Tender For Regularly Operation And Maintanance Of Complete Electric Work At Main And Other Jda Building (Amc)
Tender Value
93.25 Lakhs
Estimated cost
Bid Submission
15 Jul 2026
6 days left
EMD
1.86 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jodhpur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Regularly Operation And Maintanance Of Complete Electric Work At Main And Other Jda Building (Amc)
BOQ
| Sl. No. | Item Description |
| 1 | Providing Manpower through Contracting agency for Supervision / Execution / Operation of various Electromechanical Installations. (one shift of 8 working Hrs per day for 26 Working Days in a month) on basis of minimum wages + VDA order Dt. 28.03.2025 Ministry of Labour and Employement Govt. of India |
| 2 | Pump Operator, AC Plant Operator, ELV System Operator, Lift Operator, DG set Operator or any other services operator with experience of 3 years in relevant field ) |
| 3 | Technical Helper Having basic Knowledge of E&M Services |
| 4 | Pump Operator, AC Plant Operator, ELV System Operator, Lift Operator, DG set Operator or any other services operator with experience of 3 years in relevant field ) |
| 5 | Pump Operator, AC Plant Operator, ELV System Operator, Lift Operator, DG set Operator or any other services operator with experience of 3 years in relevant field ) |
| 6 | Technical Helper Having basic Knowledge of E&M Services |
| 7 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 8 | Short point (up to 3 mtr.) |
| 9 | Medium point (up to 6 mtr.) |
| 10 | Long point (up to 10 mtr.) |
| 11 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos 6 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 12 | Short point (up to 3 mtr.) |
| 13 | Medium point (up to 6 mtr.) |
| 14 | Long point (up to 10 mtr.) |
| 15 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 16 | On board |
| 17 | Short point (up to 3 mtr.) |
| 18 | Medium point (up to 6 mtr.) |
| 19 | Long point (up to 10 mtr..) |
| 20 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 21 | 20 mm x 12 mm |
| 22 | 25 mm x 12 mm |
| 23 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 24 | 1 x 1.5 sq.mm |
| 25 | 1 x 2.5 sq.mm |
| 26 | 1 x 4.0 sq.mm |
| 27 | 1 x 6.0 sq.mm |
| 28 | Supply & laying service connection with ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. |
| 29 | 6.0 sq.mm |
| 30 | 10.0 sq.mm |
| 31 | Supply and Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 32 | 1.5 Sq.mm 3 core flat / Round |
| 33 | 2.5 Sq.mm 3 core flat / Round |
| 34 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 35 | Single pole MCB (With B / C curve tripping characteristics) |
| 36 | 6 A to 32 A rating |
| 37 | 40 A rating |
| 38 | 50/63 A rating |
| 39 | Double pole MCB(With B/C curve tripping Characteristics) |
| 40 | 6 A to 32 A rating |
| 41 | 40 A rating |
| 42 | 50/63 A rating |
| 43 | Four pole MCB (With B/C curve tripping Characteristics) |
| 44 | 6 A to 32 A rating |
| 45 | 40 A rating |
| 46 | 50/63 A rating |
| 47 | Providing & Fixing of 240/415 V isolator ISI marked IS:13947-III/conforming to IEC 60947-3, suitable for AC22A utilization catagory, 4KV impulse withstand voltage, true contact indication, Red colour dolly / lever shall have single mould covering over all poles for operation , two position din rail mounting, minimum phase termination capacity of 25sq.mm. IP 20 contact protection and fitted in existing distribution board / sheet including making connections, testing etc. as required. |
| 48 | Double pole isolator |
| 49 | 30 A / 40 A rating |
| 50 | 63 A rating |
| 51 | Four pole Isolator |
| 52 | 40 A rating |
| 53 | 63 A rating |
| 54 | 80 A/ 100 A rating |
| 55 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 56 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 57 | 4 Way |
| 58 | 6 Way |
| 59 | 8 Way |
| 60 | 12 Way |
| 61 | P&F metal clad / Polyamide industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. (without MCB) including making connections, testing etc.as required. |
| 62 | 20 amp, (2P + E), 3 Module |
| 63 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 64 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 65 | Providing & Fixing of 6 amp. Combined flush type non modular socket and switch set made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 66 | Providing & Fixing of 16 amp. Combined flush type non modular socket and switch set with indicator and fuse set, made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 67 | Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push surface type CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 68 | Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A switch surface type, CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 69 | Providing & Fixing of non modular 6A hanging bell push/one way switch made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 70 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 71 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 72 | Providing & Fixing of ISI marked (IS:1293) 16 amp unbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal including making connection testing etc. as required. |
| 73 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 74 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 75 | Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required. |
| 76 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 77 | 10 A one way switch |
| 78 | 10 A two way switch |
| 79 | 16 A one way switch With Led Indicator |
| 80 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 81 | 6 A 3 pin shuttered socket |
| 82 | 6/16 A shuttered socket |
| 83 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 84 | 5 step fan regulator 2 Module |
| 85 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 86 | USB Charger 1 A - 1 M with BIS mark |
| 87 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 88 | 3 Module |
| 89 | 6 Module |
| 90 | 8 Module |
| 91 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 92 | 1-2 Module |
| 93 | 3 Module |
| 94 | 4/5 Module |
| 95 | 6 / 8 module |
| 96 | 10 / 12 module |
| 97 | Providing & Fixing of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid aberration marks and pasting the mat with synthetic rubber adhesive as required. |
| 98 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 99 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor confirming to IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. |
| 100 | 3 pole Power contactors with following AC 3 Rating |
| 101 | 95 Amp |
| 102 | 400 Amp |
| 103 | 4 pole Power contactors with following AC 1 Rating |
| 104 | 63 Amp |
| 105 | 100/105 Amp |
| 106 | 200 Amp |
| 107 | Providing & Fixing of Electromechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. |
| 108 | One day & week reserve (digital type ) |
| 109 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 110 | 4 pole MCCB With Thermal Magnetic release |
| 111 | up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting |
| 112 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 113 | 200 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 114 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 115 | Providing & Fixing of TP&N 415 V AC-23A front handle operated switch disconnector fuse unit, cubical type, with metallic enclosure confirming to IS/lEC 60947-3 : 1999 with HBC fuses including making connections with lugs, testing etc as required. |
| 116 | 63 A rating |
| 117 | 100/125 A rating |
| 118 | Providing & Fixing of Four Pole By pass Change Over Switch confirming to IS:13947(Part 3) : IEC:60947-3-1 and IEC:60947-6-1, Open execution type in the following ratings. |
| 119 | 400 A |
| 120 | Providing & Laying XLPE insulated & P.V.C. sheathed Un-Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing commissioning etc. as required of following size. |
| 121 | 10.0 Sq. mm |
| 122 | 4 core |
| 123 | 25.0 Sq. mm |
| 124 | 3 core |
| 125 | 16.0 Sq. mm |
| 126 | 4 core |
| 127 | 185.0 Sq. mm |
| 128 | 3.5 core |
| 129 | 120.0 Sq. mm |
| 130 | 3.5 core |
| 131 | 300.0 Sq. mm |
| 132 | 3.5 core |
| 133 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 134 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 135 | 8 SWG tinned copper Wire |
| 136 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 137 | 1200 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) |
| 138 | 1400 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 ) |
| 139 | Providing & Fixing of of M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed with cement concrete mortar with required support as required. |
| 140 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. |
| 141 | 300 mm sweep Minimum air delivery 1600 Cum / hour |
| 142 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required. |
| 143 | 450 mm sweep(1400 RPM) |
| 144 | Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts, making connection testing etc. as required. |
| 145 | 450 mm sweep Wall mounting and three speed regulator with Minimum Air Delivery 150 Cum. / Minute |
| 146 | Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap action adjustable thermostat , Dual indicating lamps Injected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top , including making inlet, outlet Flexible alloy connection, testing etc. as required. |
| 147 | 25 Ltr. |
| 148 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 149 | Recessed Mounting |
| 150 | Minimum lumen output 1300 lm |
| 151 | Minimum lumen output 1600 lm |
| 152 | Surface Mounting (with extruded alumn. Housing ) |
| 153 | Minimum lumen output 1300 lm |
| 154 | SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 155 | Recessed Mounting |
| 156 | Minimum lumen output 4800 lm |
| 157 | Surface Mounting (Driver should be Inside the Luminaire) |
| 158 | Minimum lumen output 4800 lm |
| 159 | SITC of energy efficient /energy saving IP 20 LED direct retrofit Bulb in existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf 0.95 , CRI >70, minimum life time of minimum 25000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 160 | 9 Watt |
| 161 | 15 Watt |
| 162 | 18/20 Watt |
| 163 | SITC of IP 20 box made out from 1.0 mm thick CRCA sheet steel with depth of minimun 30 mm and finished with powder coating and suitable for mounting LED tube including side covers, holders , internal wiring to illuminate the single sided connection LED tube. ( Without tube). |
| 164 | Suitable for 4' LED Tube shape fixture for single rod |
| 165 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 166 | LED Street Light fixture with Minimum lumen output 15000 lm |
