Tender For The Project Involved The Installation Of Air Conditioning In The Courtrooms And Rest Rooms Of The District Judge And Additional Judge At The Basti District Court, The Establishment Of An Integrated Electrical Substation, And Cabling Work For Th
Tender Overview
Project Description
Tender For The Project Involved The Installation Of Air Conditioning In The Courtrooms And Rest Rooms Of The District Judge And Additional Judge At The Basti District Court, The Establishment Of An Integrated Electrical Substation, And Cabling Work For The Electrical Connections Of Various Buildings.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 21-Jul-2026 | corrigendum | Date | 03-Aug-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Part - A (Electrical Work) Supply, Installation, Testing amd Commissioning of LT Panel vermin proof floor mounting , M.S. channel base with bottom and Fabricated out of 2.0/1.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineer In-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating.The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit of 50kA for panels having ACB as Incomer & 36kA for panels having MCCB Incomers. Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be completed in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering. All Incomer Feeders shall be provided with Multifunction Metering along with Phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. and all Outgoing Feeders 100A & above shall be provided with 3 phase Ammeter along with phase Indicating Lights and other associated components such as CT, control MCB Terminal Block etc. The Feeders above shall be provided ac accommodated all Measuring Instruments shall be Digital type & all Indicating Lights shall be LED type. Wiring shall be done from 1100V Grade PVC Insulated copper flexible wire. All ACB shall be Electrically operated Draw-out type with Microprocessor Based O/L, S/C & E/F Release of Breaking/ Withstand Capacity (ICU/ICs/Icw) 50kA or more All MCCB shall be Thermal Magneetic /Microprocessor with O/L & S/C Protection along with Required Spreaders & Extended Rotary Handle with pad Locking facility of Breaking capacity (ICU/ICS) 36kA or more All MCB shall be Thermal 10kA 'C' Curve. Cubicle type switch board shall be Cat-A and B only. I/C 400 Amp MCCB-1 No & O/G 200 Amp MCCB-2 Nos , 100 Amp MCCB-1 No and 63 Amp MCCB-1 NO Cat. B Pannel Cubicle Type |
| 2 | incomming: 200 amp MCCB- 01 Nos & Outgoing 63Amp MCCB- 03Nos Cat. B Pannel Cubicle Type |
| 3 | incomming: 100 amp MCCB- 01 Nos & Outgoing 63Amp MCCB- 02 Nos Cat. B Pannel Cubicle Type |
| 4 | Suppling and Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size on wall surface as required. 25 sqmm 3-1/2 Core |
| 5 | 150 sqmm 3-1/2 Core |
| 6 | 50 sqmm 3-1/2 Core |
| 7 | Supplying and fixing 4way (4+12) Double Door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Triple Pole and Neutral) |
| 9 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socketoutlet and 25 A modular SP MCB, \\"C\\" curve includingconnections, painting etc. as required. |
| 10 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2X 6sq.mm+1X6sq. mm earth wire |
| 11 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 12 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 13 | Providing and fixing 25 mm X 5 mm Copper strip on surface or in recess for connections etc. as required. |
| 14 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/cable as required. |
| 15 | Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 16 | Part- B (AC Work) - Supplying, Installation,Testing and Commissioning of 2.0 TR with 5 Star BEE Rating Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 52 0C (out door ambient temperature).Make:-O General/Mitsubishi/Daikin/Hitachi/ Carrier/Panasonic/Bluestar/LG/Voltas |
| 17 | Supplying, Installation,Testing and Commissioning of 1.5 TR with 5 Star BEE Rating Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180- 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 52 0C (out door ambient temperature).Make:-O General/Mitsubishi/Daikin/Hitachi/ Carrier/Panasonic/Bluestar/LG/Voltas |
| 18 | SITC of 4 KVA Automatic Voltage Stablizer (130-280V) Copper Winding |
| 19 | SITC of 5 KVA Automatic Voltage Stablizer (130-280V) Copper Winding |
| 20 | Supplying and Laying of 2.5sqmm, 4 core Round Copper cable for indoor unit to outdoor unit of AC . |
| 21 | Supplying and Laying of 2.5sqmm, 3 core Round copper cable for Stabilzer to Indoor unit. |
| 22 | SITC of suction/Discharge Both Copper pipe line in split A.C unit 1.5 ton capacity including cost of brazing,nitrile rubber insulation 6 mm thick class O etc comlete 1/4\\" (6.40mm) and 1/2\\" (12.70 mm) |
| 23 | SITC of suction/Discharge Both Copper pipe line in split A.C unit 1.8/2.0 ton capacity including cost of brazing,nitrile rubber insulation 9 mm thick class O etc complete 3/8\\" (9.50 mm) and 5/8\\" (15.90 mm) |
| 24 | Supplying and Laying of heavy duty PVC Plastic Braided 20mm OD Flexible pipe for condensed water drain with clipping, accessories complete. |
| 25 | Supplying and Laying of heavy duty PVC Plastic Braided 32 mm OD Flexible pipe for condensed water drain with clipping, accessories complete. |
| 26 | Supply and fixing of Out Door Unit stand for split A.C |
| 27 | Supply, Fabrication and installation of M.S. cage for protection of Outdoor unit from animal/theft L X W X H 1300 mmX 600 mm X 1200 MM complete in all respect. |
| 28 | Supply and fixing of Door closer |
| 29 | Part - C (Integrated Electrical Sub-Station) Supplying, Installation Testing and Commissioning of 400 KVA, 33/0.433 KV TRANSFORMER 8 Steps having Cable Box (HT)/ Cable Box (LT side) |
| 30 | Supply Installation,Testing and commissioning of 250A DG Panel MAINS Incomer 250A - 3 Set (Each Consisting of) MCCB 250Amp. 4P, 36kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader Digital 3 Phase VAF Meter CTR-/5A, 500V along CT 250/5A, Cl.1, Capsulated Bar Primary (Metering) Phase Indicating Lights (Red, Yellow, Blue) 22.5 230V AC CT Terminals Disconnecting Type 10A.DG Incomer 250A - 3 Set (Each Consisting of) MCCB 250A Amp, 4Pole 250A MOT. CHANGEOVER SWITCH Digital 3 Phase VAF Meter CTR-/5A, 500V along CT 250/5A, Cl.1, Capsulated Bar Primary (Metering) Phase Indicating Lights (Red, Yellow, Blue) 22.5 230V AC start/stop Push button Emergency Stop Push button Battery Charger 230V AC/ 24V DC, Automatic Trickle / Boost for DG Battery Charging DC Voltmeter Analog Type 0-30V DC DC Ammeter Analog Type 0-30A DC Control MCB 6 Amp SP, 100kA CT Terminals Disconnecting Type 10A Aux. Relays Aux. Terminals. BUSCOUPLER 250A - 2 Set Each Consisting of MCCB 250Amp. 4P, 36kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader.OUTGOING 200A -3 set Each Consisting of MCCB 200Amp. 4P, 36kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader.OUTGOING 100A - 3 set Each Consisting of MCCB 100Amp. 4P, 36kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader.OUTGOING 63A - 3 set Each Consisting of MCCB 63Amp. 4P, 25kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader 250A D.G. PANEL.MAINS Incomer 250A - 3 Set (Each Consisting of) MCCB 250Amp. 4P, 36kA with O/L, & S/C Protection Release Along with extended Rotary Handle & Spreader Digital 3 Phase VAF Meter CTR-/5A, 500V along CT 250/5A, Cl.1, Capsulated Bar Primary (Metering) Phase Indicating Lights (Red, Yellow, Blue) 22.5, 230V AC. |
| 31 | Supply and erection of factory fabricated and wired metal clad dust and vermin proof floor mounting MS channel base with bottom and top cable entries. Electrical control panel with TPN MCCB (four pole 36 KA with Thermal magnetic release) and instrument channel etc complete in all respect. The instrument chamber shall be separate having digital metering system for phase to phase voltage and single phase voltage cure and other parameters in each phase with touch type selector switches The panel board shall have suitable capacity electrolytic aluminum bus bar as per IS 8623 insulated with heat sink sleeving and mounted on nonhygroscopic support such as CMC/BMC support with detachable side cover and shall be suitable for extension on the side. The MCCB shall be complete with suitable cable end boxes compression gland and indicating lamp on incoming etc The panel board shall be fabricated with CRCA sheet with minimum thickness of 1.6 mm/2.0 mm with following details. Incomer : 630A /415Volt 4P MCCB 1No (36KA) ,Digital volt meter, 0-500v, ammeter, selector switches .CT,s etc LED Type phase indicator, set of copper Bus Bar300amp Outgoing : 400Amp 4P,36kA MCCB -01 Nos. with suitable Automatic star/Delta starter with over load protection, current Sentencing type Single phase preventer with all accessories and internal wiring. Incomer : 630A /415Volt 4P MCCB 1No (36KA) ,Digital volt meter, 0-500v, ammeter, selector switches .CT,s etc LED Type phase indicator, set of copper Bus Bar300amp Incomer : 630A /415Volt 4P MCCB 1No (36KA) ,Digital volt meter, 0-500v, ammeter, selector switches .CT,s etc LED Type phase indicator, set of copper Bus Bar300amp Outgoing : 400Amp 4P,36kA MCCB -01 Nos. with suitable Automatic star/Delta starter with over load protection, current Sentencing type Single phase preventer with all accessories and internal wiring. |
| 32 | Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed M.S clamps etc of suitable size or as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. As above for 3.5 X 25 sq. mm |
| 33 | As above for 3.5 X 50 sq. mm |
| 34 | As above for 3.5 X 150 sq. mm |
| 35 | As above for 3.5 X 240 sq. mm |
| 36 | As above for 3.5 X 400 sq. mm |
| 37 | Supplying and Laying of one number XLPE power cable of 33 KV grade of 120 sq.mm in the existing RCC/ HUME/ METAL pipe as required. |
| 38 | Supply and fixing of 7 mtr. GJ. Octagonal pole of approved make (top dia 70 mm, Bottom dia 130 mm & Base plate 12 mm thick) having 3 mm, thickness with single ann bracket length of 1 mtr. length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T & P complete in all respect |
| 39 | Supply and fixing of LED Street light Fitting with mandatory driver set having die cast aluminium body with toughend glass/ UV stabilized PC Cover and lenses suitable for 75 Watt. to 90 Watt and Confirming to IP 66, and IK07 and above protection having Company LOGO Engraved complete in all respect including Labour. |
| 40 | Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750 mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 41 | Supply and fixing following capacity of automatic street light cubical control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contactors. HRC fuses isolating switch metering instrument & Instrument box with CTs etc. in case of 40 Amp TPN complete in all respect. |
| 42 | Supply and fixing of fire extinguisher, ABC Type 4.00kg. capacity (ISI Marked IS : 15683 & TAC approved)complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 43 | Supply and fixing of C02 type fire extinguisher 4.5 kg. capacity (ISI Marked IS : 2878 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 44 | Earthing with copper earth plate 600 mm X 600 mm X3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 45 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required. |
| 46 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 47 | Wiring for circuit/ submain wiring alongwith earth wire with the 4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.(Used as Control cable 6 core 2.5 sq. mm) |
| 48 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 120 sq.mm. of 3 core, XLPE aluminium conductor cable of 33 KV grade as required: |
| 49 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 120 sq.mm. of 3 core, XLPE aluminium conductor cable of 33 KV grade as required |
| 50 | Earthing with G.I earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 51 | Providing and fixing earth bus of 50 mm X 6 mm Copper. strip on surface or in recess for connections etc. as required. |
| 52 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 53 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 54 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 55 | Supplying and fixing of brass batten/ angle holder including connection etc. as required. |
| 56 | Supplying and fixing of 5/6 A modular switch and 3 pin 5/6 A socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 57 | Supplying and fixing 8 way , Double door, single pole and neutral, sheet steel, MCB distribution board (SPN DB), 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 58 | Supplying and fixing 5 A to 32 A rating (as required), 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Double pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 59 | Supplying and fixing 5 A to 32 A rating (as required), 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 60 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core (multi stranded) cable in surface/ recessed medium class PVC conduit as required. 2X 2.5sq.mm+1X2.5sq. mm earth wire |
| 61 | 2X4sq.mm+ 1X4 sq. mm earth wire |
| 62 | 2X 6sq.mm+1X6sq. mm earth wire |
| 63 | Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. . |
| 64 | Supplying and fixing of 25 mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 65 | Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 66 | Brush Less Direct Current (BLDC) Fan without Remote Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 67 | LED Batten light (System lumen efficacy ≥120 <135 lm/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range-5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5 %), life time (LED,Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 18-22 Watt Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 10 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender