Defence Statutory Bodies & Commissions/Committees Closing in 18 days TDR #56325666

Tender For special Repair Of Lt Overhead Line Into Underground Cable And special Repair Of Gang Operated Devices, Lightning Arrestor And 2 Pole Structure At Haws Gulmarg Under Ge 969 Ews.

Issued by Statutory Bodies & Commissions/Committees · Baramulla, Jammu and Kashmir
Tender Value
36.40 Lakhs
Estimated cost
Bid Submission
27 Jul 2026
18 days left
EMD
72800
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for special Repair Of Lt Overhead Line Into Underground Cable And special Repair Of Gang Operated Devices, Lightning Arrestor And 2 Pole Structure At Haws Gulmarg Under Ge 969 Ews.

BOQ

Name of Work:- SPL REPAIR OF LT OVERHEAD LINE INTO UNDERGROUND CABLE AND SPL REPAIR OF GANG OPERATED DEVICES, LIGHTNING ARRESTOR AND 2 POLE STRUCTURE AT HAWS GULMARG UNDER GE 969 EWS.
Sl. No. Item Description
1S&F Steel tubular swaged poles complete with MS base plate Continuously welded to pole, finial taper plug, bolts, nuts & screws as specified type 410 SP- 55 (11 metres long ) includind two coat of black bituminous paint internally throughout and externally upto embedded portion and including applying two coats of synthetic enamel paint over a coat of red oxide primer with black and white strip of 30 cm each upto 1.5 m height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface aftereraction in position incl prepration of surface, incl dismantling of existing PCC or steel tubular pole, complete all as specified and as directed. (4 Pole Structure)
2Excavation in trenches n exc 1.5 m wide & n exc 1.5 mtr deep in depth for foundation, etc or for shafts, wells, cesspits, manholes, pier holesetc not exc 10 sqm on plan and n exc 1.5 mtr in depth and getting out of Hard/dense soil, complete all as specified and as directed.
3M & L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 using 40 mm graded aggregate, complete all as specified and as directed.
4M & for cement concrete for coping of poles using B1 1:2:4, 20 mm graded aggregate, smooth finishing without using extra cement, complete all as specified and as directed..
5M & for cement concrete for foundation fillings and mass conctere type C2 1:3:6 using 40 mm graded aggregate, complete all as specified and as directed.
6M&L for Lighting arresters expulsion type complete with all fittings transmission class, discharge capacity 65KA suitable for 11000 volts, complete all as specified and as directed.
7Supply and fix HT 11 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting rotating type complete with 12 insulators of rating upto 400 Amps includes of GI pipe required for operation with handle, complete all as specified and as directed.
8Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm, complete all as specified and as directed.
9Supply and laying GI pipe 80mm dia light grade for cable protection on HT cable , complete all as specified and as directed.
10S & F in repair cross arms bracing supports, MS Channels, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide zinc chrome, one under coat and one finishing coat of aluminum paint, complete all as specified and as directed.
11Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE,armoured, Al conductor cable of size 50 sqmm to 95 sqmm, complete all as specified and as directed.
12Supply & Fix LT End termination Joint 1100 V Grade with lugs suitable for XLPE cable Of size 6 to 16 x 4core, complete all as specified and as directed.
13Supply & Fix LT End termination Joint 1100 V Grade with lugs suitable for XLPE cable Of size 25 to 50 Sqmm 4/3.5 core, complete all as specified and as directed.
14Supply & Fix LT End termination Joint 1100 V Grade with lugs suitable for XLPE cable Of size 70 to 95 sqmm 4/3.5 core, complete all as specified and as directed.
15M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 25x20cm size, complete all as specified and as directed.
16S & F Pin type, porcelain, vitreous, brown insulator including one galvanised mild steel spindle, two galvanised washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade LT over head line and including taking down old, complete all as specified and as directed.
17M&L for shackle type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, 75 mm height, 90 mm dia for 1100 volts grade including dismantling /disconnecting & taking down old broken and unserviceable insulaters of any size & capacity, complete all as specified and as directed.
18M&L for shackle type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, 100 mm height, 115 mm dia for 1100 volts grade including dismantling /disconnecting & taking down old broken and unserviceable insulaters of any size & capacity, complete all as specified and as directed.
19M&L for stay assembly complete with accessories as shown in electrical plate No 1 (Loop type insulator, stay clamps excavation and concrete measured separately) 20mm dia including dismentling old and unsv stay assy complete comprising of stay clamp, stay wire, stay insulator, stay grip, thimble, bow, stay rod and stay plate etc including breaking of cement concrete including taking down old one, complete all as specified and as directed.
20M & L for Loop type insulator, vitreous porcelain brown or green insulator Large size, with overall dimensions 90mmx140mm, clearance of hole 25.5mm including taking down old one, complete all as specified and as directed.
21Dismantling /disconnecting & taking down insulaters of any size & capacity., complete all as specified and as directed.
22Supply & Fixing lugs or thimbles suitable for 10 Sqmm to 70 sqmm aluminum coductor cable suitable 1100 volts LT Cable, complete all as specified and as directed.
23Supply & Fixing Lugs or thimbles suitable for 95 Sqmm to 240 sqmm aluminum coductor cable suitable 1100 volts LT Cable, complete all as specified and as directed.
24Supply and fixing LT Cable Marker Made up of 6 mm MS Sheet 10 CM dia welded with 6 mm 1 mtr length angle iron duly coated red oxide and two coats of red enamel paint written as \\"LT MES\\" irrected by 1:2:4 PCC foundation 50 cm below ground level , complete all as specified and as directed.
25Painting to existing steel tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coats of aluminum paint superior quality of approved make on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including preparation of old painted surfaces by scraping etc complete and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified & directed.
26M&L Electrical Insulation Safety Rubber Mat Class \\"B\\" AC 11 KV, 2.5 cm Thickness as per IS 15652-2006, Size 1 x 2 mtr Length, complete all as specified and as directed.
27Dismantling of ACSR or AAC conductor from pole of any size and capacity, complete all as specified and as directed.
28Dismantling of cross arms and MS chanel or angle section etc complete all as specified and directed.
29Dismantling /disconnecting & taking down insulaters of any size & capacity, complete all as specified and as directed.
30Excavation in trenches in soft loose soil including cutting road surfaces n.exc 1.5 mtrs wide and n.exc 1.5 mtr. in deep for foundation of poles, stays, cables pipe etc and getting out, complete all as specified and as directed.
31Returning filling in, of excavated soil in trenches incl spreading, leveling, watering and well ramming in layers each layers n.exc 25cm thick in soft/loose soil, complete all as specified and as directed.
32Removal surplus spoil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above the starting point, complete all as specified and as directed.
33Supply and spread river sand to required width at bottom and top for cable cushioning all as specified in clause 19.75 of SSR part – I (Note :- thickness of sand will be measured after punning)
34Supply and lay common burnt bricks of sub class B old size laid at right angle on the cable complete in trenches for cable protection, complete all as specified and as directed.
35Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 240 Sqmm 3.5 core , complete all as specified and as directed.
36Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 120 Sqmm 3.5 core, complete all as specified and as directed.
37Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 95 Sqmm 3.5 core, complete all as specified and as directed.
38Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 50 Sqmm 3.5 core, complete all as specified and as directed.
39Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 35 Sqmm 3.5 core, complete all as specified and as directed.
40Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 25 Sqmm 2 core, complete all as specified and as directed.
41Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 16 Sqmm 2 core complete all as specified and directed.
42Supply, laying, jointing and testing LT XLPE and PVC insulated, screened, armoured, LT elctric power cables (heavy duty) with aluminium conductor, 1100 Volts Grade conforming to IS-1554 laid in trenches, pole,road crossing walls, floor etc. cross sectional area of 10 Sqmm 2 core, complete all as specified and as directed.
43M&L, GI pipe Medium grade 80 mm dia bore for cable protection fixed to pole or under road/ pavement, complete including MS clamps, nuts, bolts etc, complete all as specified and as directed.
44Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 187.5 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(MI ROOM)
45(a) INCOMING
46(i) MCCB 4 Pole 415 volts grade 125 Amps rating and 36 KA rupturing capacity - 01 No
47(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
48(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
49(iv) CTs ratio 100/5A class ISI marked sets of three each
50(v) Indicating lamp-01 set of three
51(b) OUTGOING
52(i) MCB Double Pole 40 Amp - 04 Nos
53(ii) MCB Double Pole 32 Amp - 08 Nos
54(iii) Spare Slots -05
55Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(NON CSD)
56(a) INCOMING
57(i) MCCB 4 Pole 415 volts grade 250 Amps rating and 36 KA rupturing capacity - 01 No
58(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
59(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
60(iv) CTs ratio 100/5A class ISI marked sets of three each
61(v) Indicating lamp-01 set of three
62(b) OUTGOING
63(i) MCCB 4 pole 415 volts grade 125 Amps rating and 36 KA rupturing capacity -01 No
64(ii) MCCB 4 pole 415 volts grade 100 Amps rating and 36 KA rupturing capacity -01 No
65(iii) MCB Double pole 40 AMP - 01 Nos
66(iv) MCB Double pole 32 AMP - 08 Nos
67(v) MCB Double pole 20 AMP - 04 Nos
68(vi) Spare Slots -05
69(vii) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 250 Amps.
70Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 150 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :- (STN HQ)
71(a) INCOMING
72(i) MCCB 4 Pole 415 volts grade 100 Amps rating and 36 KA rupturing capacity - 01 No
73(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
74(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
75(iv) CTs ratio 100/5A class ISI marked sets of three each
76(v) Indicating lamp-01 set of three
77(b) OUTGOING
78(i) MCB Double pole 63 AMP - 02 Nos
79(ii) MCB Double pole 40 AMP - 03 Nos
80(iii) MCB Double pole 32 AMP - 03 Nos
81(iv) Spare Slots -05
82(v) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 100 Amps.
83Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 240 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(O'Mess)
84(a) INCOMING
85(i) MCCB 4 Pole 415 volts grade 160 Amps rating and 36 KA rupturing capacity - 01 No
86(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
87(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
88(iv) CTs ratio 100/5A class ISI marked sets of three each
89(v) Indicating lamp-01 set of three
90(b) OUTGOING
91(i) MCB Double pole 40 AMP - 04 Nos
92(ii) MCB Double pole 20 to 32 AMP - 10 Nos
93(iii) Spare Slots -05
94(iv) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 160 Amps.
95Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 100 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(OR Living)
96(a) INCOMING
97(i) MCCB 4 Pole 415 volts grade 63 Amps rating and 25 KA rupturing capacity - 01 No
98(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
99(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
100(iv) CTs ratio 100/5A class ISI marked sets of three each
101(v) Indicating lamp-01 set of three
102(b) OUTGOING
103(i) MCB DP 20 TO 32 AMP - 08 Nos
104(ii) Spare Slots -05
105Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 100 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(MT)
106(a) INCOMING
107(i) MCCB 4 Pole 415 volts grade 63 Amps rating and 25 KA rupturing capacity - 01 No
108(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
109(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
110(iv) CTs ratio 100/5A class ISI marked sets of three each
111(v) Indicating lamp-01 set of three
112(b) OUTGOING
113(i) MCCB TPN 63 AMP 16 KA - 08 Nos
114(ii) MCB DP 20 TO 32 AMP - 08 Nos
115(iii) Spare Slots -05
116Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT panel board (PH front side) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bar 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of 3.15mm CRCA MS sheet and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following :-(NON CSD)
117(a) INCOMING
118(i) MCCB 4 Pole 415 volts grade 350 Amps rating and 36 KA rupturing capacity - 01 No
119(ii) Digital Voltmeter 0-500 volts, Square 96 mm, flnsh pattern with 3 way rotary selector switch-01 No
120(iii) Digital Ammeter size 96 mm, square dial flush pattern having dual range 0-600 Amps with three way rotary selector switch -01 No
121(iv) CTs ratio 100/5A class ISI marked sets of three each
122(v) Indicating lamp-01 set of three
123(b) OUTGOING
124(i) MCCB 4 Pole 415 volts grade 63 Amps rating and 25 KA rupturing capacity - 02 No
125(ii) MCCB 4 pole 415 volts grade 200 Amps rating and 36 KA rupturing capacity -01 No
126(ii) MCCB 4 pole 415 volts grade 100 Amps rating and 36 KA rupturing capacity -01 No
127(iii) MCB Double pole 40 AMP - 01 Nos
128(iv) MCB Double pole 32 AMP - 08 Nos
129(v) MCB Double pole 20 AMP - 04 Nos
130(vi) Spare Slots -05
131(vii) ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 350 Amps.
132M & L Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion using galvanised iron strip 32×6mm as earthing lead complete all as specified and directed.ncluding earthing pit in PCC (1:3:6) type C1 for chamber & Pre-cast RCC cover of size 380 x 380 x 40 mm with one handle made out of 8 mm dia round bar, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work as Exc, R&F & removal etc complete.
133Note:- Schedule of credit Rs 57,310.00 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56325666
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 36.40 Lakhs
LAST DATE 27-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for special Repair Of Lt Overhead Line Into Underground Cable And special Repair Of Gang Operated Devices, Lightning Arrestor And 2 Pole Structure At Haws Gulmarg Under Ge 969 Ews.
Basic Detail
Tender No CA NO 969 WS- /2026-27
Bidding Type Tender
Location
City Baramulla
State Jammu and Kashmir
Key Dates
Publish Date 06 Jul 2026
Submission Date 27 Jul 2026
Open Date 29 Jul 2026
Finance
Tender Value 36.40 Lakhs
Tender Fee 500
EMD 72800
Exemption Available
Document List
7365c969-38e4-4b3c-b649-e03af615ec26.html
Tendernotice_1 (2).pdf
BOQ_869727.xls
TENDER.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 27, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 18 days
Jul 29, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 20 days

Tender Documents

Download All (ZIP) ↓
html

7365c969-38e4-4b3c-b649-e03af615ec26.html

pdf

Tendernotice_1 (2).pdf

xls

BOQ_869727.xls

pdf

TENDER.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders