Tender For Supply & Installation Of Electrical Life Safety Equipment Such As Supply Installation Testing and Commissioning of Electrical Protection System, Spd And Earthing Protection System To All Panel Board And Rccb And Rcbo To All Db Box And Upgr
Tender Overview
Project Description
Tender for Supply & Installation Of Electrical Life Safety Equipment Such As Supply Installation Testing and Commissioning of Electrical Protection System, Spd And Earthing Protection System To All Panel Board And Rccb And Rcbo To All Db Box And Upgradation Of Cable Laying Of Different Buildings Opd, Trauma Care, Icu And Rdc Of Mkcg, Mc&H At Berh Ur.
BOQ
| Sl. No. | Item Description |
| 1 | Surge Protection Device for Power Line Protection: Supply and fixing Surge protection Device (SPD) Class- B, Type - I,Especially designed to handle Lightning Impulse current 10/350 μs waveform. Connected in Main Incoming Panel - Three phase with neutral system (TT& TN-S System). Made of - Encapsulated /Non extinguising spark gap Technology, Impulse discharge current limp (10/350)μs -50 (KA)/Pole and Maximum Discharge Current Imax 12.5 kA (10/350)μs. Voltage protection level,Up <1.3 KV, Response time ta <100 ns, Operating temperature range -(-)40°C to (+)80°C. Mounting on - Din Rail, Degree of protection of enclosure - IP 20, Connection Cross Section (Flexiable) - 10sqmm-25sqmm., Available LED Indication for Healthy and Failure, Testing Standards/ Certifications - IEC 61643-11 with Transperant Enclosure in complete as per the direction of Engineer in charge.Make-Legrand/OBO/DEHN/Schneider/ABB/Siemens |
| 2 | Supply of Surge protection Device (SPD) Clasee B+C, Type - 1+11 for handling Lightning surges of 10/350 μs & Switching surges of 8/20 us waveform. Installed in DB and Sub DB. Technology (L-N)-MOV with built in thermal fuse, (N-PE)-Spark Gap Encapsulated/Non-exhausting, Maximum Continuous operating Voltage -320V per pole, Nominal Discharge Current In 30 kA (8/20 μsec), Maximum Discharge Current Imax 40 kA (8/20 μsec). Lightning Impulse Current 7 kA (10/350 μsec)/pole 25 KA (10/350 μsec) Total. Voltage protection level,Up <1.3 KV, Response time ta -(L-N) - 25ns (N-PE) <100 ns,Operating temperature range -(-)40°C to (+)80°C. Mounting on Din Rail, Degree of protection of enclosure - IP 20, Standards/ Certifications - IEC 61643-1 in complete as per the direction of Engineer in charge. .Model: V25 B+C- 3+NPE-320 with Transperant Enclosure.Make-Legrand/OBO/DEHN/Schneider/ABB/Siemens |
| 3 | 630 A MAIN Panel Board AT RDC GF/O/o SUPERINTENDENT GFS/I/T&Commissioning of CPRI tested LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by siemens gray powder cote paint fallowed by 9 tank acid treatment is designed as G.A drawing as per direction of Engg.-in-Charge.Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.60X10MM Separate Aluminium Earth bus bar should be installed. All the feeders shall have ON/OFF/TRIP indication.In commer-1-01 number of 400A 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS(FROM EX TRANSFORMER)In commer-2-01 number of 400A 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS (DG INCOMMER)01 no of 630A 4P onload changeover switch (MakeABB/Siemens/Schneider/Legrand)Busbar-1&2 04 numbers of 500Amps AL busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing)Outgoing- 08 numbers of 125 A 4P Icu=100%Ics, 25 KA MCCB with adjustable TM based Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS) TO GF. Outgoing- 03 number of 400 A 4P Icu=100%Ics, 25 KA MCCB with adjustable TM based Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS) TO 1FInstrument- (i) 06 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data for all the incoming feeders2 no. 3P+N 65kA type 1+2 SPD with 63A rating,10KA breaking capacity ,4P MCB(Make-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN ) |
| 4 | S/I/T&Commissioning of CPRI tested LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by siemens gray powder cote paint fallowed by 9 tank acid treatment is designed as G.A drawing as per direction of Engg.-in-Charge.Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.20X10MM Separate Aluminium Earth bus bar should be installed. All the feeders shall have ON/OFF/TRIP indication.In commer-1-01 number of 250A 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS(FROM EX TRANSFORMER)In commer-2-01 number of 250A 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS (DG INCOMMER)In commer-2- 01 no of 250A 4P onload changeover switch (MakeABB/Siemens/Schneider/Legrand)Busbar-1&2 04 numbers of 300Amps AL busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing) Outgoing- 06 numbers of 125 A 4P Icu=100%Ics, 25 KA MCCB with adjustable TM based Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS)Instrument- (i) 06 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data for all the incoming feeders2 no. 3P+N 65kA type 1+2 SPD with 63A rating,10KA breaking capacity ,4P MCB(Make-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN ) |
| 5 | S/I/T&Commissioning of LT indoor wall mounted cubical type electrical main panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed as G.A drawing. (FOR ALL MAIN CONNECTED LOAD) BUILDING power)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list.. 20X10MM Separate Aluminium Earth bus bar should be installed.ON,OFF,TRIP INDICATION for all the feeders shall be provided. In commer- 1 number of 125 A 4P Icu=100%Ics, 16 KA MCCB with adjustable TM based Release with Ics=100% Icu. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ABB Formula/ Schneider- CVS)Busbar- 04 numbers of 200 Amps AL busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator. (for outgoing)Out going- 04 numbers of 63A 4P MCB 10KA,C series (Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200)Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse.(ii) digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data for all the incoming feeders1 no. 3P+N 40kA 4P type 2 SPD with 63A rating,10KA breaking capacity ,4P MCB 10KA,C series (Make-LEGRAND/ Siemens/ Schneider/ABB/OBO/DEHN ) |
| 6 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge. 3.5core x 300 sq mm. |
| 7 | 3.5Cx185 sqmm |
| 8 | 3.5Cx240 sqmm |
| 9 | 3.5Cx70 sqmm |
| 10 | Supplying and making end termination with brass double compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. 3.5 core x300 sq mm |
| 11 | 3.5 core x240sq mm |
| 12 | 3.5 core x185sq mm |
| 13 | 3.5 core x70 sq mm |
| 14 | Laying of one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of size exceeding 120 sq.mm but not exceeding 400 sq.mm direct in ground including excavation, refilling the trench etc. as required but excluding sand cushioning and protective covering. |
| 15 | Laying of one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground including excavation, refilling the trench etc. as required but excluding sand cushioning and protective covering. |
| 16 | Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB Itus as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years6 Way(8+18) Way TPN MCB DD DB Horizontal Type suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door.Warranty on DB is 3 years |
| 17 | Supplying and fixing 63Amps 4P 415 volts MCB, C Series, 10 kA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.Warranty on MCB is 1 year. |
| 18 | Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 years.. |
| 19 | Supplying and fixing 40 Amps rating,C series,10KA breaking capacity, 2P, 230 volts, RCCB 30mA . Make- LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. The RCCB should be Replacement Warranty will be 1 year |
| 20 | Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI/V-Guard in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 6 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallic heavy duty conduit .(4X10+2X6) |
| 21 | Supply ,installation ,testing & commissioning of 10-20KVA Parallel UPS SYSTEM WITH IGBT based inverter system, true online double conversion system, inbuilt isolation transformer & automatic phase sequence corrector of 3ph in put to 3 ph output,240V, with built in BMS with IMD and Acoustic and Visual alaram system battery back up up to 30-45 minutes with MS Rack for battery Housing, DC cable 7 Mtr with SFU and links for installation (Battery required: 12V, 65AH, 32 No.s) protection for fault by OL,UV,EF,GF,OC,Ph. (Make:Numeric/ APC/ Vertiv)as per direction of Engg.-in-Charge. Warrentee period of all accessories & component & system must be 2 years & compelete test certificate must be submitted along with ups including component list & SLD. |
| 22 | Battery: 12v/26ah SMF batteries (Exide / Quanta/eq. make only) With Wide Range DC BUS facility, with Certification of IEC62040-1,2,3 Certification with CE/RoHS & PEP Compliance. SMF BATTER UP OF 60 MINUTES WITH DC CABLE 7 MTR, BREAKER, LINKS AND MS RACK FOR BATTERY HOUSING. with Two years warranty on both UPS & battery. |
| 23 | Recessed wiring to light point/Fan point/ Exhaust fan point/Call bell point with 1.5sq.mm FRLSH PVC insulated single core multistrand copper conductor of ISI marked with 20mm dia non-metallic PVC flexible conduit FRLS(Make-AKG/kinjol/Precision/Plasto/Polycab/Anchor/BEC/Norpack with fire proof) with 6Amp ,250V Modular switch ISI marked and ceiling rose ISI marked mounted on Metal box having front Modular cover of suitable size, G.I Metal box (Make-Schneider/ABB/Hager/Gliston/Legrand/Anchor) with 1.5sq.mm FR PVC insulated single core multistrand copper conductor as earth wire including all accessories and connection (Make of wire-Finolex/Polycab/V-Guard/Anchor/KEI/RHINO/Glowstar) Supply and fixing of Modular metal box on surface or in recess with suitable size of Modular cover in front including providing and fixing of 6Amp and 6Amp Modular switches connection ( Legrand mylinc/ Schneider clipsal/Hager insysta/Anchor Dura) |
| 24 | Recessed submain wiring alongwith earth wire with the following sizes of PVC insulated single core multistrand FRLSH copper conductor ISI marked conforming to IS-694/1990 in 20mm dia non metallic heavy duty flexible conduit 1.6 mm in surface /recessed PVC conduit as required (make of wire -Finolex/Polycab/Anchor/Havells/V-Guard/KEI/RHINO) 2 X 2.5sq.mm +1 X 1.5sqmm |
| 25 | 2 X 4sq.mm +1 X 1.5sqmm. |
| 26 | CABLE TRAY /RACE WAY FOR DISTRIBUTION OF POWERSupplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 200mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge. |
| 27 | Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 300mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge. |
| 28 | Supply and Fixing of PVC cable Trunk on Surface or Undergrounding Size 80mm(H) x 200mm(W) Heavy Duty MAKE- AKG/OBO/Neidax/Plasto/Precision UL specifications as required as per direction of Engg.-in-Charge. |
| 29 | Supply and fixing copper plate earthing 600 mm X 600 mm X 3.15 mm thick ISI marked including accessories and providing masonary with charcoal and salt as required. |
| 30 | Supply and laying of 25 mm x 5 mm copper strip on surface or in recess for connection etc as required. |
| 31 | Providing and fixing 8 SWG (4 mm) dia copper wire on surface or in recess for loop earthing as required |
| 32 | Earthing Copper Busbar with insulator, Copper Lugs and nut bolt as required as per direction of Engineer-in-charge |
| 33 | Foam type 5Ltrs, Fire extingusher |
| 34 | Co2 4.5Kgs |
| 35 | Dry Power 5KG |
| 36 | Fire Bucket with Stand (4nos.in each stand) |
| 37 | HT rubber mat (1Mtrx2mtr) |
| 38 | Shock Treatment chart Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 6 daysTender Documents