| 167 | Labour charges for installation of submersible motor pump set including lowering/ delowering of pipes, cables, accessories etc. in tube-well/ open well complete including T&P, transportation of tripod, chain pulley block & any other material required for this purpose complete in all respect. |
| 168 | Delowering and Lowering |
| 169 | SITC of Radial / mixed flow water and anti-corrosive liquid filled submersible motor pump sets suitable for 100/150mm dia borewell. The size of adopter fixed on top of the motor should exceed the top of coupler , for safegaurd the coupler. The job includes labour part of lowering of riser pipe G.I./ H.D.P.E. with rope, cables & pump, installation of complete fitting and accessories, jointing of electrical cables up to Starter. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect. |
| 170 | 10.0 HP, 3-Ø, (110 - 212)Mtr, (400-167) LPM |
| 171 | SITC of Monoblock closed coupled motor pump set with TEFC motor, motor should be IP55-F class and IE2 efficiency for monobloc, with carbon steel /SS-410 shaft, Mechanical seal, Single/Three phase Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively and Dynamically balanced rotating parts to ensure min. vibration etc. complete in all respect. |
| 172 | 1.0 HP, 1-Ø, (10-30)Mtr, (76-28) LPM ( Bronze impeller & Aluminium Body) |
| 173 | 1.0 HP, 1-Ø, (10-30)Mtr, (76-28) LPM ( Bronze impeller & CI Body) |
| 174 | Supply , Installation, Testing and Commissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. Min 5 year Original Equipment Manufacturer (OEM) warranty of both compressor and Printed Circuit Board (PCB). |
| 175 | Cooling capacity 5000-5300 Watt, ISEER not less then 3.8 |
| 176 | Cooling capacity 6800-7000 Watt, ISEER not less then 3.8 |
| 177 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 178 | 25 mm |
| 179 | Supply, Fixing and testing of following capacity IS:8448 marked wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrial plug top making connection etc complete in all respect. |
| 180 | 5 kVA |
| 181 | Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia |
| 182 | 100 mm dia per running inch length |
| 183 | 150 mm dia per running inch length |
| 184 | Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge. |
| 185 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves (size as per item no. 22.43),7 mil Glass Cloth with 3 coats of anti UV paint (on area which is exposed to weather) chase cutting, supports, making good the same with sand cement plaster etc. as required. |
| 186 | Supply & Fixing of CO2 type Fire Extinguisher conforming to IS:15683:2018, charged with CO2 gas (purity 99.7% conforming to IS 15222), Powder coated Internal & External Surface Manganese steel ISI marked as per IS 7285 cylinder body , Wheel type Forged brass release valve ISI Marked as per IS 3224 with Inbuilt safety release device ((Fusible plug and Rupture Disc Type), 1.0 Mtr. Metal wire braided hose having minimum bursting pressure of 140 Kgf/cm2, Horn with metallic thread connection, QR code for Product Traceability, including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 187 | Capacity 4.5 Kg. |
| 188 | Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC type Fire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificate from OEM / External NABL Accrediated Lab is to be submitted. |
| 189 | Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. (New model ceiling fan) |
| 190 | 900/1200 mm sweep (New model ceiling fan) |
| 191 | 1400 mm sweep (New model ceiling fan) |
| 192 | All sizes (Old model ceiling fan) |
| 193 | Labour charges for removing and refixing of Ceiling fan/ Exhaust fan from site |
| 194 | Providing and Replacement of ball bearing of ceiling/ exhaust fan and refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material shall be retained by the contractor. |
| 195 | Provinding & Replacement of M.S. Shaft of ceiling fan. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 196 | P & F Aluminium Blades (a set of 3 blades) duly painted and well finished 900/ 1200 mm. The material of the fan blade shall be of designation 31500B with condition HX6 aluminium alloy sheet confirming to IS 737/2008 |
| 197 | P & F Aluminium Blades (a set of 3 blades) duly painted/ powder coated. ( 1400/ 1500 mm) The material of the fan blade shall be of designation 31500B with condition HX6 aluminium alloy sheet confirming to IS 737/2008 |
| 198 | Providing and Replacement of Gun metal bush of ceiling/exhaust/cooler fan/ as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 199 | Rewinding of Heavy duty Exhaust fan motor including all necessary material,The motor is to be wound taking no. of coils,turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 200 | 300/ 380 mm sweep |
| 201 | 450 mm sweep |
| 202 | Rewinding of single phase motor of 1400 RPM including all necessary material and of the same characteristics as original with required size of super enamelled wire 'E' class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 203 | 0.25 H.P. To 0.50 H.P. |
| 204 | 0.75 H.P. To 1.0 H.P. |
| 205 | 2.0 H.P. |
| 206 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capillary and strainer/ filter. |
| 207 | 1.0 TR Window/ Split A.C. |
| 208 | 1.5 TR Window/ Split A.C. |
| 209 | 2.0 TR Window/ Split A.C. |
| 210 | Replacement of defective compressor by company repaired compressor as per OEM recommendations of following gadgets including testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 211 | 1.0 TR A.C. |
| 212 | 1.5 TR A.C. |
| 213 | 2.0 TR A.C. |
| 214 | P & Replacement of condensing/ cooling coil of copper fins for following capacity A.C./ Water cooler/ Fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 215 | 1.0 TR A.C. |
| 216 | 1.5 TR A.C. |
| 217 | 150/150 Ltr. Water cooler |
| 218 | Servicing of 1.0/1.5/2.0 TR capacity Split/ Window type air conditioner |
| 219 | P & Replacement of overload protection of A.C./ Water cooler as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 220 | P & Replacement of thermostat of A.C./ Water cooler/fridge as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 221 | P & Replacement of selector switch of 1.0/1.5/2.0 TR A.C Fan as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 222 | P & Replacement of starting relay of A.C/water cooler/fridge compressor as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 223 | P & Replacement of fan motor of evaporator/ condensor complete as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 224 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 225 | 100-120 micro farad |
| 226 | Running capacitor |
| 227 | 2.5/3.15 micro farad |
| 228 | 4.0 micro farad |
| 229 | 10.0 micro farad |
| 230 | P & Replacement of plastic/metallic sheet condensor holder suitable for ceiling fan/ exhaust fan /motor etc complete as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 231 | All in all comprehensive maintenance including servicing , replacement of fuel - filter, coolant , lubricating oil etc of Diesel Generating set including auto mains failure (AMF) panel , change over switch , earthing etc as per OEM guidelines and maintenance manual complete in all respet. (Excluding replacement of batteries as and when required.) |
| 232 | Above 62.5 KVA |
| 233 | All in all comprehensive maintenance of Water cooler including compressor, condensing/ cooling coil ,water tank with inner piping including repair / replacement of components like filters, membrane, charging of refrigerants whenever required , cleaning , servicing etc. as per OEM's recommendations and standard terms & conditions of PWD to meet efficient performance of the equipment. |
| 234 | 150/150 Ltr capacity |
| 235 | All in all comprehensive maintenance of Reverse Osmosis water purification system including repair / replacement of components ,consumables , cleaning , servicing etc as per OEM's Guide lines to meet out the TDS level of Water as per client requirement / standard norms to meet efficient performance of the equipment. |
| 236 | 50 Ltr/hr capacity |
| 237 | All in all Comprehensive annual maintenance and repair contract for On line UPS of following Capacity ( Excluding Replacement of Batteries ) |
| 238 | 2 KVA UPS |
| 239 | 30 KVA UPS |
| 240 | S & F of 12V VRLA Lead Acid Sealed maintenance free (SMF) batteries of following capacity with Warranty of 2 years |
| 241 | 65 AH |
| 242 | 150 AH |
| 243 | Supply , Installation, Testing and Comissioning of IS:1475 marked self contained drinking water cooler with hermetically sealed compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz AC supply,Full stainless steel (SS304)body (0.8 mm thick) and tank (0.5 mm thick) , stainless steel water tray,minimum two nos Brass Chrome plated faucets and suitable drainage system complete in all respect with required height MS fabricated and Painted Angle iron frame ( Cost of frame to be paid Extra )complete in all respect of the following capacity. |
| 244 | cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs |
| 245 | SITC of RO water system with Filteration stages = Particilate filter- Membrane life enhancer filter- sediment filter- pre carbon filter- RO membrane filter- post carbon filter. Input power rating -230V AC, 50Hz, percentage of rejection TDS-90% or better, having following features (a) Double purification by RO with ESS or latest technology with TDS indicator. (b) Spin welded RO membrane housing to prevent tempering. (c) Push fit component for leak proof performance. (d) Fully automatic operation with auto start and auto off. (e) SS/ABS construction for corrosion free lifespan. (f) Equally suitable for water from all borewells, overhead storage tanks, water tankers and even municipal taps. (g) RO membrane flushing - Auto flush@ every start, every stop and every one hour of working for one minute, complete in all respect with following capacity. |
| 246 | Purification capacity - 50LPH, duty cycle 270-500 liters/day |
| 247 | Purification capacity - 25LPH, duty cycle 170-250 liters/day |
| 248 | Production capacity- 15 LPH, Water storage capacity 8 ltr |
| 249 | To Continue the TV/LCD services in office and recharge of D2H/Cable TV by depositing money in concerned service for one Month (7*12) |
| 250 | Hire charges for Cooler complete with water filling in all recspect as per direction of Engineering Incharge |
| 251 | Long Body |
| 252 | Short Body |
| 253 | PCB Plat 1.5/2.0 Ton A/C |
| 254 | Swing Moter 1.5/2.0 Ton A/C |
| 255 | Swing Roler 1.5/2.0 Ton A/C Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 08, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 15, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysJul 16, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 7 daysTender Documents
Download All (ZIP) ↓
Disclaimer