Tender For Upgradation Of Electric Transformer From 63 Kva To 250 Kva And Shifting Of Existing 63 Kva Transformer To Newly Constructed Staff Quarters And Underground Electrification Thereof At Gdc Tangmarg
Tender Value
48.46 Lakhs
Estimated cost
Bid Submission
24 Jul 2026
15 days left
EMD
96920
Bank guarantee accepted
Document Fee
795
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Baramulla → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Upgradation Of Electric Transformer From 63 Kva To 250 Kva And Shifting Of Existing 63 Kva Transformer To Newly Constructed Staff Quarters And Underground Electrification Thereof At Gdc Tangmarg
BOQ
| Sl. No. | Item Description |
| 1 | Supply,Carraige upto site, Installation, testing and Commissioning of 250 kVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Copper wound , and with LV Cable Box having detachable Aluminium Gland plate |
| 2 | Supply , Transportation and errection of 9MTR long ST Poles (410 SP-33) completely errected in the pit of 1/6th of the pole length including excavation and back filling of the pole pit. (as per REC Standard) |
| 3 | Supply, Transportation and errection of 8MTR long ST Poles (410-SP 15) completely erected in the pit of 1/6th of the pole length including excavation and back filling of the pole pit . (as per REC standard) |
| 4 | Earthing of 250 Kva substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 5 | Earthing of 100/63 Kva substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. |
| 6 | Cement bottoming of S.T poles in 1:2:4 mix 1/6th of the height of pole below the ground and 1ft above the ground cylnerical shape with circular radius 9” from the pole centre) using 40mm crushed stone aggregate mix. As per Drawing 0.48 cum/polePit =( 600x600x1600)& Tappered at the Top. (as per REC standard) for 9 MTR ST Pole |
| 7 | Cement bottoming of S.T poles in 1:2:4 mix 1/6th of the height of pole below the ground and 1ft above the ground cylnerical shape with circular radius 9” from the pole centre) using 40mm crushed stone aggregate mix. As per Drawing 0.40 cum/pole (Pit 600x600x1433.3 mm) for 8 MTR ST Pole |
| 8 | Supply, transportation and fixing of GI Channel /Angle Iron for Cross Arms, Braces, Transformer Belt, F-Top, Collers etc for Sub Station and poles (Complete Job including Nuts & Bolts and Washers) |
| 9 | Supply and fixing of 300 mm Sq Single Phase 1.1 KV Grade , PVC Insulated stranded conductor FRLS Type including Aluminum Thimbles, PG/SL Clamps etc. as per REC standard |
| 10 | Supply, Carriage up to site, Installation, testing and Commissioning of 185 Sqmm Single core cable, 1.1KV grade,XLPE unarmoured FRLS type |
| 11 | Supply, Carriage up to site, Installation, testing and Commissioning of 70 mm² Single Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type |
| 12 | Supply, Carriage up to site, Installation, testing and Commissioning of 50 mm² Single-Core Cable, 1.1kV Grade, XLPE armoured FRLS type |
| 13 | Supply, Carriage up to site, Installation, testing and Commissioning of 25 mm² Single-Core Cable,1.1kV Grade, XLPE un armoured FRLS type |
| 14 | Supply,Carraige upto site,, laying ,stringing, tensioning , binding of ACSR Weasel Conductor, (30mm2 ACSR Conductor) as per REC standard. |
| 15 | Supply and fixing of G.I pipe 150mm dia with required no. Of collars for road crossing including termination points (6'') |
| 16 | Reinstatement of roads (30 m x 0.7 m x 0.2 m thick) = 4.2 cums |
| 17 | Supply and fixing of Gapless surge arrestor, 9 KV, 10KA , LA station Type including nuts and bolts, washers, clamps etc. complete job as per REC standard. (Drilling of holes prohibited) |
| 18 | Supply and fixing of 11KV G.O set (AB Switch 3-phase,3 -pole,200A) including nuts and bolts, washers, clamps etc. complete job as per REC standard. (Drilling of holes prohibited) |
| 19 | Supply and fixing of 11KV Horn Gap fuse set 3 phase,200A including nuts and bolts, washers, clamps etc. complete job as per REC standard. (Drilling of holes prohibited) |
| 20 | Poviding and Painting of ST Poles with one coat of red oxide and two coats of aluminum paint to give an even shade using anti corrosive paint of standard brand (Nerolac/ Asian) paints) including cost of paint along with stamping on poles showing therein name of the firm date, year of instllaiton and the debitable head etc. |
| 21 | Supply, Carriage up to site, Installation, testing and Commissioning of LT Distribution Box for 63 kVA DTR with 100 Amp MCCB 3P 16 kA for incomer & 100 Amp MCCB 3P 16 kA 1 No. and 63 AmpMCCB 3P 16 kA 1 No.s for Outgoing |
| 22 | Supply, Carriage up to site, Installation, testing and Commissioning of LT Distribution Box for 250 kVA DTR with 400 Amp MCCB 3P 36 kA for incomer & 200 Amp MCCB 3P 16 kA 2 No. and 160 Amp MCCB 3P 16 kA 2 No.s for Outgoing Circuits with busbars 300 Amp |
| 23 | Supply and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 24 | Supply and fixing of Earthing of Poles Complete by Spike earthing Rod 20mm 2.5mtr long with GI strip 25x3mm (as per REC Standards) |
| 25 | Supply and fixing of HDPE Pipe Outer Dia 50 mm Inner Dia 38 mm for laying of 11kV XLPE Cable including excavation ,Back filling and laying |
| 26 | Supply, Carriage up to site, Installation, testing and Commissioning of 3 Phase, 4 Way feeder pillar with 1 No. incomer (250 Amp), 1 No. 100 A 3 Phase Out going, 4 No. 100 A Sp DP/MCCB for outgoing LT cables,Distribution feeder pillar suitable for outdoor installation made of rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 27 | Supply, Carriage up to site, Installation, testing and Commissioning of 3 Phase, 4 Way feeder pillar with 1 No. incomer (250 Amp), 2 No. 100 A 3 Phase Out going, 4 No. 100 A Sp DP/MCCB for outgoing LT cables,Distribution feeder pillar suitable for outdoor installation made of rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 28 | Supply and fixing of Aluminium Thimble 300 mm sq. |
| 29 | Supply and fixing of Aluminium Thimble 185 mm sq. |
| 30 | Supply and fixing of Aluminium Thimble 50 mm sq. |
| 31 | Supply and fixing of Aluminium Thimble 72 mm sq. |
| 32 | Supply and fixing of Low Temperature (LT) cable gland, which is designed to work in extremely cold or hot environments |
| 33 | Shifting of existing Distribution Transformer from current substation frame to fresh frame |
| 34 | Supply, Carriage up to site, Installation, testing and Commissioning of danger Plates |
| 35 | Supply, Carriage up to site, Installation, testing and Commissioning of anti-climbing devices with clamps |
| 36 | Supply, Carriage up to site, Installation, of PG clamps |
| 37 | Supply, Carriage up to site, Installation, testing and Commissioning of AI Thimbles |
| 38 | Supply, Carriage up to site, Installation, of Sign Board (2X2 feet) (Inscribed with Substation Details provided by this Division) along with required accessories like clamps, nuts and bolts etc. |
| 39 | Supply, Carriage up to site, Installation, testing and Commissioning of Sundry items like Aluminium lugs, Jumpers, Binding tapes etc. |
| 40 | Pre, during and post execution geo tagged photographic evidence consisting of 5x7 inch photographs in coffee table book (covering each pole/Sub Station) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysJul 25, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender