Tender For Special Repair/ Replacement To Street Light Junction Boxes, Timer Switches, Pole And Led Lights At 1 Fod Adm Area Under Ge (Utilities) Udh Ur.
Tender Value
48.27 Lakhs
Estimated cost
Bid Submission
28 Jul 2026
16 days left
EMD
96530
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Reasi → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Special Repair/ Replacement To Street Light Junction Boxes, Timer Switches, Pole And Led Lights At 1 Fod Adm Area Under Ge (Utilities) Udh Ur.
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE Utilities Udhampur Name of Work: Special Repair/ replacement to street light junction boxes, timer switches, pole and LED lights at 1 FOD Adm Area under GE (Utilities) Udhampur. Contract No: GE/U-77/2026-27 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Ser.No. Item Description Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT Without Taxes TOTAL AMOUNT TOTAL AMOUNT In Words |
| 2 | Dismantling of unserviceable concerete/steel tubular pole any size upto 9 mtr long including breaking up PCC and making good disturbed surface and removing materials from site of work complete all as specified and directed by Engineer-in-Charge. |
| 3 | Supply and fixing of steel tubular swaged poles with two coat of aluminium paint ovar a coat of red oxide zinc chrome prime in externally exposed to view portion and black bituminous painting to intenal surface and portion embeded in concrete incl making five alternative strips 30 cm wide in different colour above ground level or plinth level incl marking of MES pole No in black paint complete with cast iron base plate, final tapper plug, bolts, nuts and screws as specified type 410 SP-31 (9.00 mtr long) and complete all as specified and directed by Engineer-in-Charge. |
| 4 | M & L for PCC 1:4:8, type D-2, (using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 5 | M & L for PCC 1:3:6, type C-2, (using 40mm graded stone aggregate) as in foundation filling and mass concrete complete all as specified and directed by Engineer-in-Charge. |
| 6 | M & L for PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) as in coping including necessary use & waste of form work complete all as specified and directed by Engineer-in-Charge. |
| 7 | Supply and fixing LED street light fitting of capacity 72 watts ,230 volts AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optic and equipped with IP 66 protection, with impact and corrsion resistant complete with drivers and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 and all accessories and making all necessary connection including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge.. |
| 8 | Supply and fixing 150 watt energy , saving environmental friendly, long life exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural features or retail spaces, and as per national lighting code by using each LED>1W and <3 W, LED Chip efficiency>=135 Lumens/Watt, CRI>70, CCT 5000K to 6500 K with LED Lifespan at 70% of light output>50000 hours. The driver should be 140 V to 270 V universal driver with built in surge protection >5 KV, 50 Hz, +/-3%, pf>0.95, THD<10% with system efficiency must be >85 lumens/Watt and power efficiency >=90% and overall, Driver and luminaire shall comply LM-79/IS: 16106 including taking out of old unserviceable one, complete all as specified and directed by Engineer-in-Charge.. |
| 9 | S & F GI tubing medium grade 40 mm dia in protection of cable of difference dia laid in trench under road/foot path or fixed on pole with necessary clamps with bolts etc complete all as specified and directed by Engineer-in-Charge. |
| 10 | S & F GI tubing medium grade 50 mm dia in protection of cable of difference dia laid in trench under road/foot path or fixed on pole with necessary clamps with bolts etc complete all as specified and directed by Engineer-in-Charge. |
| 11 | Taking up old serviceable/unserviceable UG cable of size 16 Sqmm 4 core to 35 Sqmm 3.5 core from trench for replacement , repair and re-laying or re-routing. Earth work shall be measured and paid separately under appropriate items of Sch-'A'), complete all as specified and directed by Engineer-in-Charge. |
| 12 | Taking up old serviceable/unserviceable UG cable of size 50 Sqmm 3.5 core to 95 Sqmm 3.5 core from trench for replacement , repair and re-laying or re-routing. Earth work shall be measured and paid separately under appropriate items of Sch-'A'), complete all as specified and directed by Engineer-in-Charge. |
| 13 | Excavation in trenches not exc. 1.5 metre wide and not exc. 1.50 mtr depth for laying of underground cable, erection of poles etc. and getting out in soft/loose soil including separating serviceable bricks for re-use at site obtained during excavation complete all as specified and directed by Engineer-in-Charge. |
| 14 | Description all as per item Ser No 12.00 here-in-before, but exc. 1.50 metre depth and not exc. 3.00 metre deep, complete all as specified and directed by Engineer-in-Charge. |
| 15 | Returning, filling in, including, spreading, leveling, watering and well ramming in layers n.exc. 25 cm in soils complete all as specified and directed by Engineer-in-Charge. |
| 16 | Removing excavated soil n. exc 50 m and depositing where directed at a level n.exc. 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 17 | S&F double walled corrugated (DWC) pipe of size 63 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of LT cable in under ground complete all as specified and directed by Engineer-in-Charge. |
| 18 | S&F double walled corrugated (DWC) pipe of size 50 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of LT cable in under ground complete all as specified and directed by Engineer-in-Charge. |
| 19 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed, PVC insulated with multi stranded aluminium conductor cable of cross sectional area of following size, 1100 volts grade, ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugsof sizes 16 Sqmm 4 core complete all as specified and directed by Engineer-in-Charge. |
| 20 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed, PVC insulated with multi stranded aluminium conductor cable of cross sectional area of following size, 1100 volts grade, ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugsof sizes 35 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed, PVC insulated with multi stranded aluminium conductor cable of cross sectional area of following size, 1100 volts grade, ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugsof sizes 50 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 22 | Supply, laying, testing and commissioning LT UG armoured, XLPE insulated, inner and outer sheathed, PVC insulated with multi stranded aluminium conductor cable of cross sectional area of following size, 1100 volts grade, ISI marked with IS-7098, laid in trenches/floor/duct/wall including aluminium lugsof sizes 95 Sqmm 3.5 core complete all as specified and directed by Engineer-in-Charge. |
| 23 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement and mounting of timer panel as specification given in outgoing details of LT panel complete with following :- Incoming(a) MCCB 100 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 18 KA-01 No,Outgoing (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set |
| 24 | OutgoingAutomatic street light control switch of 8 KW three phase using Infrared sensor based and astro sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitabe rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20-32 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection class-2 (Hansel make). The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed. Model No SWADEEP 66- 8 KW3P or L&T or equivalent from the list of make given in particular sepecification |
| 25 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 240 Volts 1 phase 2 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement and mounting of timer panel as specification given in outgoing details of LT panel complete with following :-Incoming(a) MCCB 63 A, 2 pole, suitable for 240 Volts with extended 50Hz ,with rupturing capacity 16 KA-01 No,Outgoing (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,2 pole, not less than 75 cm long mounted on insulators 01 set |
| 26 | OutgoingS&F in replacement of automatic street light control switch of 3 KW single phase(20 Amp per phase) having protection IP-66 using Infrared sensor based and astro sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitable rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection . The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-Charge.Make - Navdeep with smart timer Model no -Navdeep-66-3kw 1P. or equivalent from the list of make given in particular sepecification |
| 27 | Supply and fixing street light bracket made out of 40 mm light grade GI tubing minimum 1.5 Mtr long with with suitable adapter to suit the opening of street light on one end alongwith integrated fabricated adapter round cup type with 02 Nos studs on outer side to fix the braket on top of existing steel tubular pole two way, with necessary MS clamps with one coat of red oxide and two coats of alluminium paint upon fabricated adapter including nut, bolts, washers complete all as specified and directed by Engr-in-Charge. |
| 28 | S&F of Steel tubular swaged Ring suitable for 12 m long pole for semi highmast light and for fixing of four nos flood loghts with bolts, nuts and screws, ring made out of ERW MS tubing conforming to IS-2713 including drilling of holes of required size for fixing of brackets , painting the exposed surfaces of ring with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of silver paint on the surface complete all as specified and directed by Engr-in-Charge. |
| 29 | Taking down existing old street light panel /feeder box/LT panel of any type and zsize and capaacity comprising of MCCB & switch fuse unit of any capacity and size including bus bar, ammeters, voltmeters etc after disconnecting all cable connection and removing from site complete all as specified and directed by Engr-in-Charge. |
| 30 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following:- Incoming(a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No, |
| 31 | Outgoing (a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 setNote- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level(iii) Outgoing MCCBs shall be fed with solid busbar connectors and (iii) Cables shall be terminated using gun metal /SS glands.(vi) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(v) cable glands for incoming and out going suitable cables is including rate quated by vendover |
| 32 | Supply, install commissioning and testing of cubical out door feeder LT panel board of suitable size, platform mounted, factory made totally enclosed dust and vermin proof (protection class IP-54, CPRI Approved) double shutter front and back opening with locking arrangement complete made of angle iron 50 mm x 50 mm x 6 mm thick frame work and 3.15 mm thick CRCA sheet duly painted with powder coated paint to all steel surfaces over outside and inside complete. The panel board shall be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system with epoxy type copper bus bar of appropriate size and internal control wiring shall be of insulated multi stranded copper conductor cables. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level (iii) Outgoing MCCBs shall be fed with solid busbar connectors and |
| 33 | (iv) Cables shall be terminated using gun metal /SS glands. (v) including suitable thimbles/lugs, nut bolts ,washers fitted the cables(vi) cable glands for incoming and out going suitable cables is including rate quated by vendover (vii) including suitable thimbles/lugs, nut bolts ,washers fitted the cables INCOMING(a) MCCB four pole 160 Amps, 25 KA at 415 Volts- 01 No. (b) 250 Amps rated copper bus bar suitable for 3 phase 4 wire system - 01 No.(c) Phase indicating lamp RYB neon type (Set of three ) -01 Set (d) Voltmeter Digital type 0-500 Volts capacity with selector switch.(e) Ammeter Digital type 0-200 Amp capacity with selector switch and CT coils OUT GOING(f) MCCB four pole 100 Amps, 25 KA at 415 Volts-04No |
| 34 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed steel conduit of size 2x2.5+1x2.5 Sqmm earth wire |
| 35 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60cmx 6 mm thick buried directly in ground vertically to a depth not less than 2.25 mtrs below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to galvanised iron strips 32 x 6 mm by means of nuts both check nuts and washers made of galvanised iron or steel earth strip protected by galvanised iron pipe 40 mm bore medium grade upto ground level as directed and including concrete pit in PCC ( 1 : 3 : 6) type C1 pre cast RCC cover slab 30 cm x 30 cm x 10 cm thick including reinforcement with 8 mm dia steel deformed bars at the rate of 10 cm both ways with one lifting handle made of 8 mm dia MS bar funnel, wire mesh 20 mm bore galvanised iron or steel pipe medium grade for watering charcoal on coke and salt in alternate layers, necessary excavation and earth work in any type of soil complete all as shown in electrical plate No 5 of MES schedule Pt-I and testing on completion including supply and fix earth pit chamber board of 3.15 mm thick mild steel sheet sheet of size min 45cmx30cm fixed with 12 mm thick MS rod two nos upto 90 cm height by nuts/bolts including spray painting with two coats of synthetic enamel black paint complete MS sheet both side including writing letter min 6 cm height i.e Earth pit No . Location Earthing test value and date and other letters complete. |
| 36 | Supply and fixing non transparent looping SMC kiosks pole box 3 phase of size 310×210×120 mm made out of engineering plastic one piece moulding siemens gray colour with hold fast including 4 Nos aluminium strips 60 amp of requird size fixed on unbrakable insulator and one no single pole MCB 1 to 3 amp 'C' curve including taking out of old unserviceable one, complete all as specified and directed by Engr-in-Charge. |
| 37 | Supply and fix in repair energy saving rectangular LED flood light fitting 250 Watts, 240 volts AC, cool white colour, CCT 5700°K, CRI>70, THD<10%, system lumens not less than 120 lumens/watt with innovative thermal management, available with multiple optics, equipped with IP-66 protection, 5 KV surge protection, 120 Lm/watt aluminium die cast housing with toughened glass visor, life of luminaires should not be less than 50000 burning hours and suitable for large area lighting including fixing on High mast pole/Buildings/TARMAC poles etc. by means of clamps, nuts, bolts and any other accessories complete all as specified and directed by Engr-in-charge.Make-Bajaj Cat Part No. PRAZE F 300L WH NB-A5 TG SD or equivalent from the list of make given in particular sepecifivation |
| 38 | Note for Item No 6.00 & 7.00:- All LED/Street/Flood light shall be embossed from the company/contractor by GE (U) Udhampur and CA No. Total in Figures 0.0 0.0 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysJul 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer