Tender For Repair/ Maintenance Of Old Lt Switch Gears, Feeder Pillar Boxes And Lt Cables Including Connected Items Under Ge (West) Colaba, Mumbai
Tender Value
45 Lakhs
Estimated cost
Bid Submission
27 Jul 2026
6 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mumbai → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/ Maintenance Of Old Lt Switch Gears, Feeder Pillar Boxes And Lt Cables Including Connected Items Under Ge (West) Colaba, Mumbai
BOQ
| Sl. No. | Item Description |
| 1 | Excavating in trenches, n.exc1.5 m wide and n exc 1.5 m indepth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. nexc 10 sq m on plan and n exc 1.5 m in depth and getting out complete in soft/loose soil, complete all as specified and directed. |
| 2 | All as per item No.01 above but in hard/dense soil. |
| 3 | Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 in depth for foundation of poles, stay assembly and laying of U/G cables etc. and getting out in hard rock/road cutting/RCC/PCC, complete all as specified and directed. |
| 4 | Returning, filling in soft/loose soil including spreading, levelling, watering, well ramming in layers n.exc 25 cm, complete all as specified and directed. |
| 5 | Removing of excavated material not exc 50m away from starting point and depositing where directed at a level not exc. 1.5m above the starting point in soft /loose soil, complete all as specified and directed. |
| 6 | Removing of excavated material from the site of work and transporting out of MD land, complete all as specified and directed. |
| 7 | Supply and providing unreinforced pre cast cement concrete cable cover for cable protection (Ready made Covers) of sizes Class LV type I, flat size 250x150x40 mm putting adjecent to each other, complete all as specified and directed. |
| 8 | Supply and laying tubes light grade, galvanized, 100 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable, complete all as specified and directed. |
| 9 | Supply and laying tubes light grade, galvanized, 80 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable, complete all as specified and directed. |
| 10 | Supply and laying tubes light grade, galvanized, 50 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable, complete all as specified and directed. |
| 11 | Supply and laying tubes light grade, galvanized, 40 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable, complete all as specified and directed. |
| 12 | M&L cement concrete 1:2:4 type B-1 using 20mm graded aggregate in width for Feeder panel foundation/road filling including including rafts, footings, foundation beams plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete, complete all as specified and directed. |
| 13 | Taking down/ dismantling carefully old UNSV feeder panel by discoonecting all connected cables and reconnecting same cables with new feeder panels, complete all as specified and directed. |
| 14 | Material & Labour for cable fault detection at various locations by all T & P, Equipments for HT CABLE XLPE aluminium conductor from feeder panel to feeder panel including testing and commissioning, complete all as specified and directed. |
| 15 | Material & Labour for cable fault detection at various locations by all T & P, Equipments for LT CABLE XLPE aluminium conductor from feeder panel to feeder panel including testing and commissioning, complete all as specified and directed. |
| 16 | Material & Labour for cable route detection at various locations by all T & P, Equipments for LT CABLE XLPE aluminium conductor from feeder panel to feeder panel including testing and commissioning, complete all as specified and directed. |
| 17 | Taking down for old UNSV cable from trench/wall/duct, complete all as specified and directed. |
| 18 | Supplying, laying, commissioning & testing LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty, armoured with multi-stranded aluminium conductor all as per IS 7098 (Part -1) laid in trenches, ducts, drawn through pipes or fixed on poles, as and when required on ground of following sizes:- 300 Sqmm X 3.5 Core. |
| 19 | All as per item No 18 but for cable size 240 Sqmm X 3.5 Core. |
| 20 | All as per item No 18 but for cable size 150 Sqmm X 3.5 Core. |
| 21 | All as per item No 18 but for cable size 120 Sqmm X 3.5 Core. |
| 22 | All as per item No 18 but for cable size 95 Sqmm X 3.5 Core. |
| 23 | All as per item No 18 but for cable size 70 Sqmm X 3.5 Core. |
| 24 | All as per item No 18 but for cable size 50 Sqmm X 3.5 Core. |
| 25 | All as per item No 18 but for cable size 35 Sqmm X 3.5 Core. |
| 26 | All as per item No 18 but for cable size 25 Sqmm X 3.5 Core. |
| 27 | All as per item No 18 but for cable size 16 Sqmm X 4 Core. |
| 28 | All as per item No 18 but for cable size 16 Sqmm X 2 Core. |
| 29 | Material & Labour for cable jointing kit, in repairs for LT CABLE XLPE aluminium conductor including testing and commissioning complete for the size of 35sqmm X 3.5 Core, complete all as specified and directed. |
| 30 | All as above item No -29 but of size 50sqmm X 3.5 Core. |
| 31 | All as above item No -29 but of size 70sqmm X 3.5 Core. |
| 32 | All as above item No -29 but of size 95sqmm X 3.5 Core. |
| 33 | All as above item No -29 but of size 120sqmm X 3.5 Core. |
| 34 | All as above item No -29 but of size 185 sqmm X 3.5 Core. |
| 35 | All as above item No -29 but of size 240sqmm X 3.5 Core. |
| 36 | All as above item No -29 but of size 300sqmm X 3.5 Core. |
| 37 | Taking out/down for old cable and rerouting, re laying, saddling the same after checking, meggaring complete LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty of size 10 sqmm X 2 Core to 50sqmm X 3.5 Core including connecting up electric power to panel/feeder box, complete all as specified and directed. |
| 38 | Taking out/down for old cable and rerouting, re laying, saddling the same after checking, meggaring complete LT underground cables, 1100 Volts grade, XLPE insulated, PVC sheathed heavy duty of size 70 sqmm X 3.5 Core to 240 sqmm X 3.5 Core including connecting up electric power to panel/feeder box, complete all as specified and directed. |
| 39 | Dismantling of Damaged/Burnt Change Over Switch and Supply & fixing of Change Over Switch, 4Pole, 250 Amps, Open Execution (Open Enclosure), ON LOAD type 415Volts, 50Hz AC including enclosure, complete all as specified and directed by Engr-in-charge. |
| 40 | Dismantling of Damaged/Burnt Change Over Switch and Supply & fixing of Change Over Switch, 4Pole, 250 Amps, Open Execution (Closed Enclosure), ON LOAD type 415Volts, 50Hz AC including enclosure, complete all as specified and directed by Engr-in-charge. |
| 41 | Dismantling of Damaged/Burnt Change Over Switch and Supply & fixing of Change Over Switch, 4Pole, 320/400 Amps, Open Execution (Open Enclosure), ON LOAD type 415Volts, 50Hz AC including enclosure, complete all as specified and directed by Engr-in-charge. |
| 42 | Dismantling of Damaged/Burnt Change Over Switch and Supply & fixing of Outdoor Change Over Switch, 4Pole, 320/400 Amps, Open Execution (Closed Enclosure),ON LOAD type 415Volts, 50Hz AC including enclosure, complete all as specified and directed by Engr-in-charge. |
| 43 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 4Pole, 320/400 Amps, 35/36kA, 415Volts, 50Hz AC s with enclosure of 2.00 mm thick for indoor S/S fixing on wall, complete all as specified and directed by Engr-in-charge. |
| 44 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 4Pole, 250 Amps, 35/36kA, 415Volts, 50Hz AC s with enclosure of 2.00 mm thick for indoor S/S fixing on wall, complete all as specified and directed by Engr-in-charge. |
| 45 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 4Pole, 320/400 Amps, 35/36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 46 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 4Pole, 250 Amps, 35/36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 47 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 4 Pole, 200 Amps, 35/36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 48 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 200 Amps, 35/36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 49 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 160 Amps, 36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 50 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 100 Amps, 36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 51 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 100 Amps, 10kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 52 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 63 Amps, 36kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 53 | Dismantling of Damaged/Burnt MCCB and Supply & fixing of MCCB, 3Pole, 63 Amps, 10kA, 415Volts, 50Hz AC, complete all as specified and directed by Engr-in-charge. |
| 54 | Material & Labour for repairs/ Overhauling/Servicing to Existing LT electric panels by taking shut down from appropiate authority including T&P for Attending Faults/Trippings and rectifieng /repairing the faults in HT/LT Panels Boards/ Capacitor Panels Boaeds/ MCCB's/ACB's /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut bolts and all as specified and directed by Engineer-In-Charge. (i) Tightning the loose connections and cleaning inside/out side complete replacing faulty insulation, thimbles and lugs as per the size of existing cable, applying petrolium jelly on the contactors ,providing new insulation tape to bus bars, repair to broken /hanging doors by fixing hinges or welding the door to make it servicable, spray painting as pproved colour and testing the entire panel board after the completion of servicing up to the satisfication of Engr-in-charge complete all as specified and directed. (Note : MCCB,ACB, Painting measured and paid separately under relevant items of this schedule.) |
| 55 | Dismantling/Maintenance of Old Damaged/burnt spare parts from ACB and Supply and fixing in repair of following Spare parts suitable for -ACB 415V, 630 to 1200Amps Amps indoor type of Make ; Havells/ Schneider/L&T/Legrand/C&S all as specified and directed by Engineer-in-Charge. |
| 56 | Shunt Trip Device |
| 57 | Closing coil assembly |
| 58 | Mismatch Prevention Device |
| 59 | Moving contacts assembly |
| 60 | Fixed Contact assembly |
| 61 | Auxiliary Switch |
| 62 | Arc chut with hardware |
| 63 | Current Transformers 300A/5A |
| 64 | Current Transformers 630A/5A |
| 65 | Current Transformers 800A/5A |
| 66 | Current Transformers 1200A/5A |
| 67 | Dismantling of old damaged Meters and Supply & fix Digital LT voltmeter with selector switch of size 96x 96mm rating 0 to 500 volt, complete all as specified and directed. Make: AE/MECO/ Elmeasure. |
| 68 | Dismantling of old damaged Meters Supply & fixing Digital LT Ammeter with selector switch of size 96x 96mm suitable for CT ratio 5amp, programmable type, complete all as specified and directed. Make: AE/MECO/ Elmeasure. |
| 69 | Cleaning the vegetation including glass, bushes small trees and all vegetation growth complete including digging out the root of bushes and small trees around the feeder panel. filling the rough holes with earth and levelling the surfaces by removing all debris outside MD land, complete all as specified and directed. |
| 70 | M & L for Painting with of LT panels/ LT feeder panels of any size and type including one coat of primer paint all including scrapping out the old paint by scrubbing and application of primer before double coat of paint including minor repair like welding of hinges, repairing of lock and key arrangements, complete all as specified and directed by Engineer - in - Charge. |
| 71 | Material and Labour for Attending Faults/Trippings and rectifieng /repairing the faults in LT Panels Boards/Capacitor Panels Boaeds/ MCCB's/ACB's /Change Over switches/Cable Connections/Bus Bar etc including PVC insulating Tapes/Nut bolts, complete all as specified and directed by Engineer-In-Charge. Note : Damaged/Burnt MCCB/ACB'S/Changeover switc/Lugs.will be measured and paid separately) |
| 72 | Dismantling of Damaged/Burnt out lugs and Supply & fixing of Aluminum Lugs with PVC Insulation Tape of size 185 Sqmm to 400 Sqmm, complete all as specified and directed by Engr-in-charge. |
| 73 | Dismantling of Damaged/Burnt out lugs and Supply & fixing of Aluminum Lugs with PVC Insulation Tape of size 16 Sqmm to 150 Sqmm, complete all as specified and directed by Engr-in-charge. |
| 74 | Supply & fixing Aluminium Bus Bar strips, of any size, for extention of MCCB terminals for cable terminations, inside the cable alley of LT panel board, duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size, complete all as specified and as directed.Note :- (a) Size of the strip shall be determined depending upon the current carrying capacity of the individual outgoing MCCBs. (b) Overall length of the strip shall be measured and paid after necessary conversion into weight. (c) Cost of drilling / bending / Grinding of the strips at site as required shall be included in the unit rate quoted. |
| 75 | Supply & fixing Copper Bus Bar strip, of any size, for extention of MCCB terminals for cable terminations, inside the cable alleoy of LT panel board, duly supported on the FRP / DMC support insulators including necessary drilling / bending to obtain required shape and size, complete all as specified and as directed.Note :- (a) Size of the strip shall be determined depending upon the current carrying capacity of the individual outgoing MCCBs. (b) Overall length of the strip shall be measured and paid after necessary conversion into weight. (c) Cost of drilling / bending / Grinding of the strips at site as required shall be included in the unit rate quoted. |
| 76 | Supply and fixing of suitable type and size FRP / DMC bus bar support insulator (Bridge Insulator) for fixing the extended aluminium bars, for cable terminations, duly fixed in the body of the panel board by and including galvanized steel bolts, nuts, washers etc.and necessary drillings, in the panel body, complete all as specified and directed. |
| 77 | Dismantling of Damaged/Burnt out control wiring of LT panels/ feeder panels and Supply & fixing of new control wiring of panels of any size with PVC Insulation Tape including all indicating lamps, complete all as specified and directed by Engr-in-charge. |
| 78 | S&F in repairs steel perforated cable trunking system of size 60X30 mm and providing sturdy nuts and bolts for connecting cable trunking steadily onto walls or lying in air steadily with help of metal frame, complete all as specified and directed. |
| 79 | S&F in repairs PVC cable trunking system of size 60X30 mm and providing sturdy nuts and bolts for connecting cable as per requirment on site including necessary fixing arrangement, complete all as specified and directed. |
| 80 | M & L for Earthing complete with GI earth plate electrode 60 cm X 60 cm X 6 mm thick, burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.50 mtr below normal ground level connected to GI earth lead strip 25 x 4 mm dia by means of GI bolts, nuts, check nuts, washers made out of GI/steel, all as shown on electrical plate No3 of MESschedule part-I, earth lead strip connected to indicated position including concrete pit in PCC (1:3:6, C-1), Precast RCC cover slab 55 cm x 55 cm x 5 cm with reinforcement of 8 mm dia bar 100 mm c/c bothways including one handle made of 12 mm dia MS bar embedded in pre cast slab and 20 mm bore galvanised iron pipe\\"medium grade\\" for watering with GI funnel and wire mess including charcoal and salt in alternate layers of 15 cm including necessary excavation and earth work in any type of soil, complete all as specified and as directed and testing on completion.Note: Meggering Value of earthing resistance should be less than 2 Ohm. |
| 81 | Supply & Fix earth continuty conductor fixed to wall/surface or recess or burried in ground or any situation for loop earthing by 25 X 4 mm GI strip, complete all as specified and directed by Engineer-in-Charge. |
| 82 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 83 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse (for Isolation), 415 V- 02 Nos(b ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y,B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 160 amps, 36 KA, 415 V- 01 No(b) Thermal Protection MCCB 3 pole 100 amps, 36 KA, 415 V- 06 No(c) Thermal Protection MCCB 3 pole 63 amps, 25 KA, 415 V- 02 No |
| 84 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking down old. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 85 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse(for Isolation) 315A ,415 V- 02 Nos (b ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 160 amps, 36 KA ,415 V- 01 No (b) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 02 No (c) Thermal Protection MCCB 3 pole 63 amps, 25 KA ,415 V- 04 No (d) Street Light Digital Time Switch - 01 No(e) Power contactor 3 pole AC 3 rating 32 A - 01 No |
| 86 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 87 | INCOMING(a) Changeover Switch 4 pole, 415 Volts, 320 Amps, 36 KA 415 V- 01Nos (b) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 01 Nos (c ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(d) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(e) R,Y,B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 160 amps, 36 KA ,415 V- 02 No (b) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 02 No (c) Thermal Protection MCCB 3 pole 63 amps, 36 KA ,415 V- 02 No (d) MCB 2 pole, 240 Volts, 40 Amps - 6 No. |
| 88 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 89 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse(for Isolation) ,415 V- 02 Nos (b ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 4 pole 250 amps, 36 KA ,415 V- 02 No (b) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 05 No |
| 90 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 91 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse(for Isolation) ,415 V- 02 Nos (b ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 03 No (b) Thermal Protection MCCB 3 pole 63 amps, 36 KA ,415 V- 03 No (c) Street Light Digital Time Switch - 01 No(d) Power contactor 3 pole AC 3 rating 32 A - 01 No |
| 92 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 93 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse(for Isolation) ,415 V- 02 Nos (b ) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 4 pole 250 amps, 36 KA ,415 V- 02 No (b) Thermal Protection MCCB 3 pole 200 amps, 36 KA ,415 V- 02 No (b) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 02 No (c) Thermal Protection MCCB 3 pole 63 amps, 36 KA ,415 V- 02 No (d) Street Light Digital Time Switch - 01 No(e) Power contactor 3 pole AC 3 rating 32 A - 01 No |
| 94 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands. the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 95 | INCOMING(a) Thermal Protection MCCB 4 pole, 415 Volts, 320 Amps, 36 KA with HRC Fuse (for Isolation) ,415 V- 02 Nos (b) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 160 amps, 36 KA ,415 V- 01 No (b) Thermal Protection MCCB 3 pole 100 amps, 36 KA ,415 V- 04 No (c) Thermal Protection MCCB 3 pole 63 amps, 36 KA ,415 V- 04 No |
| 96 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 500 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 97 | INCOMING(a) Changeover Switch 4 pole, 415 Volts, 400 Amps, 36 KA 415 V- 01Nos (b) Thermal Protection MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 Nos (c) Volt meter (digital type) 0-500 volts with selector switch - 01 No(d) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(e) R,Y B Indicator lamp LED type - 01 SetOUTGOING(a) Thermal Protection MCCB 3 pole 100 amps, 36 KA, 415 V- 01 No (b) Thermal Protection MCCB 3 pole 63 amps, 36 KA, 415 V- 01 No (c) MCB TPN, 415 Volts, 40 Amps - 6 No (d) MCB 2 pole, 240 Volts, 40 Amps - 8 No |
| 98 | Supply, install, testing and commissioning of factory made LT Panel board outdoor type made totally enclosed dust & vermin proof single opening with double leaf shutter duly hinged with locking arrangement made of MS angle iron frame work & CRCA sheet of 3.15 mm thick as per IS 5039 duly painted with powder coated of approved shade over a coat of zinc chrome primer after min seven tank treatment process including numbering & lettering mounted on C channel of appropriate size. Neccessary holes shall be kept on the kiosk box for incoming and outgoing cable entry, all holes shall be provide with brass cable gland of apprppriate size. The panel shall be suitablr universal mounting arrengement of thermal protection MCCBs & shall comprise with 300 Amps capacity Aluminium TPN bus bar chamber having 3 phase 4 bus bar system fixed on porceilin insulator with suitable size Aluminium Bus Bar extension till cable chamber and duly sleeved with 4 coloured heat shrinkable PVC sleeve, thimble & glands the pannel board shall confirm as per IP 52 complete all as directed with foliowing accessories including taking out old panel. (Note:-The cost of the PCC plateform deemed to be included in the qouted rates of above said item complete all as specified & directed). The panel shall be of complete bus bar system. |
| 99 | INCOMING(a) Thermal Protection MCCB 4 pole 160 amps, 36 KA , 415 V- 01 Nos (b) Volt meter (digital type) 0-500 volts with selector switch - 01 No(c) Ammeter (digital type) with 3 Nos CT and selector switch - 01 Set(d) R,Y B Indicator lamp LED type - 01 SetOUTGOING (a) Thermal Protection MCCB 3 pole 160 amps, 36 KA, 415 V- 01 No (b) Thermal Protection MCCB 3 pole 63 amps, 36 KA , 415 V- 04 No (c) Street Light Digital Time Switch - 01 No (d) Power contactor 3 pole AC 3 rating 32 A - 01 No Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 6 daysJul 29, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender