Tender For Providing Of Otm Accn For Dental Unit At Mathura Cantt
Tender Value
11.20 Crore
Estimated cost
Bid Submission
11 Aug 2026
27 days left
EMD
8.85 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mathura → Uttar Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Providing Of Otm Accn For Dental Unit At Mathura Cantt
BOQ
| Sl. No. | Item Description |
| 1 | Lump sum price worked out by the contractor for \\"BUILDING WORKS\\" as listed in Schedule ‘A’ Part-I representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 2 | Lump sum price worked out by the contractor for \\"INTERNAL WATER SUPPLY \\" as listed in Schedule ‘A’ Part-II representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 3 | Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-III representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 4 | Lump sum price worked out by the contractor for \\"ROAD, PATH AND CULVERT\\" as listed in Schedule ‘A’ Part-IV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 5 | Lump sum price worked out by the contractor for \\"SEWAGE DISPOSAL\\" as listed in Schedule ‘A’ Part-V representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 6 | Lump sum price worked out by the contractor for \\"AREA DRAINAGE \\" as listed in Schedule ‘A’ Part-VI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 7 | Lump sum price worked out by the contractor for \\"HIGH SECURITY WALL, COMPOUND WALL AND GATE\\" as listed in Schedule ‘A’ Part-VII\\" representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 8 | Lump sum price worked out by the contractor for \\"RAIN WATER HARVESTING\\" as listed in Schedule ‘A’ Part-VIII\\" representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 9 | Lump sum price worked out by the contractor for \\"EXTERNAL WATER SUPPLY\\" as listed in Schedule ‘A’ Part-IX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 10 | Lump sum price worked out by the contractor for \\"EXTERNAL ELECTRIFICATION\\" as listed in Schedule ‘A’ Part-X representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 11 | Lump sum price worked out by the contractor for \\"SUMMER APPLIANCES\\" as listed in Schedule ‘A’ Part-XI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 12 | Lump sum price worked out by the contractor for \\"HOT WATER SUPPLY\\" as listed in Schedule ‘A’ Part-XII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 13 | Lump sum price worked out by the contractor for \\"SPLIT AIR CONDITIONING\\" as listed in Schedule ‘A’ Part-XIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 14 | Lump sum price worked out by the contractor for \\"LIGHTINING PROTECTION\\" as listed in Schedule ‘A’ Part-XIV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 15 | Lump sum price worked out by the contractor for \\"DG SET\\" as listed in Schedule ‘A’ Part-XV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 16 | Lump sum price worked out by the contractor for \\"FIRE FIGHTING\\" as listed in Schedule ‘A’ Part-XVI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 17 | Lump sum price worked out by the contractor for \\"FIRE ALARM as listed in Schedule ‘A’ Part-XVII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 18 | Lump sum price worked out by the contractor for \\"AIR CURTAIN\\" as listed in Schedule ‘A’ Part-XVIII representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 19 | Lump sum price worked out by the contractor for \\"SOLAR STREET LIGHT\\" as listed in Schedule ‘A’ Part-XIX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 20 | Lump sum price worked out by the contractor for \\"FALSE CEILING\\" as listed in Schedule ‘A’ Part-XX representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 21 | Lump sum price worked out by the contractor for \\"TELEPHONE & INTERCOM\\" as listed in Schedule ‘A’ Part-XXI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 22 | Lump sum price worked out by the contractor for \\"VRF AIR CONDITIONER\\" as listed in Schedule ‘A’ Part-XXlI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price of prepriced by the MES |
| 23 | Lump sum price worked out by the contractor for \\"SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK\\" as listed in Schedule ‘A’ Part-XXllI representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 24 | Lump sum price worked out by the contractor for \\"DEMOLITION WORK\\" as listed in Schedule ‘A’ Part-XXlV representing percentage ( + or - denomination) derived under last column of this schedule above/below the lump sum price prepriced by the MES |
| 25 | Sch 'A' Part-XXV MISC ITEMS (TO BE QUOTED BY CONTRACTOR) Notes: (i) This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under column 5 signifies this fact only. (ii) Excavation and earth work except for the items which categorically includes for same shall be measured and paid separately under SCH A PART-XXIII (SITE CLEARANCE, SITE DEVELOPMENT AND EARTH WORK schedule). |
| 26 | INTERNAL ELECTRIFICATIONS&L Finolex's RG6 cable for TV point complete all as specified and directed |
| 27 | S&F of TV socket 1 module 230 volts AC complete all as specified and directed. |
| 28 | S&F blanking plates 1 module complete all as specified and directed. |
| 29 | S&F Sheet metal enclosure distribution board VTPN,6 way, 415 volt, double door powder coated, protection class IP-54, isolated neutral bar, mechanical impact strength IK 09 suitable for mounting MCB & /MCCB DBs confirrming to IS-13032, IS-8632,BS5484 with min 200 Amp raiting copper bus bar and grouting, fixing on wall with nut bolts wasshers proper with pcc works complete all as specified and directed |
| 30 | S & F for Highly efficient LED Bulbs, 9 watts complete all as specified and directed. |
| 31 | S&F Sheet metal enclosure distribution board VTPN,4 way, 415 volt, double door powder coated, protection class IP-54, isolated neutral bar, mechanical impact strength IK 09 suitable for mounting MCB & /MCCB DBs confirrming to IS-13032, IS-8632,BS5484 with min 200 Amp raiting copper bus bar and grouting, fixing on wall with nut bolts wasshers proper with pcc works complete all as specified and directed |
| 32 | SEWAGE DISPOSAL: M&L for RCC Septic tank for 50 user designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls , Base Slab , Baffle walls and Roof Slab including beams etc with Vent shaft , manhole openings with cover connection etc., complete with effective depth of 1.0 meter and overall avg depth of 1.93 meter for complete all as specified and directed (TD NO- CELZ TD/750 Sheet No 1/2 & 2/2) |
| 33 | M&L for Soakage wells 50 user 1.8 M dia X 3.0 M effective depth excavation, in any type of soil, foundation in PCC 1:4:8, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and directed ( TD NO- CEJZ/2004/TD/S-35 sheet No 1/1) |
| 34 | M&L for Septic tank for 25 user On site designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation Brick work to wall, Vent shaft, connection etc.,below foundation, RCC M-25 Design Mix in Roof Slab with Vent shaft , manhole openings with cover connection etc., complete for complete all as specified and directed ( TD NO- CEJZ/2002/TD/S-2 sheet No 1/1) |
| 35 | M&L for Soakage wells 25 user 1.2 M dia X 3.00 M effective depth excavation, in any type of soil, foundation in PCC 1:4:8, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size complete all as specified and directed ( TD NO- CEJZ/2004/TD/S-35 sheet No 1/1) |
| 36 | HIGH SECURITY WALL,COMPOUND WALL&GATE:M & L for Precast boundary wall with M-30 grade concrete 1.8 mtr height with post size 150x150x2400 mm ,panel size 2100x300x50 mm, reinforced wirh 3 mm high tensile steel, including M-10 garde concrete for foundation size 450x450x600 mm complete all as specified and directed. |
| 37 | M & L for erecting of 450 mm dia punched tape concertina coil / Razor wire concertina coil having 50 Nos spiral turns, (weight shall not be less than 9.0 Kg) and one coil (i.e 50 spiral shall not be stretched more than 6.0m), tied with GI staples and GI clips to retain in horizontal position & including necessary bolting or tied to GI birbed wire or angle iron etc., and fixed in angle iron brackets on compound wall with and including using necessary scaffolding along the length of wall complete all as specified and directed. |
| 38 | RAIN WATER HARVESTING:Construction of underground Rain water Harvesting Pit complete all as specified and directed. |
| 39 | M&L for vertical bore hole by rotary cum through direct hammering(DTH) technique in any type of strata consisting of 200mm dia drill bit from GL upto a depth as directed and getting out and disposal of spoil to a distance n.exc 250m complete all as specified and directed. |
| 40 | S&F PVC pipes 160mm bore of pressure rating 10 kgf/Sqm class 5 incl socket etc including lowering complete all as specified and directed. |
| 41 | S&F slotted PVC pipes 160mm bore of pressure rating 10 kgf/Sqm class 5 incl socket etc including lowering complete all as specified and directed. |
| 42 | EXTERNAL WATER SUPPLY:M&L Cutting of Exisiting 100/150 mm Dia DI for Connecting of New pipe including all nessary item complete all as specified |
| 43 | M&L for construction of brick / stone masonry valve pit / chamber of 600 x600 x 900 mm sizes (internal Dimensions) and all as shown in drawing No TD-573, including necessary excavation and earth work, PCC, plaster in CM 1:6 on inside and outside (above ground), angle iron frame 40 x 40 x 6 mm frame work, hold fast, MS sheet cover 3 mm thick, duly painted with one coat of bituminous paint of approved quality, handle and locking arrangements complete, incl provn of 40 mm Godrej (freedom) lock, all as specified and directed. |
| 44 | EXTERNAL ELECTRIFICATION:S&F abricating LT panel outdoor type, dust and vermin proof totally enclosed , with sloping canopy fabricated out of steel sections, the door opening shall not be less than 150 degree. The construction of panel board shall be dust, vermin proof, IP 54 standard double shutter gears front and rear frame work and 3.15 mm thick MS sheet duly painted with powder coated over two coats of redoxide primer and made of 40 x 40 x 6 mm thick angle iron frame all as specfified suitable for 415 Volts, 50 Hz 3 phase and nuetral system and shall be completed with 600 amps capacity copper bus bar with bus bar chamber,internal wiring with suitable size of PVC insulated copper cable copper lugs comprising of following accessories( LTP)Incoming:(a)MCCB 4 pole 400 A, 50KA - 1 incoming(b) Indicating lamp 3 Nos(c) LED Multifunctional meter -01 NosOutgoing:(a) MCCB 4 pole 320 A, 50 KA -1 No (For Main Building)(b) MCCB 4 pole 100 Amps 36 KA - 02 Nos (01 for Fire pump house & 01 spare)(c) MCCB 4 pole 25 Amps 16 KA - 01 Nos (Single OR)(d) SPN MCB 32 Amps 6 KA- 03(Garden Light & JCO Block & Garage)(e) Auto timer switch |
| 45 | Supply & lay Rubber mat of 1 meter x 2 meter x 10 mm complete all as specified directed. |
| 46 | Supply and fixing HT cable/route indicator cast iron of suitable size along HT cable trench including planting in ground with PCC complete all as directed. |
| 47 | Supply and fixing LT cable/route indicator cast iron of suitable size along LT cable trench including planting in ground with PCC complete all as directed. |
| 48 | S&F garden light 8 Watt New generation, energy saving, environmental friendly, long life aesthetically designed aluminium landscape luminaire for diffused lighting with high power LED as light source complete all as specified directed. |
| 49 | SUMMER APPLIANCESSupply and fix desert cooler GI body having base water tank of 20 SWG and top body 22 SWG of size 1000x800x800mm .The base tank have capacity of 60 ltr water fitted with float valve and incl three speed copper wound heavy duty electric motor single phase 240 volts suitable for 4000 CFM with heavy duty submersible water pump complete fitted with indicator three phase selector switch ,pump control by seprate 5 Amp switch with cord flexible 2 mtr long fitted with top plug and duly painted as specified and directed by Engineer-in-charge. |
| 50 | Supply, installation and commissioning of refrigerators, electric driven, 230 Volts, (single phase), 50 HZ, having nominal storage capacity 180 ltrs direct cool, Single door, 5 Star BEE rating, colour as approved by GE complete all as specified and directed. |
| 51 | Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 1 KVA complete all as specified and directed |
| 52 | SPLIT AIR CONDITIONING:Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA complete all as specified and directed |
| 53 | Supply and fix modular power unit of 20 Amps 240 Volts including metal flux box & cutting chasing in wall & making good surface all as specified and directed by Engineer-in-charge. |
| 54 | Supply and fix suction lines/discharge lines copper pipes of suitable size as necessary at site complete all as specified and directed |
| 55 | DG SET:Supply, installation, testing and commissioning of trolley mounted mobile diesel driven silent generating set to give an out put of 250 KVA /200 KW at 415 Volts, AC supply, 50 HZ, 3 phase, 4 wire directly coupled to diesel engine, liquid cooled, mounted on 4 wheel trolley with common base plate complete with fuel tank of adequate capacity, vibration damper, other accessories, acoustic enclosure, alternator etc complete all as specified and as directed . The DG set shall offer best fuel economy, best comprehensive warranty terms on entire package including rubber components and lowest maintenance cost to give most economical power solution. The DG set shall offer lowest noise levels in its range and shall be CPCB certified for emissions and noise compliance to give environment friendly power solution. The generator set shall meet the stringent exhaust emission tests as per latest MoEF norms without sacrificing fuel efficiency at normal operating loads |
| 56 | Item 55.00 Contd/…A. Engine Specifications:-Developing a net minimum power as per MoEF certified - 303.4 HP ( ± 5 % ), suitably matched with alternator to give a net directed output as specified. The engine shall be capable of delivering the required out put at 1500 RPM, as per BIS under NTP condition with provision of 10% overloading for one hours in every 12 hours of operation. The diesel engine shall also conform to IS : 10000/IS 1460/IS 13018/ISO : 3046/BS : 649 / BS : 5514 as amended upto date. The scope of supply includes :-(i) Electrical starter motor 12V DC(ii) Battery charging alternator(iii) MICO fuel system (iv) Dual spin-on fuel filter(v) Turbocharger(vi) Residential silencer(vii) Dry type air cleaner(viii) Shut-off coil with safeties for LLOP/HWT(ix) Dynamically balanced fly-wheel and flywheel housing(x) First fill of lube oil and coolant |
| 57 | Item 55.01 Contd/...The technical data shall be all as specified below comprising of the following:-(i) BHP – suitable for giving a min power of 303.4 HP as per ISO 8528-Part-1/certified MoEF at the load terminals of alternator at 1500 rpm.(ii) All moving parts of the engine shall be mechanically guarded in such a manner that a human finger cannot touch any moving Part.(iii) Cooling – Liquid Cooled.(iv) Aspiration – Turbo Charged air cooled.(v) No. of Cylinders – 06.(vi) No. of cycles – 4 stroke.(vii) RPM – 1500.(viii) Fuel - HSD(ix) Fuel injection : Engine should have suitable fuel injection system in order to achieve low fuel consumption.(x) Starting System - 12V Electrical(xi) Lube oil specification – CI4 15W40.(xii) Governing specification – Electronic governor of class A1, as per ISO 3046/BS 5514 to maintain engine speed at all conditions of load.(xiii) Type of driven – Direct SAE flange coupling.(xiv) Battery capacity/rating – 12V DC, 180 AH.(xv) Any other item not included/specified, but is a standard design of the manufacturer. |
| 58 | Item 55.02 Contd/...ALTERNATOR :- The diesel engine mentioned herein before shall be coupled through flexible coupling to an indigenous synchronous alternator mounted on a strong mild steel fabricated common base frame, with AVM pads suitable for continuous operation at 1500 RPM, 415VAC, 0.8 pf (lag) suitable for 50 HZ, 3 phase, 4 wire system, brushless type, screen protected revolving field, self excited self regulated through an AVR all as conforming to IS 4722, BS 5000 & IEC:60034 as amended upto date. The alternator has the following features :-(i) Voltage Regulation - ± 1.0% (max) in static conditions.(ii) Voltage variation - ± 5.0 %(iii) Class of Insulation - H Class(iv) Degree of protection - IP 23(v) Overload duration/capacity - 10% for one hour in every 12 hours of continuous use(vi) Frequency variation - As defined by the Engine Governor (± 1.0 %)(vii) Type of AVR( Automatic Voltage Regulator) - Electronic(viii) Stator Winding - Double layer lap(viii) Rotor - Dynamically balanced |
| 59 | Item 55.03 Contd/...Contrl Panel with microprocessor based monitoring and control system :- The control panel should be manufactured with 14/16 gauge CRCA sheet with powder coated for weather proof and long lasting finishThe control panel consisting Multifunction digital meter displaying the following parameters :- (i) Voltage (Phase to Neutral & Phase to Phase).(ii) Current.(iii) Frequency.(iv) Coolant temperature.(v) Engine Oil pressure.(vi) Power Factor.(vii) KWHR.(viii) DG Set running Hrs.(ix) Engine RPM.(x) Battery voltage.(xi) MCCB of suitable rating with overload and short circuit protections.(xii) Push button-switch or ON/OFF Switch for ON and OFF operation.(xiii) Aluminium bus bar with suitable capacity with in and outgoing terminals.(xiv) LED Indicating Lamps set for 'Load On' and 'Set Running'.(xv)Insrument fuses duly wired and ferruled. |
| 60 | Item 55.04 Contd/...System operation : Manual Mode.(i) In a manual mode, it shall be feasible to start-up the generator set by the operator on pressing the start push button(ii) Three attempts starting facility shall be operative for the start-up function(ii) Alternator circuit breakers closing and trip operations shall also be through operator only by pressing the appropriate button on the panel and closure shall be feasible only after alternator has built up full voltage. If the load is already on ‘mains’, pressure on ‘close’ button shall be ineffective.Engine shut down and alternator protection equipments : Following shut down and protection system with audio visual annunciation shall be integrated in the controller panel.1. For Engine :- (i) Low lubricating oil pressure.(ii) High/low coolant temperature.(iii) Engine over/under speed (iv) Low Fuel level.(v) High canopy temperatureFor Alternator :- (i) Over load) Short circuit) Earth fault) Over voltage) Over/Under frequency. |
| 61 | Item 55.05 Contd/...Battery/Electrical System -(i) Batteries of 12 VDC, 180 AH with copper cable of suitable sizes should be supplied with Genset are generally dry and uncharged. First charging of uncharged batteries is very important and should be done from authorized battery charging centre. Initial charging should be done for 72 - 80 hours.(ii) Batteries should be placed on stands and relatively at cool place.FUEL TANK :- One No of sheet metal steel tank fabricated from 2mm thick MS sheet of suitable capacity to contain diesel for 8.0 Hrs running at full load including the following :-(i) Level indicator duly calibrated for indicating the quantity of diesel in the tank.(ii) Drain plug with 2 meter pipe for drain out.(iii) Fuel strainer.(iv) Pipe for fuel supply to engine.(v) Fuel pump manually operated for filling tank rotary type. |
| 62 | Item 55.06 Contd/...Acoustic enclosure: The acoustic enclosure shall be fabricated out of the CRCA sheet of thickness not less than 1.6 mm on the outside cover with inside cover having not less than 0.6 mm thick perforated powder coated CRCA sheet conforming to MoEF/CPCB norms suitable for out door installation in exposed to weather condition and to limit over all noise level to 75 dBA at a distance of 1 Mtr at 75 % load or as specified by MoEF(Ministry of Environment & Forest). The enclosure has the following features:-(a) The construction should be such that it prevents entry of rain water splashing into the enclosure and allows free & quick flow of rain water to the ground in the event of heavy rain.(b) The hinged doors shall be made form not less than 16 SWG (1.6 mm) thick CRCA sheet and will be made air tight with neoprene rubber gasket and heavy duty locks(c) Designed to have optimum serviceability (d) Air inlet louvers specially designed to operate at rated load made on special purpose CNC machines for consistency in quality and workmanship(e) Powder coated for long lasting service life and superior finish (f) Acoustic enclosures are supplied with built in Anti Vibration Mountings (AVM). As such Genset can be installed directly on the leveled surface(g) USE of special hardware for longer life(h) Insulation material meets exacting IS 8183 specifications for better sound attenuation. |
| 63 | Item 55.07 Contd/...(j) Flush styling - no projection (k) Fluid drains for lube oil & fuel.(l) The canopy should be as compact as possible with good aesthetic look.(m) Fuel tank suitable for 8 hours of operation(n) The enclosure is of modular construction with the provision to assemble and dismantle easily at site.(o) The sheet metal components are hot dip seven tank pretreated before powder coating.(p) The enclosure is powder coated (inside as well outside) with a special pure polyester based powder. All nut and bolts/external hardware is made from stainless steel.(q) There is provision for filling fuel from outside the enclosure with locking arrangement.(r) External drain plugs are provided for draining Lub. Oil and diesel.(s) The doors are gasketed with high quality EPDN gaskets to prevent leakage of sound.(t) The door handles are locking type.(u) Sound proofing of the enclosure is done with high quality rock wool/mineral wool confirming to IS 8183. The rock wool is further covered with fiber glass tissue and perforated sheet.(v) A special residential silencer is provided within the enclosure to reduce exhaust noise |
| 64 | Item 55.08 Contd/...(w) Specially designed attenuators are provided to control sound at air entry and exit points.(x) Adequate ventilation is provided to meet total air requirement. If required, a blower is provided to meet total air requirement.(y) Temperature of enclosure does not exceed beyond 5 degree centigrade of ambient temperature.(z) The enclosure is provided with high enclosure temperature safety trip.(aa) Provision of emergency shut down from outside the enclosure.(ab) An arrangement for illuminating the enclosure from inside.(ac) The acoustic lining should be made up of high quality insulation material i.e. glass/mineral wool of minimum 50mm thickness and 75 Kg/cubic metre to 100 Kg/ cubic meter for sound absorption as per standard design of manufacturer’s to reduce the sound level as per CPCB norms. The insulation material shall be covered with fine glass fiber cloth and should be supported by perforated M.S. Sheet duly powder coated.Exhaust System : DG Set shall be fitted with retrofit Emission Control Device (RECD) to control exhaust emission limits as per latest guideline issued by CPCB And meet requirements of environmental (protection) Rule 1986. |
| 65 | Item 55.09 Contd/...COUPLING & MOUNTING ARRANGEMENT : The engine and alternator are directly coupled by a SAE flange and mounted through AVM pads on a heavy duty steel base frame. The arrangement ensures that there is no chance of misalignment of the DG Set and vibrations of the DG Set are not transmitted to the base frame & to the enclosure. The fuel tank is mounted in the base of the enclosure. The batteries are kept in a separate tray inside the enclosure.COMMISSIONING: The DG Set shall be successfully commissioned by the contractor at the site as directed.TROLLEY SPECIFICATION : Fabrication of 04 wheel ( double axle ) trolley for mounting arrangement of DG sets with Fe 410 grade steel to hold the complete DG set of minimum platform size 4650 mm x 1700 mm x 2480 mm and designed to carry minimum 3110 Kgs weight with the following Specification complete in all respect and as directed:-(i) MS Chassis - MC 200X75mm.(ii) MS Axle two Nos - 65X65mm.(iii) MS Chequered plate top - 8mm thick supported with suitable size angle and beams welded to Chassis and base plate.(iv) Rims and wheels - 4 Nos, tyer 7.5/16 inches (16 Ply)(v) Hydraulic Parking break - (vi) Towing hook of suitable size.(vii) Leaf springs suspension sets with U clamps - 04 Sets.(viii) Trolley shall be painted with two coats of synthetic enamel paint over a coat of red oxide/ Zinc chrome primer of approved colour. |
| 66 | FIRE FIGHTING SYSTEM:Providing and fixing fire hose cabinet 2100x900 mm (IFH) (Door) fabricated from 16 gauge M.S. Sheet with single or double glazed front door (with 4 mm thick glass) and locking arrangement, painted fire red with stove enamelled paint \\"FIRE HOSE\\" written on front including necessary supports complete all as specified and directed. |
| 67 | S&F 5000 Ltr rotational moulded polyethylene water storage tanks(cylindrical vertical with closed top) hoisted and fixed in position complete all as specified and directed. |
| 68 | Supplying and fixing 63 mm dia, 30 m long Reinforced Rubber lined (RRL} hose pipe with 63 mm dia male and female gun metal couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required complete all as specified and directed |
| 69 | Providing & fixing Auto Air vent for fire hydent and sprinkler, suitable for pressure not less than 15 Kg/Sq.cm.25 mm dia. complete all as specified and directed |
| 70 | Supply installation testing and commissioning of ABC type Fire Extinguisher capacity 6 kg filled with Mono Ammonium Phosphate powder 50% conforming to IS 14609, powder coated MS body stored Pressure type Discharge time 18 Sec, controllable discharge is 90%, applicable on class A,B & C and electrically started fire, A Rating-3A, Rating 21B, safety pin is of SS material, Sheet metal thickness: 1.0 mm, Helium Leak Detection Tested ISI Approved IS 15683:2006. 5 years Warranty. |
| 71 | Supply installation testing and commissioning of Carbon Dioxide (CO2) type Fire Extinguisher capacity 4.5 kg conforming to IS 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets, PESO/CCOE Approved cylinder body and confirms to IS : 7285, High grade Enamel painted externally with PO Red finish, wheel operated controllable discharge high Pressurebress valve confirming to IS : 3224 which is provided with pressure relief dischargeable and easy to service, non conductive agent for electrical use without risk to operator ,CO2 gas disappiears quickly leaving no residue applicable on class B & C and electrically started fire, B rating 21B started fire, A Rating-3A, Rating 21B, safety pin is of SS material, Sheet metal thickness: 1.0 mm, Helium Leak Detection Tested ISI Approved IS 15683:2006. 5 years Warranty. |
| 72 | Supply installation testing and commissioning of 04 Kg Clean agent Fire Extinguisher stored pressure type, complying with IS-1568, filled approved agent(HFC-236fa)EF-36) suitable for class A,B &C fire and safe for sensitive electronic equpment,seamless/welded steel cylinder with epoxy finish, working pressure 15 bar and test pressure minimum 35 bar, provided with pressure guage, squeeze-grip control valve, discharge time 10-12 seconds, effective jet range 3-4 mtr SS material, Sheet metal thickness: 1.0 mm, Helium Leak Detection Tested ISI Approved IS 15683:2006. 5 years Warranty. |
| 73 | Supply installation testing and commissioning of Carbon Dioxide (CO2) type Fire Extinguisher capacity 09 kg PRESSURE TYPE conforming to IS 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets, PESO/CCOE Approved cylinder body and confirms to IS : 7285, High grade Enamel painted externally with PO Red finish, wheel operated controllable discharge high Pressurebress valve confirming to IS : 3224 which is provided with pressure relief dischargeable and easy to service, non conductive agent for electrical use without risk to operator ,CO2 gas disappiears quickly leaving no residue applicable on class B & C and electrically started fire, B rating 21B started fire, A Rating-3A, Rating 21B, safety pin is of SS material, Sheet metal thickness: 1.0 mm, Helium Leak Detection Tested ISI Approved IS 15683:2006. 5 years Warranty. |
| 74 | Supply of Fire pump panel fully compartmentalized cubical type sheet clad floor mounted totally enclosed , extensible on both sides, switch board suitable for use on 415 Volts 3-phase, 4 wire, 50 Hz system having 35 KA fault capacity, housed with incoming and outgoing, Aluminium bus bars with current rating of 0.8 Amp/sq.mm, interconnection etc. with indication lamps, accessories etc, as required as per specification and schematic diagram as required.INCOMING:-200 Amps. MCCB (35 KA)Ammeter with CTs 400/5A class-IOne Digital Volt meter (0-500 V) with selector switch.Set phase indication lights (R, Y, B)BUS BARS:-500 Amps. TP&N aluminium bus bars (35 KA)OUTGOING:-5 Nos 63 A, MCCB (35KA).1 No 63A DP MCB(10KA).FOR LIGHTING (i) Two fully automatic Star Delta starters suitable for 22 KW Pump Motor with MN type over load relay timer push buttons and Auto/Manual selector switch.(ii) One fully automatic Star Delta starters suitable for 7.5 KW suitable for Jockey Pump motor with MN type overload relay, timer push buttons and Auto/Manual selector switch(iii) Three panel Digital type Amp. Meters, one for each motor with ASS CTS etc.(iv) Three sets of On/Off –neon indicating lam |
| 75 | Item 64.00 contd/...(v) Fully Automatic Diesel engine starting system complete with automatic battery charger, 8 window annunciator, indicating lights, transformer, rectifier , timer, voltmeter. Ammeter, selector switches, push buttons, auxiliary relay etc. compete as required as per TAC rules.(vi) All interconnecting power and control wires/cable suitable size within the panel and from panel to motors diesel engine, pressure switches, level switches, cable tray, pipes etc. including brass glands termination within fire pump house. |
| 76 | Supply, fixing, testing & commissioning, PVC insulated multi stranded copper conductor FRLS cable single core 1100 volt grade, IS-694 marked size 10 sqmm for pump connection from panel board to pumping set inclosed in GI pipe 25 mm dia medium grade embedded in floor/fixed to wall etc. Note- 25 mm medium grade pipe shall be measured & paid separately |
| 77 | Supplying, fixing, testing & commissioning double flanged flexicon rubber expansion joint 100 mm dia(suitable for system test pressure) of standard length as per specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications |
| 78 | Supplying, fixing, testing & commissioning double flanged flexicon rubber expansion joint 150 mm dia(suitable for system test pressure) of standard length as per specs including rubber gaskets, flanges, nuts, bolts and washers complete as required as per specifications |
| 79 | Supply, installing, testing and commissioning heavey duty perforated MS cable tray suitable to accommodate the cables of fire fighting pump house from LT Panel to all fire pumps/jockey pumps. The cable tray shall be MS sheet, Minimum thickness 2.00mm or as per load calculation, hot dip galvanized after fabrication (HDG, 80-120 microns zinc coating), with 50 mm side height and adequate withdh(typically 150-300mm) finalized as per actual cable quantity with 30% spare capacity). The tray shll include all bends,tee,reducers,couplers, covers(where required, splice plate,nuts & bolts, support on MS angle/channels supports at maximum 1,2-1.5mtr spacing, properly earthed, aligned, and fixed on wall/ceiling as required and directed by Engr-in-Charge. |
| 80 | FIRE ALARM:Supply,fixing, testing and commissioning detectors complying with and type certified to EN-54-29, addressable type multisensor detectors with heat and smoke Combination, LED indicator with standard ceiling base, 360 degree visible alram, operating voltage 15-32V DC (loop wired), alarm current 5-10mA , smoke sensing-optical/photoelectric, adjustable sensitivity (0.10-0.30dB/m), heat sensing fixed temperatur+ rate of rise, class A1R/A2R at operating temperature -10 degree celcius to+55 degree celcius, relative humidity 0-95% RH non-condensing and compatibility with addressable fire alarm control panel EN-54 loop system,onforming to BS-5839 Standards and duly Approved by EN54/LPCB, All as specified and directed by Engr-in-Charge |
| 81 | Supply,fixing,testing and commissioning of Analog Addressable Type Manual Call Point (MCP) (break-glass or push /button type) including back/flush mounting box for MCP having Surface or flush mounting Option fully complaint to EN54 having Rotary Decade Swicthes for Addressing from 01-99 complete as required, conforming to BS-5839 Standards and duly Approved by EN54/LPCB,All as specified and directed by Engr-in-Charge |
| 82 | Supply,fixing, testing and commissioning of fault isolator base EN-54-17 (short circuit isolators) addressable type, loop powered with termination preferably after every 10-15 devices and shall be able to isolate electrical short circuit or over current fault in the wiring etc.operating voltage 15-32 V DC as required complete all as specified and directed |
| 83 | Supply,fixing, testing and commissioning of remote response indicator fault isolator base EN-54-17 (short circuit isolators) addressable type, loop powered with termination preferably after every 10-15 devices and shall be able to isolate electrical short circuit or over current fault in the wiring etc.operating voltage 15-32 V DC as required,all as specified and directed by Engr-in-Charge |
| 84 | Supply,fixing, testing and commissioning of addressable 2 Loop Micro processor based complaint with BS EN54-2(control & indicating equipment ) and EN54-4(power supply equipment) 1 wire fault tolerant loop, required loop network (each loop accessing 99 detector & 99 module & up to 200 modules) fire alarm/detection control panel.(FACP) The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFF respective control module whenever any alarm is triggered. The panel shall have rectifier, Loop cards, 80 character LCD display unit to indicate Fire/Fault relay Signal, RS-485 communication port with addresses.The Panel Shall be Sheet Steel Painted, sealed to IP30. The panel have provision to integrate with PA System . The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF dry batteries capable of running for a minimum of 48 hours with battery charger complete as required. The panel shall include the space for above batteries and complete with accessories, wiring, terminal blocks, gland plates and earthing etc complete, conforming to BS5839 Standards and duly Approved by EN54/LPCB and all as specified and directed by Engr-in-Charge. |
| 85 | Supply,fixing, testing and commissioning of active repeater Panel addressable Micro processor based compatible with the main addressable fire alarm control panel. The repeater shall repeat all status indicator and LCD display information including fire, fault, supervisory, disable, test and device address/location. The repeater panel shall include LCD display (4x40 Characters or graphical), LED indicators (fire, fault, power, silence, disable test), including soft touch control keys such as acknowledge, silence buzzer, silence alarm, reset, evacuate. RS-485 CANBUS communication interface , built in buzzer.The Panel Shall be Sheet Steel Painted powder coated , sealed to IP30. compatible with smoke and heat detectors multisensors , MCP and modules. The inernal power supply 2x 12 V 24AH SMF dry batteries EN54-2/EN54-4 compliant complete with connector, terminal, wiring, commissioning and programming complete, duly Approved by EN54/LPCB and all as specified and directed by Engr-in-Charge |
| 86 | Supply, install,testing and commissioning of Addressable central modular hooter for the fire detection and alarm system. The modules shall provide audiable evacuation signaling in accordance with EN54 standard and shall be fully compatible with the existing addressable fire alarm control panel (FACP). The hooter shall deliver 90-105dB(A) at 01 meter, offer selectable tones and adjustable volume, provide LED indication for status and fault, support synchronized operation across the loop. complete as required and directed by Engr -in-Charge. |
| 87 | Supply, install,testing and commissioning of Electric siren system, AC, 415 V-3 phase , 50 HZ, protection waterproof/dustproof (IP65), powder coated MS sheet of DB range 65 to 120 measured at 1.5 mtrs with sound output variation of + 5 db for range 2 Kms installed at roof of Bldg including civil work & suitable canopy & neccessary foundation. and all as specified and directed by Engr-in-Charge |
| 88 | Supplying and drawing flame retardent low smoke, FRLS cables of 2 core 1.5 sqmm ATC cable unaurmored flexible/stranded bare copper conductor PVC insulated, multistranded twisted pair shielded cable 1100 volts grade drawn through in the surface / concealed conduit as required including cutting chasing for concelead Wiring & finished to good surface.and all as specified and directed by Engr-in-Charge |
| 89 | Supply,fixing and testing OUTPUT CONTROL MODULE addressable and fully compatible with the specified intelligent fire alarm control panel, providing supervised control of external devices such as fire shutters, dampers,relays,fans and third party equpment The module shall support both normally open (NO) and normaly closed (NC) contacts, with a rated output not less than 24 Volt DC, and shall include built -in short-circuit protection and line monitorig for open/short condition, module shall have unique software -selectable address, LED indicator for status and programming, and provision for removable, clearly labeled terminal blocks. The module shall be housed in a fire retardan enclosure or be suitable for mounting inside an approved juction box and shall comply with EN-54-18 (input/Output device) or equivalent cerfication including all accessories for mounting and commissioning and all as specified and directed by Engr-in-Charge |
| 90 | Supply,fixing and testing INPUT MONITOR MODULE, intelligent, addressable and fully compatible with the specified intelligent fire alarm control panel (FACP), designed to monitor the status of external devices such as beam detectors, aspirating detectors, The module shall support both normally open (NO) and normaly closed (NC) contacts, The module shall provide supervised monitoring of input circuits, including end-of- line (EOL) resistance to detect open , short and normal conditions and shall have a unique address set electronically or via addressing tool. It shall include LED status indicators for polling and acivation, removable terminal blocks for easy wiring, and built -in protection against short circuits on the loop. The module shall be housed in a fire retardan enclosure or be suitable for mounting inside an approved juction box and shall comply with EN-54-18 (input/Output device) or equivalent cerfication including all accessories for mounting and commissioning and all as specified and directed by Engr-in-Charge |
| 91 | Supply and fixing MS conduit 20mm dia, 16 SWG stove enamelled both internally and externally, steel conduit alongwith accessories in concealed / surface all as specified and directed. |
| 92 | Supply and fixing MS conduit 25 mm dia, 16 SWG stove enamelled both internally and externally, steel conduit alongwith accessories in concealed / surface all as specified and directed. |
| 93 | AIR CURTAIN:Supply and fix air curtain sensor for item mentioned in respective schedule complete all as specified & directed. |
| 94 | SOLAR STREET LIGHT:Supply & fix“Lithium based Energy Efficient Integrated Solar Street light 40Watt” in Single FRP body with polyurethane coating ( Camouflage Color ) encases Solar PV Panel 80Wp Mono crystalline , Lithium Battery 11.1/12.8V, 39.6AH with inbuilt BMS, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with PIR Motion Sensor ), Dusk to Down Operation, suitable for pole height 8 - 9 mtr,, Working temperature: (-) 40C to (+)55C, Weight: 18-20 kg, with adjustable MS clamp suitable for pole/wall mounting. Protections: Short Circuit, overload, Reverse polarity and battery protections. With Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS, IP66 and IK08 Compliant all as specified and directed. |
| 95 | Supply & fix 80mm Medium Class Galvanised pole of 7 mtr height and base plate 200x20012mm mounting accessories with 4 nos of M20x600mm long ‘J’ type foundation bolt along with template sand suitable arrangement to mount solar light as directed and including foundation and errection as per manufacturer drawing complete all as specified by Engr-In-Charge |
| 96 | TELEPHONE & INTERCOM:Supply and install, testing wall termination Telephone socket RJ-11 all as specified and directed. |
| 97 | VRF Outdoor Units (Modular Type)Design, Supply, installation, testing and commissioning of factory assembled, air cooled, 100% inverter driven single/multiple compressor based, Non CFC refrigrent based variable refrigerant flow (VRF) modular type Air conditioning system, suitable to operate at 400V +/- 10%, 50 Hz electric supply, suitable for multi indoor units with external condensing unit, copper refrigent pipe, full charge of refrigerant with additional topup if required, drain pipe, transmission cum control wiring cordless remote controls, MS slotted angle irons, provision of winter heating arrangement (Heat recovery Ventilation System) ,etc , suitable for Mathura condition without tripping including all accessories as specified below for maintaining inside temperature (22±2) Degree Celsius considering weather condition of Jaipur outdoor units suitable for operation at ambient temperature up to 46°C. The unit shall be modular in design with minimum COP of 3.5 at full load. Refrigerant shall be R410A/R32. Compressor shall be hermetically sealed scroll type with inverter control. The unit shall have inbuilt microprocessor with auto restart, oil balancing, low noise operation (<65 dB), and all safety protections including HP/LP switch, overload protection, phase failure, reverse phase protection. |
| 98 | Item 86.00 Contd/...The unit casing shall be powder coated, weatherproof (IPX4 minimum). The unit shall be complete with factory wiring, refrigerant charge, and compatible for integration with BMS.Make approval shall be obtained prior to supply.Floor mounted Outdoor top discharging type condensing units equipped with Micro-processor control panel, sub cooler, accumulator, hermetically sealed highly efficient 100% inverter type scroll compressor, low noise condenser fan with DC motor, auto check function for connection error, auto address setting, vibration isolator and all the necessary accessories for proper functioning of the units. critical zones: OT, X-ray, Recovery requires ducted air distribution20 HP ODU - 3 Nos |
| 99 | VRF Outdoor Units (Modular Type):Design, Supply, installation, testing and commissioning of factory assembled, air cooled, 100% inverter driven single/multiple compressor based, Non CFC refrigrent based variable refrigerant flow (VRF) modular type Air conditioning system, suitable to operate at 400V +/- 10%, 50 Hz electric supply, suitable for multi indoor units with external condensing unit, copper refrigent pipe, full charge of refrigerant with additional topup if required, drain pipe, transmission cum control wiring cordless remote controls, MS slotted angle irons, provision of winter heating arrangement (Heat recovery Ventilation System) ,etc , suitable for Mathura condition without tripping including all accessories as specified below for maintaining inside temperature (22±2) Degree Celsius considering weather condition of Jaipur outdoor units suitable for operation at ambient temperature up to 46°C. The unit shall be modular in design with minimum COP of 3.5 at full load. Refrigerant shall be R410A/R32. Compressor shall be hermetically sealed scroll type with inverter control. The unit shall have inbuilt microprocessor with auto restart, oil balancing, low noise operation (<65 dB), and all safety protections including HP/LP switch, overload protection, phase failure, reverse phase protection. The unit casing shall be powder coated, weatherproof (IPX4 minimum). The unit shall be complete with factory wiring, refrigerant charge, and compatible for integration with BMS. Make approval shall be obtained prior to supply. |
| 100 | Item 87.00 Contd/..Floor mounted Outdoor top discharging type condensing units equipped with Micro-processor control panel, sub cooler, accumulator, hermetically sealed highly efficient 100% inverter type scroll compressor, low noise condenser fan with DC motor, auto check function for connection error, auto address setting, vibration isolator and all the necessary accessories for proper functioning of the units. critical zones: OT, X-ray, Recovery requires ducted air distribution8 HP ODU - 1 Nos |
| 101 | VRF Indoor Units (High Static Ductable)Design, Supply, installation, testing and commissioning of ceiling concealed high static ductable indoor units suitable for VRF system. Units shall have adjustable ESP up to 100 Pa. Cooling coil shall be made of copper tubes with aluminium fins, with hydrophilic coating. Unit shall be provided with washable synthetic filters, insulated drain pan, and low noise operation (<45 dB). The unit shall be suitable for false ceiling mounting and connected with supply and return air ducting. Each unit shall be complete with electronic expansion valve, fan motor, and wired controller. The unit shall be factory tested and fully compatible with VRF outdoor system.Indoor unit ductable type capacity 2 TR - 12 Nos |
| 102 | VRF Indoor Units (High Static Ductable)Design, Supply, installation, testing and commissioning of ceiling concealed high static ductable indoor units suitable for VRF system. Units shall have adjustable ESP up to 100 Pa. Cooling coil shall be made of copper tubes with aluminium fins, with hydrophilic coating. Unit shall be provided with washable synthetic filters, insulated drain pan, and low noise operation (<45 dB). The unit shall be suitable for false ceiling mounting and connected with supply and return air ducting. Each unit shall be complete with electronic expansion valve, fan motor, and wired controller. The unit shall be factory tested and fully compatible with VRF outdoor system.Indoor unit ductable type capacity 3 TR - 11 Nos |
| 103 | Refrigerant Copper Piping with InsulationDesign, Supply, installation, testing and commissioning of copper refrigerant piping for interconnection between each set of indoor units and outdoor units as per design alongwith Y joint set fittings and any other item to make system complete. Refrigent piping using hard drawn copper pipes conforming to ASTM B280. The piping shall be carried out with proper supports at regular intervals and brazed using silver alloy. Nitrogen purging shall be done during brazing to avoid oxidation. Complete system shall be pressure tested with dry nitrogen and vacuumed up to 500 microns before charging refrigerant. Pipes shall be insulated with closed cell elastomeric nitrile rubber insulation of density minimum 40 kg/m3 and thickness 9mm to 19mm depending on pipe size. All joints shall be sealed with adhesive and vapor barrier maintained. Note : Rate shall include all refnet joints, headers, reducers, oil traps, supports and accessories—no extra payment shall be made. Route of pipe to be approved by GE. |
| 104 | Drain Piping SystemDesign, Supply and installation of UPVC drain piping of 6kg/cm2 rating of size 25mm with 9mm thick nitrile foam rubber insulation from indoor units including necessary fittings such as bends, tees, reducers and traps. The piping shall be laid with proper slope (minimum 1:100) to ensure gravity flow. All drain pipes shall be insulated to prevent condensation. The drain shall be connected to nearest floor trap or drain point as directed by Engineer-in-Charge. Testing shall be carried out to ensure no leakage and proper flow. Please Enable Macros to View BoQ information |
| 105 | Drain Piping SystemDesign, Supply and installation of UPVC drain piping of 6kg/cm2 rating of size 25mm with 9mm thick nitrile foam rubber insulation from indoor units including necessary fittings such as bends, tees, reducers and traps. The piping shall be laid with proper slope (minimum 1:100) to ensure gravity flow. All drain pipes shall be insulated to prevent condensation. The drain shall be connected to nearest floor trap or drain point as directed by Engineer-in-Charge. Testing shall be carried out to ensure no leakage and proper flow. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedAug 11, 2026
17:00 IST