Defence Statutory Bodies & Commissions/Committees Closing in 18 days TDR #56328026

Tender For Repair/ Replacement Of Internal Wiring, Distribution Board, Light Fitting, Sub Main Wiring Including Fittings And Fixtures At Colaba, Cotton Green, Sion Area And Santacruz Los, Kalina And Old Airport Area At Af Stn Kalina Under Ge(Af)Thane

Issued by Statutory Bodies & Commissions/Committees · Thane, Maharashtra
Tender Value
21 Lakhs
Estimated cost
Bid Submission
25 Jul 2026
18 days left
EMD
42000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Thane → Maharashtra
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/ Replacement Of Internal Wiring, Distribution Board, Light Fitting, Sub Main Wiring Including Fittings And Fixtures At Colaba, Cotton Green, Sion Area And Santacruz Los, Kalina And Old Airport Area At Af Stn Kalina Under Ge(Af)Thane

BOQ

Name of Work:- REPAIR/ REPLACEMENT OF INTERNAL WIRING, DISTRIBUTION BOARD, LIGHT FITTING, SUB MAIN WIRING INCLUDING FITTINGS AND FIXTURES AT COLABA, COTTON GREEN, SION AREA AND SANTACRUZ LOS, KALINA AND OLD AIRPORT AREA AT AF STN KALINA UNDER GE(AF)THANE
Sl. No. Item Description
1Taking down carefully point wiring and removing from site such as (Light,fan socket or power) Complete including fitting and fixtures,fan regulators switch boards,switches,ceiling rose's lamp holder from existing batten PVC conduit/steel conduit / PVC casing and capping wiring complete excluding light fittings and fans all as specified and making good to the disturbed surfaces to match, complete all as specified and directed by Engineer-in-Charge.
2Taking down main Switches,MCB DB with MCBs complete all as specified and directed by Engineer-in-Charge.
3Taking down sub main wiring of any sizes complete all as specified and directed by Engineer-in-Charge.
4M & L for point wiring with FRLS insulated 1100 Volts grade single core multistranded Copper conductor cable 1.5 Sqmm drawn and including PVC casing capping and accessories, fixed on wall/ ceiling etc with necessary fixing accessories and earth continuity conductor cable of size 1.5 Sqmm green colour Connected to common earth dolly including pressed steel terminal boxes concealed in wall Covered with laminated sheet top cover of required thickness for mounting switches/ sockets/ fan regulators / bell push buttons etc fixed with cadmium plated machine screws and washers, complete all as specified and directed by Engineer-in-Charge for the following :-
5One light / fan/bell point controlled by one way switch
6One socket outlet 5 Amps on independent board
7One socket outlet 5 Amps on the same board
8All as per Sl item No 4 herein before but with 2.5 Sqmm for phase & neutral and 2.5 sqmm for earth wire for socket out let 15 Amps complete all as specified and directed by Engineer-in-Charge.
9All as per Sl item No 4 herein before but with 4 Sqmm for phase & neutral and 4 sqmm for earth wire for AC point independent 15 AMP complete all as specified and directed by Engineer-in-Charge.
10M & L for point wiring with FRLSinsulated 1100 Volts grade single core multistranded Copper conductor cable 1.5 Sqmm drawn and including PVC conduit and accessories, concealed in wall conduit on ceiling (for fan/downlighter only) etc with necessary fixing accessories and earth continuity conductor cable of size 1.5 Sqmm green colour Connected to common earth and earth dolly including pressed steel terminal boxes concealed in wall Covered with laminated sheet top cover of required thickness for mounting switches/ sockets/ fan regulators / bell push buttons etc fixed with cadmium plated machine screws and washers including making good the disturbed surface and painting the surface with color matching to the wall color complete all as specified and directed by Engineer-in-Charge for the following :-
11One light / fan/bell point controlled by one way switch
12One socket outlet 5 Amps on independent board
13One socket outlet 5 Amps on the same board
14All as per Sl item No 7 herein before but with 2.5 Sqmm for phase & neutral and 2.5 sqmm for earth wire for socket out let 15 Amps complete all as specified and directed by Engineer-in-Charge.
15All as per Sl item No 7 herein before but with 4 Sqmm for phase & neutral and 4 sqmm for earth wire for socket out let 15 Amps complete all as specified and directed by Engineer-in-Charge.
16Supply and Fix in repairs of Switch piano flush type single pole one way 5 Amp complete all as specified and directed by Engineer-in-Charge.
17Supply and Fix in repairs of Ceiling rose surface bakelite two to three terminal complete all as specified and directed by Engineer-in-Charge.
18Supply and Fix in repairs of Fan regulator electronic step type 240 V complete all as specified and directed by Engineer-in-Charge.
19Supply and Fix in repairs of Bell push flush type 5 Amps complete all as specified and directed by Engineer-in-Charge..
20Supply and Fix in repairs of Electronic Call Bell 230 volts single pole AC complete all as specified and directed by Engineer-in-Charge..
21Supply and Fix in repairs of Switch socket combined two in one 06 pin 5/15 Amps flush type universal complete all as specified and directed by Engineer-in-Charge.
22Supply and Fix in repairs of Switch Socket multipurpose 5 pin 5 Amps 240 V flush type complete all as specified and directed by Engineer-in-Charge.
23Supply and Fix in repairs of Lamp holder,insulated body with back plate complete all as specified and directed by Engineer-in-Charge.
24M&L MCCB DB verticle type made of sheet steel , powder painted with neutal bus bar 200 A, neutral link, IP-30-IK08 protection grade , 415Volts TPN with 8 way Double door complete all as specified and directed by Engineer-in-Charge.
25M&L MCCB DB verticle type made of sheet steel , powder painted with neutral bus bar 200 A, neutral link, IP-30-IK08 protection grade , 415Volts TPN with 4 way Double door complete all as specified and directed by Engineer-in-Charge.
26M&L MCCB TPN 100 Amps , 415Volts, 25KA ,3 Pole complete all as specified and directed by Engineer-in-Charge.
27M&L MCCB TPN 160 Amps , 415Volts, 25KA ,3 pole complete all as specified and directed by Engineer-in-Charge.
28Supply and Fix in repairs of MCB DB SPN 8 Way Double door type 240 Volts complete all as specified and directed by Engineer-in-Charge.
29Supply and Fix in repairs of MCB DB TPN 4 Way double door type 415 V with bus bar complete all as specified and directed by Engineer-in-Charge.
30Supply and Fix in repairs single pole and neutral enclouser with a two pin and earth and metal clad plug socket complete with one single pole MCB 25 Amp 240 Volts complete all as specified and directed by Engineer-in-Charge.
31Supply and Fix in repairs of MCB TPN 63 Amps 415 Volts complete all as specified and directed by Engineer-in-Charge.
32Supply and Fix in repairs of MCB SP 06 to 32 Amps 240 Volts complete all as specified and directed by Engineer-in-Charge.
33Supply and Fix in repairs of SPN 6- 32 Amps 240 Volts complete all as specified and directed by Engineer-in-Charge.
34Supply and Fix in repairs of MCB SPN 40 Amps 240 Volts complete all as specified and directed by Engineer-in-Charge.
35Supply and Fix in repairs of MCB SPN 63 Amps 240 Volts complete all as specified and directed by Engineer-in-Charge. NOTE FOR ITEM NO 18 to 29 -(1).The unit rate includes for cutting the brick walls to accommodate DB to make flush to wall./ DB tobe fixed on wall including frame made out of MS flat 40x5mm(2).The unit rate includes for making good the disturbed surfaces including finishes to match with the adjoining surface
36M&L in repair for Sub Main wiring with two single core 4 Sqmm FRLS insulated multistranded flexible copper conductor cable 660/1100 volts grade drawn in through rigid flexible PVC casing -n- caping/PVC conduit with and including PVC insulated 2.5 Sqmm single core multi strand copper conductor as continuous earth wire in green colour connected to common earth dolly complete all as specified and directed by Engineer-in-Charge.Note:- 1. Two runs of cable and one run of earth wire incl PVC conduit will be measured and paid one unit. 2. Separate sub main wiring will be run for each accn
37M&L for Sub Main wiring complete with 6.0 Sqmm FRLS insulated 1100 Volt grade with multistranded copper conductor cable with and including drawn through PVC casing -n- caping/PVC conduit with all accessories fixed on Walls/floors/roofs with and including pressed steel terminal sunken boxes fixed on the existing sunken portion (Where the old boxes are removed under respective item) with 3 mm laminated bakelite sheet top cover fixed with cadmium plated screws,cup washer for housing metal clad plug socket for AC Point including provision of 4 sqmm PVC insulated copper wire as earth continuity conductor and connecting to common earth dolly complete all as specified and directed by Engineer-in-Charge.
38All as per item No.30 herein before but with 6 Sqmm PVC insulated FRLS multistranded flexible copper conductor cable drawn in through PVC casing -n- caping/PVC conduit complete with all accessories including provision of 6.0 sq mm FRLS insulated copper wire as earth continuity conductor all complete all as specified and directed by Engineer-in-Charge.
39S&F energy efficient light emmitting LED light fitting 1x 18/20 watt, four feet , white fittings with LED rod complete with all accessories & Provn of three core cable of copper conductor of size 0.75 sqmm, making necessary electric connetion from ceiling rose to fitting terminal , fixing the fitting on wall including all necessary fixing accessories complete all as specified and directed by Engineer-in-Charge.
40S&F for energy efficient light emmitting LED light fitting 1x10 watt Two feet LED tube light with LED rod complete with all accessories & Provn of three core cable of copper conductor of size 0.75 sqmm, making necessary electric connetion from ceiling rose to fitting terminal , fixing the fitting on wall including all necessary fixing accessories complete all as specified and directed by Engineer-in-Charge.
41S&F in Repairs LED Light luminaries Square type 36W suitable suitable for Modular/pop/Gypsum ceiling with starter, connector block, etc,complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible conductor of copper with PVC square blocks of size 600mmX600mm for fixing the fittingcomplete complete all as specified and directed by Engineer-in-Charge.
42M & L for Earth recharger/Earth resistance reducing compound of 6 KG per buckets comprising of ion and catalyser for reduction of earth resistance as well as retaining moisture in the earth pit with certified( ERDA, NABL, ROHS, IS3043, IEEE IS RULES) and without corroding the earth pit material suitable for all type of earth pit complete all as specified and directed by Engineer-in-Charge.Note-(a) Percentage reduction of earth resistance should be min 70 Percentage (b) Earth resistance value should be retain atleast 1.5 years.(c) contractor will submit earth resistance value before and after utilization of material. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56328026
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 21 Lakhs
LAST DATE 25-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/ Replacement Of Internal Wiring, Distribution Board, Light Fitting, Sub Main Wiring Including Fittings And Fixtures At Colaba, Cotton Green, Sion Area And Santacruz Los, Kalina And Old Airport Area At Af Stn Kalina Under Ge(Af)Thane
Basic Detail
Tender No GE (AF) T-07 OF 2026-27 (8615)
Bidding Type Tender
Location
City Thane
State Maharashtra
Key Dates
Publish Date 06 Jul 2026
Submission Date 25 Jul 2026
Open Date 01 Aug 2026
Finance
Tender Value 21 Lakhs
Tender Fee 500
EMD 42000
Exemption Available
Document List
Tendernotice_1 (2).pdf
8ce0a714-d916-4058-915f-ffdcc3c93e39.html
BOQ_869753.xls
TD8615.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 25, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 18 days
Aug 01, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 25 days

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1 (2).pdf

html

8ce0a714-d916-4058-915f-ffdcc3c93e39.html

xls

BOQ_869753.xls

pdf

TD8615.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders