Tender For Erection Of 33 Kv Line And 33 Kv Line Bay At 1X50 Mva, 132/33 Kv Grid Station Jourian For Proposed Industrial Estate At Village Sole Sungal (Scheme Code Indss2425100114) In Respect Of Sub Transmission-I, Jpdcl, Jammu
Tender Overview
Project Description
Tender for Erection Of 33 Kv Line And 33 Kv Line Bay At 1X50 Mva, 132/33 Kv Grid Station Jourian For Proposed Industrial Estate At Village Sole Sungal (Scheme Code Indss2425100114) In Respect Of Sub Transmission-I, Jpdcl, Jammu
BOQ
| Sl. No. | Item Description |
| 1 | 13 Mtr. Long Pole (ST-410 SP69) |
| 2 | GI V cross-arm with top Bracket including clamp |
| 3 | GI Channel X-arm including clamps and braces |
| 4 | 150 mm² ACSR Conductor |
| 5 | PG Clamps for 150 mm² ACSR Conductor |
| 6 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 7 | 33kV Polymeric composite Disc Insulator 36kV, min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 8 | Galvanized Nuts and Bolts. |
| 9 | Danger Plates with Clamps |
| 10 | Anti-Climbing Device with Clamps |
| 11 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 12 | Red Oxide |
| 13 | Aluminium Paint |
| 14 | Cement bottoming 1:2:4 mix as per REC standards 0.7cum /pole |
| 15 | Aluminium Jointing Sleeves |
| 16 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator (2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 17 | Guard netting |
| 18 | 33 KV Isolator without Earthing Blade (36KV, 1250A, Outdoor, 3 Poles, 25 KA) |
| 19 | GI Channel / Angle Iron Including Clamps |
| 20 | 150mm2 ACSR Conductor |
| 21 | Galvanized Nuts and Bolts. |
| 22 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator (2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender