Water Resources and Irrigation Government Departments Closing in 5 days TDR #56352761

Tender For Relocation & Reconstruction Of Various Lift Water Schemes (Lwss Sihor Balla) And Lift Irrigation Schemes (Lis Chowki Kior And Lis Bulli) On The Right Bank Of River Beas Affected Due To Submergence In The Poundage Of Dhoulasidh In Tehsil Ja

Issued by Government Departments · Kangra, Himachal Pradesh
Tender Value
2.47 Crore
Estimated cost
Bid Submission
17 Jul 2026
5 days left
EMD
3.22 Lakhs
Bank guarantee accepted
Document Fee
7000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Kangra → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Relocation & Reconstruction Of Various Lift Water Schemes (Lwss Sihor Balla) And Lift Irrigation Schemes (Lis Chowki Kior And Lis Bulli) On The Right Bank Of River Beas Affected Due To Submergence In The Poundage Of Dhoulasidh In Tehsil Jawalamukhi Distt. Kangra (Hp)

BOQ

Name of Work:- Relocation & Reconstruction of various Lift water schemes (LWSS Sihor Balla) and Lift Irrigation schemes (LIS Chowki Kior and LIS Bulli) on the Right bank of River Beas affected due to Submergence in the Poundage of Dhoulasidh in Tehsil Jawalamukhi Distt. Kangra (HP)
Sl. No. Item Description
1Excavation in foundation, trenches upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing and pumping out water, blasting soft/ hard rock or chieselling soft/hard rock where blasting is prohibited in all lifts including trimming and dressing of sides, leveling of beds to correct grade i/c shoring/strutting, planking, timbering & dewatering wherever required, stacking the useable & unuseable material/soil separately & after laying jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposoited layer by ramming & watering & then disposing of all surplus excavated soil /unusable material as directed with in all leads & lifts including restoration of metaled unmetalled surfaces & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of Engineer-in-charge. (For Intake Structure)
2Excavation in foundation, trenches (for pipes & pits) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing and pumping out water, blasting soft/ hard rock or chieselling soft/hard rock where blasting is prohibited in all lifts including trimming and dressing of sides, leveling of beds to correct grade i/c shoring/strutting planking, timbering & dewatering wherever required, stacking the useable & unuseable material/soil separately & after laying jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposoited layer by ramming & watering & then disposing of all surplus excavated soil /unusable material as directed with in all leads & lifts including restoration of metaled, unmetalled surfaces & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of Engineer-in-charge. (For Rising Main)
3Providing and laying cement concrete 1:3:6 (1: cement :3 sand :6 graded crushed stone agg. of 40mm. Nominal size) and curing complete excluding the cost of form work in foundation and plinth with in all leads and lifts as per direction of the Engineer-in-charge.
4Providing and laying cement concrete 1:1.5:3 (1: cement:1.5 sand :3 graded crushed stone agg. of 20mm. Nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :-
5Foundation footing bases of column and the like mass concrete with in all leads and lifts as per direction of the Engineer-in-charge.
6Wall (any thickness but not less than 0.10 mtr. Thickness) including attached pilasters buttersses, plinth and string courses etc, from top of foundation upto floor two level complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
7Suspended floor roofs, landing and shelves and their support balconies, beams, girders, bressumers and contilever upto floor two level with in all leads & lifts as per direction & entire satisfaction of the Engineer in-charge.
8Providing and laying Cement concrete flooring 1:2:4 (1:cement :2 sand:4 graded crushed stone aggregate of 20mm nominal size) and curing complete laid in one layer finished with a floating coat of neat cement 40mm thick with in all leads and lifts as per the direction and satisfaction of the Engineer-in-charge.
9Providing mild steel/tor steel reinforcement for RCC work including bending, binding and placing in position complete upto floor two level with in all leads & lifts as per direction & entire satisfaction of the Engineer - in-charge.
10Providing form work with steel plates 3.15mm. thick welded with angle iron in frame 30x30x5mm. So as to give a fair finish including centering shuttering strutting and propping etc, with wooden battens and ballies height of propping and centering below supporting floor to ceiling not exceeding 4 mtrs. and removal of the same for insitu reinforced concrete and plain concrete work in:-
11Foundation footing bases of column and the like mass concrete complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
12Column, pillars, posts & struts upto floor two level with in all leads and lifts as per direction of the Engineer-in-charge.
13Beams, cantilever, girders and lintels sides and soffits of beams, beam haunchings, cantilevers, bressumers and lintels not exceeding 1 mtr. In depth in all heights from floor with in all leads & lifts as per direction & entire satisfaction of the Engineer - in charge.
14Flat surfaces such as soffits of suspended floor, roofs landing and the like floors etc.upto 200mm in thickness.upto all thickness including all with in all leads & lifts as per direction & entire satisfaction of the Engineer-in-charge.
15Vertical surfaces such as walls (any thickness) partitions and the like including attached pilasters buttersses, plinth and string courses etc, and the like with in all leads and lift as per direction & entire satisfaction of the Engineer-in-charges.
16Brick work using common burnt clay building bricks (2nd. class) in super structure above plinth level upto floor two level in cement mortar 1:6 (1cement:6 sand) with in all leads & lifts as per direction & entire satisfaction of the Engineer - in-charge.
1715mm thick cement plaster in single coat on rough side of bricks/stone masonary for interior plastering upto floor two level including arrises, internal rounded angles chamfers and/or rounded angles not exceeding 80mm in girth and finished even and smooth in C.M 1:6 (One cement: six sand) with in all leads & lifts as per direction & entire satisfaction of the Engineer in-charge.
18Providing & fixing cast iron cover for frame of internal size 560 mm dia with frame (Medium duty) with in all leads and lifts as per direction of the Engineer-in-Charge. (weight of cover and frame not less than 116 kg.)
19Providing & fixing steel bar cage for fasting of pump with piers of 300 mm dia of mesh size 50 mm x 50 mm, 16 mm square steel bars with in all leads & lifts as per direction & entire satisfaction of the Engineer - in- charge.
20Steel work welded in built up section trusses and framed work i/c cutting hoisting fixing in position and applying a priming coat of red lead paint in gratings framed guards bars, ladders railing, brackets and similar work complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
21Providing & fixing ISMB 200 girder AS/ST DES including fixing complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
22Providing and fixing 5.00 Ton Chain Pully/ gantry of approved ISI make electrically operated alongwith all allied accessories complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
23Providing and laying cement concrete 1:2:4 (1: cement :2 sand :4 graded crushed stone agg. of 20mm. Nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :-
24Wall (any thickness but not less than 0.10 mtr. Thickness) including attached pilasters buttersses, plinth and string courses etc, from top of foundation upto floor two level complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
25Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS: 13592 Type A, including jointing with seal ring conforming to IS: 5382, leaving 10 mm gap for thermal expansion (1) Single sockted pipes 110 mm dia complete in all respect with in all leads and lift as per direction & satisfaction of the Engineer-in-charges.
26Providing, laying, jointing & testing GMSERW pipes (Zinc coated) with 94% circumfrential butt welded joints & 6% intermediate flanged joints of total length by electrical arc welding (weld thickness shall be equal to pipe wall thickness) confirming to BIS/ISO: 3183-2007 of steel grade L-290 or X-42 & L-210 or A (latest with upto date amendments) for the following pipe diametres having wall thickness & flange table as specified below & capable of withstanding required test pressure in a random length of 5.5 to 6.5 meters including cost of manufacturing/fabrication of reducers/tapers, all short pieces, bends etc. made from parent tubes as per site requirements. The laying of pipe, where ever required, shall include flanged joints duly welded in three layers (two at outer & one at inner face) at suitable spacing as per the directions of the Enginer-in-charge (Earth work in trenches and the cost of providing flanges i/c nuts & bolts & gasket will be measured and paid for seperately) and all operations such as cutting, welding, jointing, fabrication of bends, tees i.e. lowering & laying in excavated Trenches to ensure required level i/c flushing, cleaning and hydraulic testing complete in all respects shall be carried out to the entire satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe and the pipes shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards and the damaged portion of the pipes and specials (if damaged during laying jointing operation of pipe) made form the parent tube, shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon/L&T or ISI marked make. The rates also includes entire carriage of materialwith in all leads and lifts, flushing, cleaning & hydraulic testing, DP test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge.
27125 mm dia RD 0 to 200 Mtr = 200 Mtr Wall Thickness = 4.80 mm
28250 mm dia RD 0 to 230 Mtr = 230 Mtr Wall Thickness = 4.80 mm
29200 mm dia RD 0 to 500 Mtr = 500 Mtr Wall Thickness = 4.80 mm
30Providing and welding M.S. flanges (In Pair's) at 6% joint flanged, conforming to following tables as per IS 6392-1971 (Latest with up to date amendments) with MSERW pipe by two layers on outer faces and one layers on inner face to make the joint leak proof (The cost of providing and laying of GI pipes and butt welded joint to be measured and paid for separately). The welding of flanges should conform to IS: 816-1969 with electrodes as per IS: 814-1991 and required number of nuts and bolts conforming to IS 1364 including cost of gasket sheet nuts & bolts. The thickness of gasket sheet not less then 3.00mm conforming to IS 2712-1998. The work shall be done to the entire satisfaction of Engineer in Charge with in all leads and lifts.
31125 mm dia (Flange Table - 5)
32250 mm dia (Flange Table - 5)
33200 mm dia (Flange Table - 5)
34Providing double flanged Cl Reflux/Non-return valve of Kirloskar/ Lader make of follwoing dia (PN 1.0), conforming to IS-14846 with upto date amendaments and capable of with standing the normal seat pressure of 16 kg/cm2. complete in all respects with in all leads & lifts as per directions and entire to the satisfaction of the Engineer-in-charge.
35125 mm dia
36250 mm dia
37200 mm dia
38Providing and fixing cast iron air valve of 40 mm dioa double Ball type Kirloskar/ Lader make of folkwoing dia (PN 1.0), conforming to with upto date amendaments and capable of with standing the normal seat pressure of 10 Bar Hyd or 11.22 kg/cm2.complete in all respects with in all leads & lifts as per directions and entire to the satisfaction of the Engineer-in-charge.
39LWSS Sihor Balla
40Supply of submersible pumping set of KSB/Kirloskar/Johnston/Crompton/BS/ SABAR/ Oswal make conforming to latest relevant BIS Code 8034:1976. The pump should be fitted with bronze impeller or suitable alloys suitable for handling Clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP & 2900/1450rpm of reputed make conforming to BIS 9283-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps, cable clips and depth gauge etc.
41Location of site :- The site is located at a distance of 35 kms from Divisaion.
42The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
43Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
44Rated Voltage :- 415 (+/-) 10% Treated.
45Type of water (Raw/ Treated) Clear Water
46Water free from sand or not :- Free from sand (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
47Humidity :- Humid during rainy season.
48Nature of atmosphere :- Normal
49Water corrosive or not :- Not corrosive
50Turbidity :- Less than 50.00 ppm
51PSL Leval 516.48 mtr.
52Discharge level highest point 548.90 mtr.
53No. of pump required 2 Nos (One stand by)
54Discharge required from each Pump 11.08 LPS (For each Pump)
55Static Head in mtr
56Total head in mtr 39.02 mtr.
57Length of R/Main 200.00 mtr.
58Dia of R/Main 125 mm dia GMSERW Pipe
59No of working hours P/day 8.00 Hours
60Limits of pump operction (-) 15 % ( + ) 10 % of total head
61H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
62R.M.P. of Pump (2900/1450) 2900 RPM
63MNPSH available 450 M
64Test Run 16 hours Continuousely for 7 days
65Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
66Supply, Installation, Testing and Commissioning of Fully Automatic LT Panel for submersible pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos, pump of rating 12.50 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
67Energy Saving Variable Frequency Starter of 12.50 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequency of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture of reputed make. 3(i) Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication Make:- L&T/Conserve/Schnieder/Aarmation 1 No.3(ii) Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 (Latest edition) 1 No. 3(iii) LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 (Part I & II) latest with upto date ammendments 1 No. 3(iv) LED On / Off & Trip indicator and push buttons, Control and power wiring, Power capacitor, Cooling fan 230 VAC, Control terminal, Bus Bar, ie.Bolt, insulator, etc. 1No. 3(v) Selector Switch for Auto and Manual Operation 1No. 3(vi) Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions 2 No. 3(vii) Control Transformer Make: Aarmation Electric/MAS/Elle 1 No. 3(viii) Power and Control Wiring and Busbar 1No. 3(ix) Installation, Commissioning and Software Development 1 No. 3(x) Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges 1No.3(xi) Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements 1 No. 3(xi) Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schnieder/L&T 1 No.
68Automation System for Unmanned Operations with SCADA features, PLC, HMI and Level Sensor: (i) PLC (Programmable logic controller) with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Aarmation Electric/Bechoff Automation/Rockwell Automation 1 No. (ii) Electronic relay card 8 channel 1 No. (iii) SMPS 4.5 Amps to energise PLC system 1 No. (iv) HMI (Human Machine Interface) 7\\" display for Monitoring and Controlling of Centrifugal pumps Make: Aarmation Electric/Bechoff Automation/Roackwell 1No. (v) Control MCB for Automation System 1 No. (vi) Level Sensor to indicate the water level of tank remotely 1 No. (vi) Shielded Data Cable for Communication of Level Sensor with PLC 1 No. (vii) Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/Rockwell Automation. (viii) Cloud GateWay for Data Clouding to Server 1 No. (ix) SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/Backoff. 1 No. (x) Cloud Space for data storage at cloud/server 1 No. (xi) Installation, Commissioning and Software Development.
69Providing and fixing of Kirloskar/Kilburn/Leader/Kartar make Cast iron double flanged swing Check type Reflux Valve of class PN 1.0 having bye pass arrangement (to be provided on delivery side) of size of 1 size higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 10.20Kgs./cm² confirming to BIS 5312-1984 Part-II) (The size & class of valve shall be specified by the tenderer).
70Providing & fixing of Kirloskar / Kilburn / Leader/Kartar make Cast Iron double flanged swing check type Reflex valve of class PN 1.0 having by pass arrangement and size equal to dia of R/Main that is 125 mm dia) and shall be suitable for withstanding nominal seat pressure of 10.20 Kgs./cm² confirming to BIS 5312-1984 Part-II) (The size & class of valve shall be specified by the tenderer).
71Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part 1) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles, flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
72On supply side of 3½ core copper cable 4.00 mm² (From HPSEB Meter to Switch & Starter).
73On motor side 3 core flat joint less copper cable of size 2.50 mm² (From Switch & Starter to Motor) pump installed in the bore.
74Supply of standard make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
75P/L GMSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set. The pipe shall conform to relevant BIS codes & capable of with standing the field test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
76Column assembly (size to be specified by the tenderer)
77Providing and lying double loop earthing with copper plate 600x600 x3 thick electrode and copper strip of 25x3 complete including providing of material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, Copper/GI wire/ Strips of required capacity conforming to BIS 8034-1978 latest with upto date ammendments for above motor & other electrical equipments including all civil works.
78Erection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
79LWSS Chowki Keor
80Supply of submersible pumping set of KSB/Kirloskar/Johnston/Crompton/BS/ SABAR/Oswal make conforming to latest relevant BIS Code 8034:1976. The pump should be fitted with bronze impeller or suitable alloys suitable for handling Clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP & 2900/1450rpm of reputed make conforming to BIS 9283-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps, cable clips and depth gauge etc.
81Location of site :- The site is located at a distance of 35 kms from Divisaion.
82The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
83Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
84Rated Voltage :- 415 (+/-) 10% Treated.
85Type of water (Raw/ Treated) Clear Water
86Water free from sand or not :- Free from sand (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
87Humidity :- Humid during rainy season.
88Nature of atmosphere :- Normal
89Water corrosive or not :- Not corrosive
90Turbidity :- Less than 50.00 ppm
91PSL Leval 516.48 mtr.
92Discharge level highest point 549.75 mtr.
93No. of pump required 2 Nos (One stand by)
94Discharge required from each Pump 23.03 LPS (For each Pump)
95Static Head in mtr
96Total head in mtr 40.38 mtr.
97Length of R/Main 230.00 mtr.
98Dia of R/Main 250 mm dia GMSERW Pipe
99No of working hours P/day 8.00 Hours
100Limits of pump operction (-) 15 % ( + ) 10 % of total head
101H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
102R.M.P. of Pump (2900/1450) 2900 RPM
103MNPSH available 450 M
104Test Run 16 hours Continuousely for 7 days
105Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
106Supply, Installation, Testing and Commissioning of Fully Automatic LT Panel for submersible pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump of rating 30.00 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
107Energy Saving Variable Frequency Starter of 30.00 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequency of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture of reputed make. 3(i) Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication Make:- L&T/Conserve/Schnieder/Aarmation 1 No.3(ii) Main incomer MCCB of suitable capacity of L&T/Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 (Latest edition) 1 No. 3(iii) LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 (Part I & II) latest with upto date ammendments 1 No. 3(iv) LED On/Off & Trip indicator and push buttons, Control and power wiring, Power capacitor, Cooling fan 230 VAC, Control terminal, Bus Bar, i.c.Bolt, insulator, etc. 1No. 3(v) Selector Switch for Auto and Manual Operation 1No. 3(vi) Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions 2 No. 3(vii) Control Transformer Make: Aarmation Electric/MAS/Elle 1 No. 3(viii) Power and Control Wiring and Busbar 1No. 3(ix) Installation, Commissioning and Software Development 1 No. 3(x) Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges 1No.3(xi) Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements 1 No. 3(xi) Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schnieder/L&T 1 No.
108Automation System for Unmanned Operations with SCADA features, PLC, HMI and Level Sensor: (i) PLC (Programmable logic controller) with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Aarmation Electric/Bechoff Automation/Rockwell Automation 1 No. (ii) Electronic relay card 8 channel 1 No. (iii) SMPS 4.5 Amps to energise PLC system 1 No. (iv) HMI (Human Machine Interface) 7\\" display for Monitoring and Controlling of Centrifugal pumps Make: Aarmation Electric/Bechoff Automation/Roackwell 1No. (v) Control MCB for Automation System 1 No. (vi) Level Sensor to indicate the water level of tank remotely 1 No. (vi) Shielded Data Cable for Communication of Level Sensor with PLC 1 No. (vii) Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/ Rockwell Automation. (viii) Cloud GateWay for Data Clouding to Server 1 No. (ix) SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/ Backoff. 1 No. (x) Cloud Space for data storage at cloud/server 1 No. (xi) Installation, Commissioning and Software Development.
109Providing and fixing of Kirloskar/Kilburn/Leader/Kartar make Cast iron double flanged swing Check type Reflux Valve of class PN 1.0 having bye pass arrangement (to be provided on delivery side) of size of 1 size higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 10.20Kgs./cm² confirming to BIS 5312-1984 Part-II) (The size & class of valve shall be specified by the tenderer).
110Providing & fixing of Kirloskar / Kilburn / Leader/Kartar make Cast Iron double flanged swing check type Reflex valve of class PN 1.0 having by pass arrangement and size equal to dia of R/Main that is 250 mm dia) and shall be suitable for withstanding nominal seat pressure of 10.20 Kgs./cm² confirming to BIS 5312-1984 Part-II) (The size & class of valve shall be specified by the tenderer).
111Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part 1)-1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles, flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type, size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
112On supply side of 3½ core copper cable 10.00 mm² (From HPSEB Meter to Switch & Starter).
113On motor side 3 core flat joint less copper cable of size 6.00 mm² (From Switch & Starter to Motor) pump installed in the bore.
114Supply of standard make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
115P/L GMSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set. The pipe shall conform to relevant BIS codes & capable of with standing the field test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
116Column assembly (size to be specified by the tenderer)
117Providing and lying double loop earthing with copper plate 600x600 x3 thick electrode and copper strip of 25x3 complete including providing of material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, Copper/GI wire/ Strips of required capacity conforming to BIS 8034-1978 latest with upto date ammendments for above motor & other electrical equipments including all civil works.
118Erection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
119LWSS Bulli
120Supply of submersible pumping set of KSB/Kirloskar/Johnston/Crompton/BS/ SABAR/ Oswal make conforming to latest relevant BIS Code 8034:1976. The pump should be fitted with bronze impeller or suitable alloys suitable for handling Clear water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP & 2900/1450rpm of reputed make conforming to BIS 9283-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps, cable clips and depth gauge etc.
121Location of site :- The site is located at a distance of 35 kms from Divisaion.
122The Altitude of place in which the motor is intended to work :- Altitude of phase is 500 mtr. Above mean sea level.
123Type of current :- A.C. Three phase supply with frequency of 50 cycles per second.
124Rated Voltage :- 415 (+/-) 10% Treated.
125Type of water (Raw/ Treated) Clear Water
126Water free from sand or not :- Free from sand (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
127Humidity :- Humid during rainy season.
128Nature of atmosphere :- Normal
129Water corrosive or not :- Not corrosive
130Turbidity :- Less than 50.00 ppm
131PSL Leval 515.90 mtr.
132Discharge level highest point 550.33 mtr.
133No. of pump required 2 Nos (One stand by)
134Discharge required from each Pump 18.37 LPS (For each Pump)
135Static Head in mtr
136Total head in mtr 47.24 mtr.
137Length of R/Main 500.00 mtr.
138Dia of R/Main 200 mm dia GMSERW Pipe
139No of working hours P/day 8.00 Hours
140Limits of pump operction (-) 15 % ( + ) 10 % of total head
141H.P. Motor /drive unit: - BHP with following margins/multipying factor at duty point whichevear is higher (a) Up to 2 HP = 1.5 (d) 10 to 20 HP = 1.2 (b) 2 to 5 HP = 1.4 (e) 20 to 100 HP = 1.15 (c) 5 to 10 HP = 1.3 (f) Above 100 HP = 1.10
142R.M.P. of Pump (2900/1450) 2900 RPM
143MNPSH available 450 M
144Test Run 16 hours Continuousely for 7 days
145Charactrstics of water : - (a) Temperature 20°C (b) Turbidity upto 10 NTP (c) Hardness- Mg/Liter (as CaCo3) (d) Alkalinity Mg/Liter (as CaCo3) (e) PH= ______ (f) Total Solids ______ Mg/Litre (h) Other ______
146Supply, Installation, Testing and Commissioning of Fully Automatic LT Panel for submersible pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 2 nos. pump of rating 30.00 HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
147Energy Saving Variable Frequency Starter of 30.00 HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequency of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture of reputed make. 3(i) Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication Make:- L&T/Conserve/Schnieder/Aarmation 1 No.3(ii) Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) 1 No. 3(iii) LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 (Part I & II) latest with upto date ammendments 1 No. 3(iv) LED On / Off & Trip indicator and push buttons, Control and power wiring, Power capacitor, Cooling fan 230 VAC, Control terminal, Bus Bar, i.c.Bolt, insulator, etc. 1No. 3(v) Selector Switch for Auto and Manual Operation 1No. 3(vi) Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions 2 No. 3(vii) Control Transformer Make: Aarmation Electric/MAS/Elle 1 No. 3(viii) Power and Control Wiring and Busbar 1No. 3(ix) Installation, Commissioning and Software Development 1 No. 3(x) Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges 1No.3(ii) Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements 1 No. 3(xi) Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schnieder/L&T 1 No.
148Automation System for Unmanned Operations with SCADA features, PLC, HMI and Level Sensor :- (i) PLC (Programmable logic controller) with appropriate digital and analog inputs and outputs to give automatic command to Star Delta Starter Panel/ Energy Saving Variable Frequency Starter Panel Make Aarmation Electric/Bechoff Automation/Rockwell Automation 1 No. (ii) Electronic relay card 8 channel 1 No. (iii) SMPS 4.5 Amps to energise PLC system 1 No. (iv) HMI (Human Machine Interface) 7\\" display for Monitoring and Controlling of Centrifugal pumps Make: Aarmation Electric/Bechoff Automation/Roackwell 1No. (v) Control MCB for Automation System 1 No. (vi) Level Sensor to indicate the water level of tank remotely 1 No. (vi) Shielded Data Cable for Communication of Level Sensor with PLC 1 No. (vii) Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/ Rockwell Automation. (viii) Cloud GateWay for Data Clouding to Server 1 No. (ix) SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/ Backoff. 1 No. (x) Cloud Space for data storage at cloud/server 1 No. (xi) Installation, Commissioning and Software Development.
149Providing and fixing of Kirloskar/Kilburn/Leader/Kartar make Cast iron double flanged swing Check type Reflux Valve of class PN 1.0 having bye pass arrangement ( to be provided on delivery side) of size of 1 size higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 10.20Kgs./cm² confirming to BIS 5312-1984 Part-II )(The size & class of valve shall be specified by the tenderer).
150Providing & fixing of Kirloskar / Kilburn / Leader/ Kartar make Cast Iron double flanged swing check type Reflex valve of class PN 1.0 having pass arrangement and size equal to dia of R/Main that is 200 mm dia ) and shall be suitable for withstanding nominal seat pressure of 10.20 Kgs./cm² confirming to BIS 5312-1984 Part-II )(The size & class of valve shall be specified by the tenderer).
151Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
152On supply side of 3½ core copper cable 10.00 mm² ( From HPSEB Meter to Switch & Starter).
153On motor side 3 core flat joint less copper cable of size 6.00 mm² ( From Switch & Starter to Motor) pump installed in the bore.
154Supply of standard make 100 mm dia circular/square dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
155P/L GMSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the field test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
156Column assembly (size to be specified by the tenderer)
157Providing and lying double loop earthing with copper plate 600x600 x3 thick electrode and copper strip of 25x3 complete including providing of material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, Copper /GI wire/ Strips of required capacity conforming to BIS 8034-1978 latest with upto date ammendments for above motor & other electrical equipments including all civil works.
158Erection of all equipments including cost of tees, bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56352761
AUTHORITY Government Departments
TENDER VALUE 2.47 Crore
LAST DATE 17-07-2026
Authority
Authority Name Irrigation And Public Health Department
Work Description Tender for Relocation & Reconstruction Of Various Lift Water Schemes (Lwss Sihor Balla) And Lift Irrigation Schemes (Lis Chowki Kior And Lis Bulli) On The Right Bank Of River Beas Affected Due To Submergence In The Poundage Of Dhoulasidh In Tehsil Jawalamukhi Distt. Kangra (Hp)
Basic Detail
Tender No JAM-KNG02-742
Bidding Type Tender
Location
City Kangra
State Himachal Pradesh
Key Dates
Publish Date 08 Jul 2026
Submission Date 17 Jul 2026
Open Date 18 Jul 2026
Finance
Tender Value 2.47 Crore
Tender Fee 7000
EMD 3.22 Lakhs
Exemption Not Available
Document List
BOQ_205061.xls
Form6.pdf
Form8.pdf
Tendernotice_1 (10).pdf
Termsandconditions.pdf
514eea4e-ee00-4050-aeaf-91e06ec50707.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 08, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 17, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 5 days
Jul 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 6 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_205061.xls

pdf

Form6.pdf

pdf

Form8.pdf

pdf

Tendernotice_1 (10).pdf

pdf

Termsandconditions.pdf

html

514eea4e-ee00-4050-aeaf-91e06ec50707.html

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders