Tender For Augmentation Of Gss Kathua From 3X50mva To 4X50mva By Way Of Supply Installation Testing and Commissioning of One 132/66Kv,50Mva Power Transformer With Allied Works, Construction Of New 132 Kv Line Bay, Conversion Of Existing Line Bay To T
Tender Overview
Project Description
Tender for Augmentation Of Gss Kathua From 3X50mva To 4X50mva By Way Of Supply Installation Testing and Commissioning of One 132/66Kv,50Mva Power Transformer With Allied Works, Construction Of New 132 Kv Line Bay, Conversion Of Existing Line Bay To Transformer Bay, Uprating Of Existing Twin Bus Bar From Acsr Zebra To Twin Moose Conductor At 66 Kv Yard,Extension Of Control Room Building, Supply Installation Testing and Commissioning of Battery Bank And Charger (300 Ah, 110V), Replacement Of Old And Obsolete Ac,Dc Board And 250 Kva Auxilliary Transformer At 132/66 Kv Grid Station Kathuaand Allied Works.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 06-Jul-2026 | CORRIGENDUM 01 | Other | 24-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Design Engineering, Manufacture, testing at manufacture’s work place, packing and forwarding, insurance. Supply of Main Equipments /materials at 3x50MVA 132/66KV Grid Station Kathua |
| 2 | Cost of 40/50 MVA, 132/66 KV Three PhasePower Transformers with OLTC, SCADA Compatible RTCC, NIFPS, HV and LV connectors and other required accessories and fittings with online DGA monitoring kit, online dehydration kit and maintenance free automatic Breathers as per detailed technical specs, Mandatory spares as per SBD (current density for HV/LV winding not more than 2.4 A/sq mm. Core flux density not more than 1.5T) |
| 3 | Galvanised Structures |
| 4 | Galvanised Nuts and Bolts |
| 5 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 6 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 7 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 8 | 3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 9 | 400 sq mm ACSR ZEBRA,(a) Alumunium=54/3.18 mm(b) Steel=7/3.18 mm Overall dia 28.62mm.Approximate Wt 1621Kg/Km Ultimate breaking Load=130.32 KN |
| 10 | Single Tension Fittings For Single Zebra shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. |
| 11 | Single Suspension Fittings For Single Zebra shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 12 | T Clamps Twin 0.4 / Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:55611970 (latest edition |
| 13 | Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected |
| 14 | 7/3.15 mm G.I. Wire for ground conductor |
| 15 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire |
| 16 | Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing |
| 17 | Rail Track |
| 18 | Erection Testing and Commission of Main Equipments for installation of 50MVA transformer at GSS Kathua |
| 19 | cost of 40/50 MVA, 132/66 KV Three PhasePower Transformers with OLTC, SCADA Compatible RTCC, NIFPS, HV and LV connectors and other required accessories and fittings with online DGA monitoring kit, online dehydration kit and maintenance free automatic Breathers as per detailed technical specs, Mandatory spares as per SBD (current density for HV/LV winding not more than 2.4 A/sq mm. Core flux density not more than 1.5T) |
| 20 | Galvanised Structures |
| 21 | Galvanised Nuts and Bolts |
| 22 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS,alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 23 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 24 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 25 | 3.5 Core, 25 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, alvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 26 | 400 sq mm ACSR ZEBRA,(a) Alumunium=54/3.18 mm(b) Steel=7/3.18 mm Overall dia 28.62mm.Approximate Wt 1621Kg/Km Ultimate breaking Load=130.32 KN |
| 27 | Single Tension Fittings For Single Zebra shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. |
| 28 | Single Suspension Fittings For Single Zebra shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 29 | T Clamps Twin 0.4 / Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:55611970 (latest edition |
| 30 | Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected |
| 31 | 7/3.15 mm G.I. Wire for ground conductor |
| 32 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire |
| 33 | Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing |
| 34 | Rail Track |
| 35 | Civil works for transformer |
| 36 | Concreting of yard & Laying Of Gravel |
| 37 | Laying of Transformer foundations for Three phase 50 MVA Transformer (as per Drawing) |
| 38 | nstruction of Oil sump & Tank for Three phase 50 MVA Power Transformer (as per drawing) |
| 39 | Laying of 132 KV Column foundations (as per Drawing) |
| 40 | Supply of Main Equipments and allied materials for Construction of 132KV line bay and conversion of existing line bay to transformer bay complete job |
| 41 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps or higher, of 3 phase, 50 c/s and 40 KA for 1 second) along with supporting structures etc. complete in all Respects SS BODY,UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES |
| 42 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 KA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 43 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 44 | Single phase, 50 c/s 145KV Current Transformers (600-300-150/1-1-1-1-1 A or 1200600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-11A or as per site specifications), 40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories , auxiliaries etc. |
| 45 | Neutral Current Transformer with Current Rating 1A/5A and VA Burden 15VA Ratio as per site specifications. 02 No PS class cores, 01 No 0.2s core, GALVANISED TANK 31.5KA for one second, rated dynamic current 31.5KA(peak), including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. |
| 46 | Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor, class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries. |
| 47 | 132KV Control and Relay Panel for Transformer bay simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GE MICOM/ALSTOM/SCHNEIDER with IEC 61850 compatibility, including Differential Protection, Directional O/C & E/F Protection (on HV & LV side), numerical communicable REF protection relay, Over Fluxing Protection Local Breaker Backup (LBB) Protection separate relays for primary and backup protection |
| 48 | 132KV Post Insulators Solid Core Type/ Polymer Type, Power Frequency Withstand Voltage 275 KV RMS Dry lightning impulse withstand voltage ± 650 (KVP) |
| 49 | Single phase, 50 c/s, 72.5 kV Current Transformers (1600-1200-800/1-1-1-1-1 A or 1200-800-400/1-1-1-1-1A or 2000-1600-1200/1-11-1-1 A or as per site specifications), 31.5 KA for one second, Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. Complete in all respects |
| 50 | Single phase, 50 c/s, outdoor, metal oxide gapless type, 60 kV (rms), class 3 arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification. |
| 51 | Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3)V, One min power freq withstand 275KVrms GALVANISED TANK. Acc Class 0.2 |
| 52 | Galvanised Structures |
| 53 | Galvanised Nuts and Bolts |
| 54 | 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 55 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 56 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 57 | 12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 58 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 59 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 60 | 4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 61 | 10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 62 | 2 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 63 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly shoved. The paint thickness shall be at least 50 microns. |
| 64 | 400 sq mm ACSR ZEBRA,(a) Alumunium=54/3.18 mm(b) Steel=7/3.18 mm Overall dia 28.62mm.Approximate Wt 1621Kg/Km Ultimate breaking Load=130.32 KN |
| 65 | Single Tension Fittings For Single Zebra shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. |
| 66 | Single Suspension Fittings For Single Zebra shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 67 | T Clamps Twin 0.4 / Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:55611970 (latest edition |
| 68 | P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 69 | Disc Insulators 70 KN,Ball& Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. |
| 70 | Disc Insulators 120 KN,Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected |
| 71 | 7/3.15 mm G.I. Wire for ground conductor |
| 72 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire |
| 73 | Lugs, Ferrules, Welding Material, Cotton Waste etc |
| 74 | Erection Testing and commissioning of Main Equipments and allied materials for Construction of 132KV line bay and conversion of existing line bay to transformer bay complete job |
| 75 | 3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 2500 Amps or higher, of 3 phase, 50 c/s and 40 KA for 1 second) along with supporting structures etc. complete in all Respects SS BODY,UNIVERSAL SPRING CHARGING MOTOR WITH MANDATORY SPARES |
| 76 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 KA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX. |
| 77 | 145kV, 50c/s , 2500 A, SCADA Compatible, 40 kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Switch. COPPER FIXED AND MOVING CONTACTS/ COPPER CURRENT CARRYING PARTS, GALVANISED IRON MECHANISM BOX |
| 78 | Single phase, 50 c/s 145KV Current Transformers (600-300-150/1-1-1-1-1 A or 1200600-300/1-1-1-1-1A or 2000-1600-1200/1-1-1-11A or as per site specifications), 40 KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories , auxiliaries etc. |
| 79 | Neutral Current Transformer with Current Rating 1A/5A and VA Burden 15VA Ratio as per site specifications. 02 No PS class cores, 01 No 0.2s core, GALVANISED TANK 31.5KA for one second, rated dynamic current 31.5KA(peak), including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. |
| 80 | Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor, class 3 including Surge counters/monitors, insulating base all associated accessories, auxiliaries. |
| 81 | 132KV Control and Relay Panel for Transformer bay simplex/duplex as per requirement, completely wired including Substation automation supporting IEDs/numerical relays of make ABB/SIEMENS/GE MICOM/ALSTOM/SCHNEIDER with IEC 61850 compatibility, including Differential Protection, Directional O/C & E/F Protection (on HV & LV side), numerical communicable REF protection relay, Over Fluxing Protection Local Breaker Backup (LBB) Protection separate relays for primary and backup protection |
| 82 | 132KV Post Insulators Solid Core Type/ Polymer Type, Power Frequency Withstand Voltage 275 KV RMS Dry lightning impulse withstand voltage ± 650 (KVP) |
| 83 | Single phase, 50 c/s, 72.5 kV Current Transformers (1600-1200-800/1-1-1-1-1 A or 1200-800-400/1-1-1-1-1A or 2000-1600-1200/1-11-1-1 A or as per site specifications), 31.5 KA for one second, Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. Complete in all respects |
| 84 | Single phase, 50 c/s, outdoor, metal oxide gapless type, 60 kV (rms), class 3 arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification. |
| 85 | Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3)V, One min power freq withstand 275KVrms GALVANISED TANK. Acc Class 0.2 |
| 86 | Galvanised Structures |
| 87 | Galvanised Nuts and Bolts |
| 88 | 2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 89 | 5 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 90 | 8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 91 | 12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 92 | 16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 93 | 19 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 94 | 4 Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS ,galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 95 | 10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 96 | Core, 6 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanized steel wire/ strip armoured stranded copper conductor control cable complete |
| 97 | Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, self-supporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly shoved. The paint thickness shall be at least 50 microns. |
| 98 | 400 sq mm ACSR ZEBRA,(a) Alumunium=54/3.18 mm(b) Steel=7/3.18 mm Overall dia 28.62mm.Approximate Wt 1621Kg/Km Ultimate breaking Load=130.32 KN |
| 99 | Single Tension Fittings For Single Zebra shall have minimum failing load of 100% ultimate strength of Bundle cnductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN. |
| 100 | Single Suspension Fittings For Single Zebra shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 101 | T Clamps Twin 0.4 / Twin 0.4, made of Alluminium Alloy and shall comply in all respects with IS:55611970 (latest edition |
| 102 | P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 103 | Disc Insulators 70 KN,Ball& Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. |
| 104 | Disc Insulators 120 KN,Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected |
| 105 | 7/3.15 mm G.I. Wire for ground conductor |
| 106 | Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding conductivity of GSS ground wire |
| 107 | Conversion of 132KV line bay to transformer bay& Lugs, Ferrules, Welding Material, Cotton Waste etc |
| 108 | Civil works for 132KV line bay and conversion of existing line bay to transformer bay |
| 109 | Cable Ducts With Covers: Main Duct of Size 1200mm x 1200mm with 6 mm M.S Chequered Trench Covers of size 1300x500 mm |
| 110 | Main Duct of Size 1200mm x 1200mm with 75mm Concrete Covers grade M15 of size 1300x500 mm M15 of size 1300x500 mm |
| 111 | Sub Main Duct of Size 600mm x 600mm with 75mm Concrete Covers grade M15 of size 700x500 mm |
| 112 | Tee off Duct: 150mm sand filled HDPE pipes from Sub main to Equipments in the outdoor area |
| 113 | Earth Mat (40mm dia steel bars) as per approved design, Galavanised Iron (75mm x 12mm/ 50mm x 6 mm) risers for Equipment and Structural Earthing |
| 114 | Concreting of yard & Laying Of Gravel |
| 115 | Laying of 132KV Column foundations (as per Drawing) |
| 116 | Laying of 132KV Isolator foundations (as per Drawing) |
| 117 | Laying of 132KV SF6 Breaker foundations (as per Drawing) |
| 118 | Laying of 132KV CT foundations (as per Drawing) |
| 119 | Laying of 132KV NCT foundations (as per Drawing) |
| 120 | Laying of 132KV LA foundations (as per Drawing) |
| 121 | Laying of 132KV Post Insulator foundations (as per Drawing) |
| 122 | Laying of 66KV CT foundations (as per Drawing) |
| 123 | Laying of 66KV LA foundations (as per Drawing) |
| 124 | CABLE TRAYS/CABLE RACKS/ACCESSORIES Cable Trays of size 400mm x 3000mm made of M.S angles 40x40x6mm,40x6 Flat. |
| 125 | Cable Trays of size 300mm x 2500mm made of M.S angles 40x40x6mm,40x6 Flat. |
| 126 | Supply of Main Equipments and allied materials for twinning of bus bar of 132KV and 66KV Yard with ACSR double moose conductor at Grid station Kathua |
| 127 | 500mm2 ACSR Moose (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 128 | Single Tension Fittings For Twin Moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN |
| 129 | Single Suspension Fittings For Twin Moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 130 | T Clamps Twin 0.5 / Twin 0.5, made of Alluminium Alloy and shall comply in all respects with IS:55611970 (latest edition) |
| 131 | Disc Insulators 120 KN,Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. |
| 132 | Disc Insulators 70 KN,Ball& Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. |
| 133 | Spacers for Twin ACSR Conductor |
| 134 | P G Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 135 | P I Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 136 | Erection testing and commissioning of Main Equipments and allied materials for twinning of bus bar of 132KV and 66KV Yard with ACSR double moose conductor at Grid station Kathua |
| 137 | 500mm2 ACSR Moose (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN |
| 138 | Single Tension Fittings For Twin Moose shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 120 KN |
| 139 | Single Suspension Fittings For Twin Moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 140 | Single Suspension Fittings For Twin Moose shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor. The ball and socket designation must be 20mm.Minimum Ultimate strength (Tensile strength) shall be 70 KN. |
| 141 | Disc Insulators 120 KN,Ball& Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected. |
| 142 | Disc Insulators 70 KN,Ball& Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected. |
| 143 | Spacers for Twin ACSR Conductor |
| 144 | P G Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 145 | P I Clamps 0.5 made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition) |
| 146 | Supply of Battery bank and battery charger at grid Station Kathua |
| 147 | Battery Bank 110 V, 300 AH, of 55 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant. |
| 148 | Battery charger (Three phases): Battery charger as well as Automatic Regulators shall be of static type compatible with VRLA Batteries. Should also have necessary temperature sensors. Should have both Automatic and Manual control of output voltage and current. 110 V/30 A FC & 40 A FCBC 3 phase 4 wire for 300 AH VRLA Battery |
| 149 | Erection testing and commissioning of Battery bank and battery charger at Grid Station Kathua |
| 150 | Battery Bank 110 V, 300 AH, of 55 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame retardant. |
| 151 | Battery charger (Three phases): Battery charger as well as Automatic Regulators shall be of static type compatible with VRLA Batteries. Should also have necessary temperature sensors. Should have both Automatic and Manual control of output voltage and current. 110 V/30 A FC & 40 A FCBC 3 phase 4 wire for 300 AH VRLA Battery |
| 152 | Supply of old obsolete AC and DC distribution boards at grid Station Kathua |
| 153 | DC Distribution Panel (110V, DC) with 1 No.10Amp. Air break Circuit Double pole for battery incoming supply with DP MCBs & indicating Lamps etc. |
| 154 | AC Distribution panel (415V,AC) complete with Circuit Breakers, indicating lamps etc for 132/66 KV Grid station Kathua |
| 155 | 100 KVA servo stabilizer 3-phase 4 wire copper wound indoor type, input voltage range 220-460V, output 400V ± 1%,in two parts of oil cooled and air voltage range 220-460V, output 400V ± 1%,in two parts of oil cooled and air cooled having, Digital control, Response time <10ms, Automatic Switch-Off against:• Under / Over-Voltage• Over-Load & Short - Circuit• Single Phasing, Class C Type Secondary surge Protection |
| 156 | Power cables for AC/DC network in Control room for 132/66 KV Grid Station. The armoured XLPE insulated 1100 V grade power cables shall be of FRLS type, of category C1 conforming to IS: 7098 Part I (as amended up to date). The conductor shall be stranded aluminum, circular / shaped and compacted. In multi core cables, the core shall be identified by red, yellow, blue and black colored strips or coloring of insulation. A distinct inner sheath shall be provided in all multi core cables. For multi core cables the inner sheath shall be of extruded PVC of type ST-2 of IS: 5831. Armoring for single core cables shall be aluminum strips/wires. Outer sheath for all cables shall be extruded PVC of type ST- 2 of IS: 5831 |
| 157 | Erection testing and commissioning of old obsolete AC and DC distribution boards at grid Station Kathua |
| 158 | DC Distribution Panel (110V, DC) with 1 No.10Amp. Air break Circuit Double pole for battery incoming supply with DP MCBs & indicating Lamps etc. |
| 159 | AC Distribution panel (415V,AC) complete with Circuit Breakers, indicating lamps etc for 132/66 KV Grid station Kathua |
| 160 | 100 KVA servo stabilizer 3-phase 4 wire copper wound indoor type, input voltage range 220-460V, output 400V ± 1%,in two parts of oil cooled and air voltage range 220-460V, output 400V ± 1%,in two parts of oil cooled and air cooled having, Digital control, Response time <10ms, Automatic Switch-Off against:• Under / Over-Voltage• Over-Load & Short - Circuit• Single Phasing, Class C Type Secondary surge Protection |
| 161 | Power cables for AC/DC network in Control room for 132/66 KV Grid Station. The armoured XLPE insulated 1100 V grade power cables shall be of FRLS type, of category C1 conforming to IS: 7098 Part I (as amended up to date). The conductor shall be stranded aluminum, circular / shaped and compacted. In multi core cables, the core shall be identified by red, yellow, blue and black colored strips or coloring of insulation. A distinct inner sheath shall be provided in all multi core cables. For multi core cables the inner sheath shall be of extruded PVC of type ST-2 of IS: 5831. Armoring for single core cables shall be aluminum strips/wires. Outer sheath for all cables shall be extruded PVC of type ST- 2 of IS: 5831 |
| 162 | Supply of 250KVA transformer for provision of alternate 11KV supply at 132/66KV grid Station Kathua |
| 163 | Allied items of 11 KV Tapping Point |
| 164 | 11 KV XLPE Cable Single Circuit Three Core 120 sq.mm |
| 165 | 250 KVA,11/0.4 KV,3Ph LT Transformer ( Platform Mounted) |
| 166 | Provision of Change Over Switch, 3.5 core 185mm2 LT cable, MCBs etc. |
| 167 | 11 KV Outdoor Heat Shrinkable Cable Termination Kits |
| 168 | Erection testing and commissioning of 250KVA transformer for provision of alternate 11KV supply at 132/66KV grid Station Kathua |
| 169 | Installation of 11 KV Tapping Point |
| 170 | Erection of 11 KV XLPE Cable Single Circuit Three Core 120 sq.mm |
| 171 | nstallation of 250 KVA,11/0.4 KV,3Ph LT Transformer ( Platform Mounted) |
| 172 | Provision of Change Over Switch, 3.5 core 185mm2 LT cable, MCBs etc. |
| 173 | 11 KV Outdoor Heat Shrinkable Cable Termination Kits |
| 174 | Supply of Marshaling Kiosk as per specifications |
| 175 | (132 KV)/66KV Marshalling kiosk with Kiosk frames Stainless steel/HotDip Galvanised structural sections for pressed and shapedcold-rolled sheet steel, thickness not less than 2.0 mm.Shall be provided with a degree of protection of IP: 55,with Copper Bar earthing for 132 kV.as per specifications |
| 176 | Erection Testing and commissioning of Marshaling Kiosk |
| 177 | (132 KV) /66KV Marshalling kiosk with Kiosk frames Stainless steel/HotDip Galvanised structural sections for pressed and shapedcold-rolled sheet steel, thickness not less than 2.0 mm.Shall be provided with a degree of protection of IP: 55,with Copper Bar earthing for 132 kV.as per specifications |
| 178 | Supply of Auxilliary transformer and allied materials |
| 179 | 66/0.433 KV, 1000 KVA , 3-Phase Transformer With Bimetallic Terminal connectors Energy Level-2 Copper Wound |
| 180 | 630 mm2 single core cable 1.1 KV Grade, Armoured, XLPE Insulated Stranded conductor FRLS type |
| 181 | 72.5 kV, 50 c/s, 1600 Amps, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD( With one Earthing Blades) |
| 182 | Post Insulators complete in all respects as specified in the technical specification mentioned in SBD( 70 KV) |
| 183 | Single phase, 50 c/s, 72.5 kV Current Transformers (50-25-12.5/1-1-1 A or as per site specifications), 31.5 KA for one second, Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. Complete in all respects |
| 184 | Single phase, 50 c/s, outdoor, metal oxide gapless type, 60 kV (rms), class 3 arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification. |
| 185 | Galvanised Structures |
| 186 | Galvanised Nuts and Bolts |
| 187 | Supply Erection Testing and commissioning of Auxilliary transformer |
| 188 | 66/0.433 KV, 1000 KVA , 3-Phase Transformer With Bimetallic Terminal connectors Energy Level-2 Copper Wound |
| 189 | 630 mm2 single core cable 1.1 KV Grade, Armoured, XLPE Insulated Stranded conductor FRLS type |
| 190 | 72.5 kV, 50 c/s, 1600 Amps, 31.5 kA for 3 second, AC Motor Operated horizontal double break, outdoor type isolators with all accessories including solid core post insulators, auxiliaries, marshalling boxes, other essentials, complete in all respects as specified in the technical specification mentioned in SBD( With one Earthing Blades) |
| 191 | Post Insulators complete in all respects as specified in the technical specification mentioned in SBD( 70 KV) |
| 192 | Single phase, 50 c/s, 72.5 kV Current Transformers (50-25-12.5/1-1-1 A or as per site specifications), 31.5 KA for one second, Class A insulation, Burden 20 VA 3 NO PS CORE, 1 NO 5P20, 1 NO 0.2s class, Galvanised tank, including first fill of transformer oil plus 20% extra and all accessories, auxiliaries Etc. Complete in all respects |
| 193 | Single phase, 50 c/s, outdoor, metal oxide gapless type, 60 kV (rms), class 3 arresters including surge counters / monitors, insulating base and all associated accessories, auxiliaries, complete in all respects as specified in the technical specification. |
| 194 | Galvanised Structures |
| 195 | Galvanised Nuts and Bolts |
| 196 | Civil works for Aux. transformer |
| 197 | Foundation plate form for Aux. Transformer (as per Drawing) |
| 198 | Laying of 66KV Isolator foundations (as per Drawing) |
| 199 | Laying of 66KV Post Insulator foundations (as per Drawing) |
| 200 | Construction of Store Shed at Grid station Kathua |
| 201 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: |
| 202 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with:1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) |
| 203 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 204 | Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns |
| 205 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each depositedlayer by ramming and watering, lead upto 50 m and lift upto 1.5 m. |
| 206 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each depositedlayer by ramming and watering, lead upto 50 m and lift upto 1.5 m. |
| 207 | Cement concrete flooring 1:2:4 (1cement: 2 coarse sand: 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete 50 mm thick with 20mm nominal size stone aggregate. |
| 208 | Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer all complete. welded |
| 209 | Providing corrugated G. S. sheet roofing including vertical/curved surface fixed with polymer coated J or L hooks, bolts and nuts 8mm diameter withbitumen and G.I limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (upto any pitch in horizontal/vertical or curved urface)excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required 0.50 mm thick with zinc coating not less than 275 gram/m2 |
| 210 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointedtogether at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength confirming to IS:4454 part-1 and M.S. top cover of required thickness for rolling shutters. |
| 211 | Electrification of Shed |
| 212 | Construction of Toitet at Grid station Kathua |
| 213 | Earth work in excavation by manual means in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed: |
| 214 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:4:8(1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 215 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with 1:3:6(1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 216 | Reinforced cement concrete work in walls (any thickness) including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts up to floor five level including curing but excluding cost of cantering shuttering, finishing and reinforcement. 1:1½:3 (1 cement: 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size)) including providing and placing PVC pipes 100 mm dia for weep holes |
| 217 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 218 | Centering and shuttering including strutting, propping etc. and removal of form for: Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc |
| 219 | Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in : Cement mortar 1:6 ( 1 cement : 6 coarse sand) |
| 220 | Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level |
| 221 | Cement concrete flooring 1:2:4 (1cement: 2 coarse sand: 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete. |
| 222 | Cement concrete flooring 1:2:4 (1cement: 2 coarse sand: 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete. |
| 223 | Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.of angle iron size 50x5x6 |
| 224 | Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness to be specified by the manufacturers) of 1st quality conforming to IS: 15622 of approved make, laid on 20 mm thick bed of cement mortar 1: 4 ( 1 cement : 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete.e.In colour such as White, Ivory, Grey, Fume Red Brown. |
| 225 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1:3 ( 1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 226 | Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. With ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws |
| 227 | Finishing walls with water proofing cement paint of required shade on New work (two or more coats applied @ 3.84 kg/10sqm) |
| 228 | Painting of doors and windows with ready mixed synthetic enamel paint of approved brand and manufacture in all shades. |
| 229 | Providing and fixing wash basin with C.I. brackets, 15mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever required : White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar taps. |
| 230 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. |
| 231 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid , 10 liter low level white vitreous china flushing cistern and CP flush bend with fittings and C.I. brackets, 40mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required: 18.3.1 W.C. pan with ISI marked white solid plastic seat and lid. |
| 232 | Providing and fixing brass bib cock of approved quality. 15 mm nominal bore |
| 233 | Providing and fixing 15 mm nominal bore C.P. brass angle valve for basin mixer and geyser points of approved make conforming to IS : 8931 |
| 234 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to European type W.C. of quality and make as approved by Engineer - in - charge. |
| 235 | Providing and fixing PTMT grating of approved quality and colour. 100 mm nominal dia. 19.49.1 Circular type |
| 236 | Providing and fixing un plasticized P.V.C. connection pipe with PTMT nuts, collars and bush of approved quality and colour |
| 237 | Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc.: Concealed pipe including painting with anti corrosive bitumastic paint, cutting chases and making good the wall: 19.4.2.1 15 mm dia. nominal bore |
| 238 | Providing and placing on terrace polyethylene water storage tank ISI:12701 marked indicating BIS License No. with cover and suitable locking arrangement and making necessary holes for inlet ,outlet and overflow pipes but without fitting and the base support for tank (syntex,star,lotus or equivalent having valid ISI License. |
| 239 | Providing and fixing on wall face un-plasticized Rigid PVC rain water pipes conforming to IS: 13592 Type A including jointing with seal ring conforming to IS: 5382 leaving 10 mm gap for thermal expansion. (i) Single socketed pipes 110 mm diametre |
| 240 | Providing and fixing on wall face un-plasticized - PVC moulded fittings/accessories for un plasticized Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.Bend 87.5° 110 mm bend |
| 241 | Carraige of material by MT at an average distance of 20 kms: Cement |
| 242 | Aggregate |
| 243 | Bricks |
| 244 | Carraige of material by HL at an average distance of 100 mtr: Cement |
| 245 | Aggregates |
| 246 | Bricks |
| 247 | Electrification of Toilet |
| 248 | Extension of Control Room Grid Station Kathua |
| 249 | Extension of control room as per specification of SBD (as per drawing) |
| 250 | Dismantling of Existing Control room walls |
| 251 | Bore well at GSS Kathua |
| 252 | Deep drilling of bore hole 125 mm dia. as per the strata encountered including installation, testing and commissioningof M-II Hand Pump as per IS specifications by using ODEX method. The job includes extraction of MS Casing Pipe if any required during the drilling work and construction of platform as per site conditions. |
| 253 | Providing of 125 mm dia. M.S. Casing Pipe. The 125mm dia. M.S. Casing Pipe ISI marked should have thickness of 5.4mm conforming to as per IS 4270/2001 medium class (Part-1) 2004 (Heavy C Class, weight per mtrs 18.11 kg) electric resistance welded beveled ended inside beed free pipes. Two coats of anti-corrosive paint. No circumferential weld. |
| 254 | Providing, fitting,installation, testing and commissioning of Submersible,pump set along with Stand-By pump set (02-03 HP) & amp; LT 1.00 No. 210000 /No. 210,000.00 control panel.Includes Reputed make KSB,Crompton,Kirlosker,etc.). Lowering via HDPE Pipe, submersible cable, rope, clamp,nuts, bolts.Fabrication and fitting of well cap,tripod stand, chain block, and electrical connections. |
| 255 | Supply of T&P Items |
| 256 | Telescopic Ladder - Aluminum 6 m height |
| 257 | Arc Welding machine electronic (9/10 KVA) |
| 258 | Hand Drilling Machine |
| 259 | Safety belt, minimum 2 m rope length along with scaffold hook - Class-A material suitable for EHV Transmission Line maintenance staff (PN56 & 351)(Double lanyard with padded straps and supports) |
| 260 | Thermovision Camera low end |
| 261 | Digital Earth resistance meter |
| 262 | Tong tester/clamp meter AC/DC Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 16 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender