Tender For Construction Of Equipment Structure Of 33Kv Line And Tranformer Bay Alongwith Indoor Swicth Gears For Under Construction Rec Station At Chandgam Pulwama Under Ut Capex 2026-27.
Tender Value
1.08 Crore
Estimated cost
Bid Submission
28 Jul 2026
17 days left
EMD
2.16 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pulwama → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of Equipment Structure Of 33Kv Line And Tranformer Bay Alongwith Indoor Swicth Gears For Under Construction Rec Station At Chandgam Pulwama Under Ut Capex 2026-27.
BOQ
| Sl. No. | Item Description |
| 1 | Supply,Loading, Transportation, insurance, Unloading, Carriage and Delivery at Site, pit excavation of pits, installation,Testing and Commissioning of |
| 2 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) |
| 3 | 33 kV Isolator with Earthing Blade (36kV,800A, Outdoor,3 poles, 25 kA) |
| 4 | 33 kV Isolator without Earthing Blade (36kV,800A, Outdoor,3 poles, 25 kA) |
| 5 | 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core, Outdoor) (1 No. per Φ) |
| 6 | 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ) |
| 7 | 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) |
| 8 | 33 kV C&R Panel along with O/C, E/F,REF and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port |
| 9 | 33 kV 10 kN Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m |
| 10 | G.I Pipe structure for equipments having nominal bore 200mm, 5.9 mm Thick 3 m long as per OS 1161 with G.I Base Plate of size (1'.6\\"x1'.6\\") 8 mm Thick |
| 11 | Galvanised Steel Structures of sizes/sorts |
| 12 | Galvanised Nuts & Bolts |
| 13 | 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 14 | 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 15 | 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS. |
| 16 | Lugs, Ferrules etc. |
| 17 | 200 mm² ACSR Conductor( Panther) |
| 18 | T Clamps |
| 19 | 33 kV Single Tension Fittings (6 bolt) |
| 20 | 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting |
| 21 | Earth Wire 7/4.00 sqmm |
| 22 | GI flat for earthing 50x6 mm |
| 23 | 100 kVA,33/0.433 kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Copper wound) |
| 24 | 33 kV Horn Gap Fuse set |
| 25 | 95 mm² 3-1/2 core cable 1.1 KV grade armoured, XLPE insulated stranded Aluminium conductor FRLS |
| 26 | End termination Kits for 95 mm² 3-1/2 core cable (indoor/outdoor) |
| 27 | Earthing of 100 kVA SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCCslab cover. |
| 28 | 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, Outdoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (1+5) Set |
| 29 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) |
| 30 | 11 kV 630 mm² Single Core XLPE Cable (with one spare length) armoured, FRLS |
| 31 | 11 kV 3- Core XLPE 400 mm² armoured, FRLS |
| 32 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for incoming Cable |
| 33 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits for incoming Cable |
| 34 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for Outgoing Cable |
| 35 | 11 kV Outdoor Heat Shrinkable Cable Termination Kits for Outgoing Cable |
| 36 | Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant. |
| 37 | b). 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply . |
| 38 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
| 39 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 40 | Rubber Mat 1mx2m 19mm thick |
| 41 | Stand with 3 Sand Bucket & Fire Extingiusher |
| 42 | Safety helmet (insulated type) as per standard with latest amendments |
| 43 | Safety/ Industrial Helmet with Straps ISI Mark, with Head lamp Bracket and Detachable and Interchangeable LED Headlamp alongwith charger/charging facility. |
| 44 | Rubber Gloves for 33 kV level Class 2 or above |
| 45 | Rubber Gloves for 11kV level Class 2 or above |
| 46 | Safety Belt |
| 47 | Safety Shoes (Ankle Boot) |
| 48 | Earthing Discharge rod 5 mtr long with 25 sqmm cable 12 mtr |
| 49 | CCTV Complete(LED 32\\" with 06 No.AHD Cameras) alongwith necessary accessories |
| 50 | Alumunium Ladder 2*20 ' , 3 mm Thick (extendable with rope and pully arrangement) |
| 51 | Fire Extingiusher Co2 Type of 4.5 kg capacity for Control room building |
| 52 | Fire Extingiusher Co2 Type of 22.5 kg capacity (Trolley Type) |
| 53 | 9 Mtr. Long Pole (ST-410 SP33) |
| 54 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm |
| 55 | Red Oxide |
| 56 | Aluminium Paint |
| 57 | Anit Climbing device with clamps |
| 58 | Danger Plates |
| 59 | Cement bottoming 1:2:4 mix as per Standards 0.48 cum per pole |
| 60 | 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance320mm |
| 61 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting |
| 62 | 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. |
| 63 | Loading, Transportation, insurance, Unloading, Carriage from CSD Pampore and Delivery at Site including installation,Testing and Commissioning of 33/11KV 10 MVA Power Transformer complete job |
| 64 | Yard lighting of Sub Station using 4 No of 12m long GI Highmast poles continuously tapered of octagonal cross section, including suitable shallow raft foundation using 8 Nos non integral flood light luminary with single piece diecast aluminium housing and pot optic reflector with toughened glass cover confirming to IP 66, complete with all accessories along with input armoured cable of suitable size. |
| 65 | Outdoor type Marshalling Kiosk with IP 65/66 rating with arrangement for sufficient no. of input/output connection holes, canopy along with mounting arrangement Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysJul 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender