switch, rated for a minimum of 100 Amp at 415 Volt AC, suitable for continuous duty, one for Mains and one for DG supply with manual provision of changeover switch of 100 Amp rating for bypass arrangement. AMF Controller: Microprocessor-based, programmable AMF Controller/Relay for auto-start/stop of DG, monitoring Mains/DG voltage and frequency, and controlling the automatic changeover with adjustable timers (start delay, cool-down, transfer time, etc.). Metering & Indication: Digital Multi-Function Meter (MFM) to display Volts (V), Amps (A), Frequency (Hz), Power Factor (PF), Kilowatts (kW), and Energy (kWh) for both Mains and DG supply. Protection: Fuses/MCBs for control circuits, and over-current/short-circuit protection devices (e.g., MCCB/MCB) on the output side, suitable for the load current. Auxiliary Components: Control wiring, terminal blocks, selector switches (Auto/Manual), Emergency Stop button, indicating lamps (Mains ON, DG ON, Load ON, Trip), Battery Charger (built-in or standalone, suitable for DG starting battery), and necessary interlocks complete in all aspect including necessary PCC foundation complete in all aspect. |
| 36 | Supply testing and commisioning of LT panel board made out of 3.15 mm thick CRCA sheet and 50 x 50 x 6 mm thick angle iron frame duly power coated outdoor type suitable for 3 phase 4 wire system 415 volts 50 HZ with copper bus bar of capacity 400 amps with epoxy inslulators pre wired with single core PVC insulated multistranded copper conductor cable 1100 volts grade with digital volts meter 0-500 volts and ammeter 0-350 amps with suitable CTs and LED type indicator lamps for 3 phase and selector switch for volt meter and ammeter, danger notice board etc. All switch gear must be placed individually cubicle and provision of cable glands for incomming and out going cable as per cable size. The LT panel board should comprising of the following :-(a) MCCB conforming to IS 13947(P-2) 4 pole 400 amps, 415 volts AC 50 HZ adjusable type , breaking capacity 36 KA - 01 No (Incomer).(b) MCCB conforming to IS 13947(P-2) 4 pole 100 amps , 415 volts AC 50 HZ adjustable , breaking capacity 25 KA- 04 Nos . (Outgoing)(b) MCCB conforming to IS 13947(P-2) 4 pole 63 amps , 415 volts AC 50 HZ adjustable , breaking capacity 25 KA- 02 Nos. (Outgoing)Note :- The cost of panel board will be included all necessary civil works (i.e., PCC work, MS stand for fixing or installation of Panel |
| 37 | Supply, laying, jointing and testing of LT XLPE and PVC insulated, screened, armoured, LT electric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 185 Sqmm 3.5 core complete all as specified and directed. |
| 38 | Supply, laying, jointing and testing of LT XLPE and PVC insulated, screened, armoured, LT electric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 70 Sqmm 3.5 core complete all as specified and directed. |
| 39 | Supply, laying, jointing and testing of LT XLPE and PVC insulated, screened, armoured, LT electric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 50 Sqmm 3.5 core complete all as specified and directed. |
| 40 | Supply, laying, jointing and testing of LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 35 Sqmm 3.5 core complete all as specified and directed. |
| 41 | Excavation in trenches in soft loose soil including cutting road surfaces not exc 1.5 mtrs wide and not exc 1.5 mtr. in deep for foundation of poles, stays, cables pipe etc and getting out all as specified. |
| 42 | Returning filling in, of excavated soil in trenches incl spreading, leveling, watering and well ramming in layers each layers not exc 25cm thick in soft/ loose soil all as specified. |
| 43 | Removal surplus spoil to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed. |
| 44 | Supply and spread river sand to required width at bottom and top for cable cushioning all as specified in clause 19.75 of SSR part – I (Note :- thickness of sand will be measured after punning) |
| 45 | Supply and lay common burnt bricks of sub class B old size laid at right angle on the cable complete in trenches for cable protection complete all as directed by Engr-in-charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender