Tender For Sitcof Fire Fighting System Including Aerosol Based Fire Suppression System, 30 Kva Dg Set Inverter, Earthing, Internal Electrification Of Main Panel And Db At Old Chc Sanamasigam In The District Of Nabarangpur Buildings.

Issued by Government Departments · Nabarangpur, Odisha
Tender Value
35.63 Lakhs
Estimated cost
Bid Submission
15 Jul 2026
7 days left
EMD
35700
Bank guarantee accepted
Document Fee
6000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Nabarangpur → Odisha
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Sitcof Fire Fighting System Including Aerosol Based Fire Suppression System, 30 Kva Dg Set Inverter, Earthing, Internal Electrification Of Main Panel And Db At Old Chc Sanamasigam In The District Of Nabarangpur Buildings.

BOQ

Name of Work:- SITCof Fire Fighting System including Aerosol Based Fire Suppression System, 30 KVA DG Set Inverter, Earthing, Internal Electrification of Main Panel and DB at Old CHC Sanamasigam in the District of Nabarangpur Buildings.
Sl. No. Item Description
1FIRE FIGHTING SYSTEM
2PUMPS AND APPURTENANCES
3Supplying, installation, testing and commissioning of Electric Motor Driven Pressurization Terrace Pump having discharge of 900 LPM at 35 Mtr head complete with Pump Set, Electric Motor suitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame.Make-Wilo/KSB/Kirloskar
4Supply & fixing of Terrace tank (5000 ltr) Fiber Water tank triple layer unbrakable extra thick and flexible material for long life new UV threaded lid to keep dust particles out with all needed accessories. (Mukta/Sintex or Equivalent make)
5Supply, Installation of structural steel like ( Beam , Channel, Angle, Plate & Sheet) for 2 nos terrace tank base & barricade .
6Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable for 7.5 HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge Control panel for fire pumps for auto action.make-Legrand/schneider/ Siemens/ABB/Hager /C&S /L&T/ Havells
7Supply, Installation of Pump protection shed on terrace made by structural steel & sheet
8PIPE & VALVES ETC.
9Supplying, installing, testing and commissioning of MS Pipes, ERW confirming to IS 1239 Pt - I HEAVY grade up to 150mm dia and pipes 200mm dia and above shall be M.S as per IS: 3589 with painting, suitable type of supports, anchor fasteners, bolts nuts, clamps, \\"U\\" bolts, malleable specials such as Reducers,Tees, elbows, flanges. Including cutting, Welding, fixing in / on walls, ceiling by using suitable supports etc, complete.Make-TATA/SAIL/JINDAL
10100mm NB
1180mm NB
1225mm NB
13Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C. Make-Zoloto/Leader/Audco
14100mm NB
15Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Make-Zoloto/Leader/Audco
16100mm NB
17Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru
18Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge.Make-Danfoss/Indfoss/ Grundfoss
19Supply,Installation,Testing & Commissioning of stainless steel strainer fabricated out of 1.6 mm thick stainless steel sheet Y Stainer with 3 mm dia hloes with stainless steel flange as required. Make- -Zoloto/Leader/Audco
20100mm NB
21Supplying, installing, testing and commissioning of Gun metal chrome finished Ball valves with fittings of screwed end type.Make-Kartar/Zoloto/ Leader/Kirloskar/Eq
2225mm NB
2315mm NB
24DOWN COMER SYSTEM
25Supply,Installation,Testing & Commissioning of Stainless steel Hydrant Valve / Landing valve, of 63 mm NB size, type-A, single headed , oblique type, as per IS :5290/93 and as per direction of Engineer-in-charge.Make-Newage/Minimax/ Fireshield
26Supply,Installation,Testing & Commissioning of SS short branch pipe with 63 mm male inlet and 19 mm outlet nozzle, as per IS:903 and as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield
27Supply,Installation,Testing & Commissioning of 63 mm NB and 15meter long RRL Fire Hose fitted with 63mm intstantaneous stainless steel male & female SS coupling, complete by GI wire binding for Internal Hydrant as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield
28Providing supply & fixing of MS Hose Box for of suitable size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long fire hose and a branch pipe, wall mounted type as per direction of Engineer-in-charge. Make-Newage/Minimax/ Fireshield
29Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing first aid hose reel made from MS sheet and waterways and moving parts with rubber hose of 20 mm dia. and 30 mtrs. long with ABS(Plastic) shut-off nozzle as per IS: 444/IS: 12585 Type-I., complete with all accessories as per direction of Engineer-in-charge. Make-Newage/ Minimax / Fireshield
30Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. Make-Zoloto/ Leader/Audco
31Providing, fitting & fixing of 2-Way GM fire brigade connection consisting of 63 mm dia instantaneous type male couplings with built-in check valves, 150mm dia flanged outlet complete with bolts, nuts and rubber insertions confirming to IS:904 with ISI mark including testing & commissioning the system etc. all complete as per apporoved specification & direction of EIC. Make-Zoloto/ Leader/Audco
32AEROSOL BASED FIRE EXTINGUISHERS
33Supply & Installation 8 gm Portable Aerosol based Automatic Fire Shield (Coverage: 0.008 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent
34Supply & Installation of 20 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.2 m3), EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction of Engineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent
35Supply & Installation of 30 gm Portable Aerosol based Automatic Fire Extinguisher (Coverage: 0.3 m3) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 10 years. Make-Pyrogen/Genefire/Stat-x/Equivalent
36Supply & Installation of 50 gm aerosol based Manual Fire Extinguisher (Duration:10-20 sec) , EN 15276-1:2019 and EN 15276-2:2019 ,ISO 15779:2011 approved ,capable for extinguishing Class A, B, C & E fire, non-corrosive, non-conductive, non-toxic, activation temperature 70 deg-180 deg Celcius including all accessories as per the direction ofEngineer-in-Charge. Replacement warranty on the product shall be 3 years and shell-life of 5 years. Make-Pyrogen/Genefire/Stat-x/Equivalent
37Fire buckets round bottom type enamel painted, white inside & Red out side and Letter \\"FIRE\\" in black out side and handle with mounting bracket.
38Fire bucket stand fabricated by MS angles to install 3 Nos. of buckets.
39SIGNAGES
40Providing and fixing in position the signage of \\"Fire Extinguisher\\" to be fixed near the every fire shaft at all floors.Size 6'' x8 ''.
41Providing and fixing in position the signage of \\"Fire Hydrant & Hose Reel \\" to be fixed near the every fire shaft at all floors.Size 6'' x8 ''.
42Providing and fixing in position the signage of \\"Manual Call Point\\" to be fixed near the every fire shaft at all floors.Size 6'' x8 ''.
43FIRE ALARM SYSTEM
44Supplying, installation, testing and commissioning of Addressable Multi Detector(Smoke cum Heat) complete with base and isolator as per direction of Engineer-in-charge.Make-Morley IAS/Siemens/ Bosch/ Honeywell/Edward
45Supply, Installation, testing and Commissioning of addressable manual call box made of polycarbonate with plastic break glass front and complete with monitor module MCB shall be recessed in wall .Make-Morley IAS/Siemens/Bosch/ Honeywell/Edward.
46Supply Installation, Testing & Commissioning of wall mounting loop powered addressable type hooter with strobe and all accessories as per specification.Make-Morley IAS/Siemens/ Bosch/ Honeywell/Edward
47Supply, Installation,Testing & Commisioning of Microprocessor based Addresable fire alarm control panel , fully networkable with each loop capable of taking 99 devices, 8 line x 40 character alpha- numeric liquid crystal display .The panel shall be soft addressable type . The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 8 hours with integral battery charger complete as required and as per specification. The fire alarm panel shall be suitable for software integration with BMS & PA system.Make-Morley IAS/ Siemens/ Bosch/ Honeywell/Edward
482 Loop Panel
49Supply and installation of visual type response indicators with LED indicating lamp, housed in suitable MS enclosure with acrylic cover fixed in flush with wall to operate in conjunction with smoke/Heat detectors operating on 24 VDC installed above the false ceiling or below the false floor, complete with all accessories and fixing materials as required and as directed by Engineer-in-charge.
50Supplying, installing, testing and commissioning of 2C x 1.5 mm², armoured, single stand, outer sheathed, FRLS, PVC insulated copper conductor cable confirming to specified IS standards .Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI
512 C x 1.5 Sqmm.
52Supplying, installing, testing and commissioning approved make PVC FRLS conduits on ceiling / wall / floor etc. complete with accessories like, Junction boxes, Collars, Bends etc. 25mm dia.Make-AKG/BEC/Precision/Norpack
53DG Set
54Supply, Transportation, erection, testing and commissioning of 3 Phase, 415V, 50Hz, water cooled multi cylinder diesel generator set with alternator of 30KVA ( Make -Kirloskar / Jakson/Mahindra) out put contineous rating directly coupled Engine and Alternator with guard and mounted on a common base plate of Robust construction and complete with AMF panel having IP-52 protection, Acoustic Enclosure as per CPCB IV+ norms , sound absorbing material, to restrict sound level up to 75 dB up to 1 mtr distance and as per CPCB IV + norms etc as per following specifications mentioned below.Warranty period of panel must be 2 years
55ALTERNATOR:The alternator of the output rating shall be 3 Phase, 415V, 50Hz, Ac , 0.8 P.F. lagging at 1500 RPM. The alternator is self excited, self regulated, and shall confirm to IS: 13364 of 1992 with regulation of +5% from no load to full load. degree of protections shall be IP21.
56ENGINE:. Diesel Engine start, developing suitable BHP output at 1500 RPM with mechanical / electronic governing so as to enable the alternator to give 30KVA continuous output at 0.8 P.F. lagging at NTP conditions. The diesel engine shall be capable of providing 10% O/L for 1 Hr for every 11 Hrs of continuous running at full load. The engine with 1st filling of oil and Diesel etc.01. Exhaust pipe of required size and length with insulation or clading.02. Diesel tank suitable for 8 to 12 Hours running capacity.03. Industrial Silencer.04. SMF Batteries with leads as per the Manufacturer standards
57AMF PANEL: Cubical, Compartmentalized, AMF Panel Baord with all Power & Control Contractors,for both main & dg along with battery charger,relay,timer & all required accessories, Meters and other accessories, Internal Wiring, connection, inter-connection etc. for Trouble Free smooth function for 30KVA DG Set complete with Battery Charger & leads as required.
58BASE PLATE: Common Base Plate of required size for mounting of Engine Alternator Set fabricated from MS Channerl and vibration damping arrangement with cushy foor mounting including paintng etc. as required.
59FOUNDATION: Suitable size Cement Concrete (1:2:4) foundation duly plastered and finished with neat coat Cement as required along with smoke exhaust system piping including base frame of structure & lightening protection system. *It also includes 2 nos copper plate earthing and 4 nos copper plate earthing for neutral, control cable of 15mtr 2.5sqmm 6core , civil foundation work.(The Manufacturing of DG set shall not in any case be more than six months old from the date of award of work)
60INVERTER AND EARTHING
61Supply and fixing 3.5 KVA /36 Volt Pure Sine Wave Inverter.(Make:V-Guard/Luminous/Microtek/Eq.)
62Supply and fixing 200 AH Inverter battery (Make:V-Guard/Luminous/Exide/Eq.)
63Supply of Rack for Storing Batteries.
64S/F of 100A Onload Change Over with SS Enclosure.Make:Legrand/Hager/Schneider/Siemens/ABB/L&T
65Supply of 50 sq.mm Single core XLPE Al.Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster)
66Supply of 16 sq.mm Single core core XLPE Al.Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster)
67Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of not exceeding 25 sq.mm direct in ground including excavation, sand cushing, protective covering and refilling the trench etc. as required.
68Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm on surface as required.
69Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground including excavation, sand cushing, protective covering and refilling the trench etc. as required.
70Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm on surface as required.
71Supply of 50mm dia PN10 HDPE Pipe.
72Supply, installation, testing and commissioning of UPVC pipes for filling line from existing tank to fire water tank on terrace floor with all accessories.
73S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.
74Supplying and laying 25 mm x 5 mm GI earth strip ISI marked on surface or in recess for connection etc as required.
75Internal Electrification of Main Panel and DB
76Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge.
77a) 4x16mm2 + 2x10mm2
78S/I/T&Commissioning of LT indoor floor mounted cubical type electrical main panel made out by 2mm CRCA steel sheet duly derusted & pented by simens gray powder cote paint is designed as G.A drawing as per direction of Engg.-in-Charge. In commer- 01 number of 250 Amps 4P MCCB,25KA with 250A 4P changeover switch (Icu=100%Ics) with shunt trip.with auxuliary Busbar- 04 numbers of 250Amps Aluminium busbar duly sleeved by color coaded PVC sleeve and 01 no. busbar for Earthing & supported by suitable size DMC insulator Out going- (i) 100A,16KA 4P MCCB 2 nos (ii) 63A,16KA 4P MCCB 2 nos (iii) 63A 4P MCB 3 nos . (iv) 63A 2P MCB 4 nos (v) 40A 2P MCB 2 nos. Instrument- (i) phase indicating lamp with HRC fuse.(ii) 01 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication(iii) 01 set of 40KA TYPE 1+2 4P SPD along with 63A 4P MCB.Make of switchgear-Legrand/Schneider/Siemens/ABB/ L&T
79Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FRLSH PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB ITUS as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years.
804 Way(4+12) Way VTPN MCB DD DB Vertical Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door(but with out MCB/ RCCB/ Isolator) Warranty on DB is 3 years
814 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door(but with out MCB/ RCCB/ Isolator) Warranty on DB is 3 years
82Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 year.
83Supplying and fixing 40 Amps rating, C series,10KA breaking capacity,DP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge.The MCB should be Replacement Warranty will be 1 year.
84Supplying and fixing 63 Amps rating, C series,10KA breaking capacity,DP, 240 volts, MCB . Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. The MCB should be Replacement Warranty will be 1 year.
85Supplying and fixing 63Amps 4P 415 volts RCCB 30 mA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.The RCCB should be Replacement Warranty will be 1 year.
86Supplying and fixing 63Amps 4P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 year.
87Supplying and fixing 63Amps 3P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 year.
88Supplying and fixing 40Amps 3P 415 volts MCB Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 year.
89S/F of 100A,25KA 4P MCCB.Make:Legrand /Hager/ Schneider/ Siemens/ABB/L&T
90S/F of 100A Onload Change Over with SS Enclosure.Make:Legrand/Hager/Schneider/Siemens/ABB/L&T
91Supply of 95 sq.mm Single core XLPE Al.Armoured Cable of ISI marked.(Make -Polycab/Havells /KEI/RR Kable/Finolex/Gloster)
92Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm direct in ground including excavation, sand cushing, protective covering and refilling the trench etc. as required.
93Laying and fixing of PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 120 sq.mm on surface as required.
94Supply, installation, testing and commissioning of UPVC pipes for filling line from existing tank to fire water tank on terrace floor with all accessories.
95S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.
96Supplying and laying 25 mm x 5 mm GI earth strip ISI marked on surface or in recess for connection etc as required.
97Lightning Arrester
98Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB
99Supply of Roof conductor holder for parapet- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested.Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB
100Supply of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black @ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB
101Supply of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB
102Supply of 1 mtr vertical air terminal with mounting accessories on the flat surface to meet the requirements of IS/IEC 62305.Tested for Electrical , mechanical and chemical as per IEC 62561. Tested for 100kA lightning current. Make-OBO/Dehn/ABB
103Supply of Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 Nominal size Ø10/16 mm aluminium rod: 3 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. Tested as per IEC 62561. Make-OBO/Dehn/ABB
104Supply for Providing of Stand for Fang Fix system 16 kg with base and clamp ,made up of frost resistant concrete and clamp testedupto 100KA lightning current . Make-OBO/Dehn/ABB
105Supply for Providing of Stand for Fang Fix system 16 kg made up of frost resistant concrete. Make-OBO/Dehn/ABB
106Supply of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer.Tested for 100kA lightning current. Make-OBO/Dehn/ABB
107Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr Height For Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB
108Supply of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor Hot Dipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB
109Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB
110Supply of flat conductor holder- Fit: FL 30, With mounting hole 6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece from hot-dip galvanised steel, Bottom section from polyamide, black. Tested as per IEC 62561. Make-OBO/Dehn/ABB
111Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB
112Supply of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2mm with copper coating thickness of 250micron tested as per IEC 62561-2 Make-OBO/Dehn/ABB
113Supply of universal clamp made of SS to connect rod with flat conductor Make-OBO/Dehn/ABB
114Supply of Earth conductivity enhancing mineral compound shall be of 25kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB
115Supply of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Make-OBO/Dehn/ABB
116Installation of The above arrangements including all accessories as per Direction of Engg. In charge. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56318290
AUTHORITY Government Departments
TENDER VALUE 35.63 Lakhs
LAST DATE 15-07-2026
Authority
Authority Name Road And Building Department
Work Description Tender for Sitcof Fire Fighting System Including Aerosol Based Fire Suppression System, 30 Kva Dg Set Inverter, Earthing, Internal Electrification Of Main Panel And Db At Old Chc Sanamasigam In The District Of Nabarangpur Buildings.
Basic Detail
Tender No 4 /2026-27/NGP
Bidding Type Tender
Location
City Nabarangpur
State Odisha
Key Dates
Publish Date 06 Jul 2026
Submission Date 15 Jul 2026
Open Date 17 Jul 2026
Finance
Tender Value 35.63 Lakhs
Tender Fee 6000
EMD 35700
Exemption Available
Document List
469b47d4-b708-4e2b-ace7-962aea3527b3.html
BOQ_599779.xls
Tendernotice_1.pdf
Tendernotice_2 (6).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 15, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 7 days
Jul 17, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 9 days

Tender Documents

Download All (ZIP) ↓
html

469b47d4-b708-4e2b-ace7-962aea3527b3.html

xls

BOQ_599779.xls

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2 (6).pdf