Power Government Departments Closing in 12 days TDR #56313878

Tender For Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Wor

Issued by Government Departments · Reasi, Jammu and Kashmir
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Jul 2026
12 days left
EMD
10.92 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Reasi → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 08-Jul-2026 TermsofPaymentCompletionperiod Other 24-Jul-2026

BOQ

Name of Work:- Creation of 6.3 MVA 33/11 KV Receiving Station at ChassanaTehsil Mahore Block Chassana of District Reasi .Scheme Code : PDDSS2627100648Important Note : All allied and associated works required for successful execution of above items of works including testing and energisation , specifically mentioned or not in above description but required at site shall be deemed to be included and covered in the quoted rates.
Sl. No. Item Description
1Survey, Supply, Installation , Testing and Commissioning for 33 kV Line BAY (LILO) of existing Darmarhi Line at Receiving Station SarBagha
233 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves,Pascal,Stelmec,Yamuna etc .
333kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ).
433kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ).
533 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase
630 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less
733 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
833 KV voltage transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase
933 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type
10CONTROL CABLES : i) 12 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a
11ii) 4 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
12iii) 2 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
13Galvanised Steel Structures
14Galvanised Nuts & Bolts
1533 KV yard concreting and metalling providing supply and laying 100 mm thick PCC1:4:8 using 20 mm normal course aggregating and spreading 100 mm three layer of 20 mm single size crushed / broken stone (One Line Bay) along with Foundation of all Electrical equipments of LILO
16Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay)
17Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
18Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
19Survey, Supply, Installation , Testing and Commissioning for 33 kV LINE BAY at Receiving Station Chassana
2033 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m
2133KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless)
2233 KV voltage transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase
2333kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
2433kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
2512 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
264 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
272 core 2.5mm2 Control Cable copper Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc.
28Galvanised Steel Structures
29Galvanised Nuts & Bolts
30Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay)
31Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
32Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
33Survey, Supply, Installation , Testing and Commissioning for TRANSFORMER BAY at Receiving Station Chassana
3433kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
3533kv C&R Panel along with O/C, E/F relays , mimic diagram, Voltmeter, Ammeter, Annunciation windows with annunciation relays, 3-Phase Tri-Vector Smart meter- % amps, DLMS Compliant including earthing. Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc .
3633KV Current Transformer (CTR 250/125-5A,1- phase multi-core, outdoor,1No. Per phase) on along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
3733 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m
3833KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless)
3933kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards.
4012 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
414 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc.
422 core 2.5mm2 Control Cable copper Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc.
43Galvanised Steel Structures
44Galvanised Nuts & Bolts
45Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay)
46Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat.
47Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering
48SITC of POWER TRANSFORMER (6.3 MVA)
4933/11kV, 3 phase ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections (6.3 MVA) as per latest IS Standards
5012 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
516 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
522 Core 2.5mm2 control cable copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc.
53SITC of 11 kV INDOOR SWITCHGEAR OF 33/11 kV SUBSTATION
5411 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal etc,:- For 6.3 MVA Power Transformer (1+4) including Smart meters Trivector.
5511kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (5Sets Station type 1 for Power Tx))
5611 kV 3- Core XLPE 185 mm² armoured, FRLS
5711 kV 3- Core XLPE 400 mm² armoured, FRLS
5811 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core(Indoor)
5911 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core (outdoor )
6011 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (indoor)
6111 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (outdoor)
6211 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch.
6311kV DO set , AB Switch 3-Phase, 3-Pole, 200 Amp
64Galvanised iron of sorts
6509 Mtr. Long Pole(ST-410 SP33)
6695 mm² PVC LT Cable 4 Core, armoured, FRLS
67Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole
68Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip for ST poles
69100 KVA Auxillary Transformer
70Earthing for Auxillary Transformer (complete as per REC standards)
71MCCB 200 Amp with box
72COMMON MISCELLANEOUS WORKS
73HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room
74Providing & Laying of Earthmat by Using G.I. Flat of Size 50 mm x 8mm as grounding Conductor.The mesh Size shall 2 m x 2 m.The Burial Depth of G.I. Flat Shall be minimum 600 mm.The work involves the excavation of trenches for burial of grounding flat,Laying of G.I.Flat including welding & Backfilling of Trenches
75Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip.
76Supply, Errection, Testing & commisioning of Battery Bank 32v 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant of make Exide Amaron or Tata etc.
77Supply, Errection, Testing & commisioning of Float-Cum-boost Charger with full wave rectification for 220v, 1 Phase 50HZ AC input supply suitable for charging of Battery Bank 32V, 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant.
78Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories
79Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories
80Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room (with ISI mark)
813 Sand Bucket Fire Extingiusher including MS stand
82Civil /Misc Works
83Earthfilling/Cutting upto desired FGL (As decieded by Engineer incharge during detailed Engineering)by Way of Removing Weeds,Wild Grass and endulation if any including disposal of surplus material
84Construction of 3000 mm wide Road,with 300 mm thick dry well compacted local soil of 95% Procter density ,with 100 mm thk P.C.C. 1:4:8 Layer in middle,with 100 mm thk R.C.C. (1:2:4) in top layer with 8 mm tor steel @ 300 mm c/c bothways in middle of top layer shall be provided.Polythene sheet of thk 125 micron shall be provided between middle & Top Layer.Expansion joint shall be provided at every 3000 m length.115 MM Thk side brick masonary shall be provided on both sides of road. (Reference Drawing Enclosed)
85Development of Side drains of road 300 mm x 300 mm section with side walls & floor 150 thk P.C.C. 1:3:6 & 12 mm thk plaster 1:4 complete finished job
86Ornamental Landscapping of Free land/space along with Plantation of ornamental trees & Grass complete job to the satisfaction of engineer in charge
87Compound Walling of identified land by way of Mass Concrete in Foundations and 228 mm bricks of 2 metre height and plastering. (150 RM)
881. Construction of R.C.C. Pillars (M-20) with square footing of size 1300 x 1300 x 200 mm & Pedastal of Size 230 x 300 x 2800 mm.The reinforcement in footing shall be 10 mm dia tor steel steel at 200 c/c bothways in bottom of raft & 8 mm dia tor steel at 200 c/c both ways at top of raft.4 no 12 dia tor steel rods shall be provided in pedastal with 8 mm dia stirups at 200 c/c.The rates shall include cost of excavation,all material,Shuttering etc. R.C.C. Pillars shall be spaced @ 3000 mm c/c.
892. Plinth Beam of size 230mm x 300 mm with four 12 mm dia tor steel members with 8 mm dia stirups at 200 c/c including cost of form work
903. Brick Masonary work (Cement sand mortar 1:5) 230 mm thk & 2000 mm high.
914. 12 mm thk Cement plaster 1:4 on both sides of Brick wall
925. Providing & Fixing of M.S.Angle 50mm x 50mmx 6mm Y shaped Posts embeded in R.C.C. Pockets of size 100 mm x 100 mm x 300 mm
936. Providing & Fixing of 3 rows of Barbed wire on Angular Posts
94Galvanized Chain link Fencing of 33 kV Yard of Substation by way of Mass Concrete in Foundations and chain link fencing of 6 ft height (Size 75 mm x 75 mm made of G.I.Wire 3.15 mm in diamond pattern) using Fencing posts of M.S.angle size 65x65x6mm embedded in 1:2:4 C.C. Block of Size 400 mm x 400 mm x1000m at an average spacing of 2.5 m c/c.The chain Link mesh fencing shall be secured to M.S.Angle post with flat iron strip of size 50x6 mm on both sides.There shall be a provision of 3 rows of 2 strand Barbed wire on top of fencing post. at GMC Receiving Station and dairy Farm Receiving Station Line bay.
95Trench Excavation between C.C.Blocks holding angle Posts of size 300 mm x 400 mm ,Laying of 75 mm Thk lean Pad 1:4:8 ,Plum Mass concrete in 1:3:6(30% Boulders) of height 425 mm & width 400 mm with 50 mm Band Coping on Top in C.C.1:2:4 complete job including cost of shuttering & Curing.
96Providing & Fixing of double frame Gate(Min 4000 mm wide & 2000 m high) with 50 dia G.I.Tube in outer frame & 10mm/20 mm Sq rods welded to tubular frame (Final Design to be approved by Engineer incharge).There shall be provision of drop Bolts of 16 mm dia M.S. Rod & suitable Concrete Pockets for holding Bolts.Wheels at bottom & flat arrangement for smooth opening & closing shall be provided
97Construction of R.C.C. Pillars for holding of gate including cost of material & labour.(Design of Reinforcement & sizing shall be finalised by Enginer incharge
98RCC Cable trench (1:2:4) including excavation and disposal of un-wanted soil. for laying of 11 KV XLPE Power Cable and control cable from power transformer, VCB and other equipments to control room and for outgoing cables from control room to outgoing structures including cable duct covers (cable duct covers should be covered with Angle Frames using angle 45x45x5 mm and 8 mm Tar Steel @ 200 c/c & M-20 Concrete)
99BUILDING: A. Control Room Buildingon ground floor complete with Column and Beam structures with 1 no J.E. Room , 1 Store room, 1 Battery Room and a main hall including aluminium windows, cable ducts for power and control cable, Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures)White Washing of entire building , painting of doors and windows etc. Overhead /undergroung water Storage tanks . 2 nos of office tables and 6 nos of chairs , staircase . Water Supply . Septic Tank complete with Sanitary Fittings including kota stone floor .complete in all respects
100BUILDING:B .Staff Quarters on 1st floor with Column and Beam structures including Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures) White Washing of entire building Complete in all respectsainting of doors and windows etc. Overhead water Storage tanks . Pantry Room with all the Fittings. Water Supply . including marble flooring ,Furniture(including 2 single Beds, 4 Chairs, 2 table, Matress, Curtains)(Note: The Contractor shall submit the building drawing in all respects i.e. structral / architechural prepared by authorised Architect for approval from the dept for execution of works.)
10133/11 kV Power Transformer Foundation as per REC standards
102Auxillary Transformer Foundation as per REC standards
10333 kV Equipment Foundation & Gantry foundation as per REC standards
10433 KV Yard Concreting and metalling with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick.
10533 kV Yard Lightening ( 100 Wt LEDs on 9 mtr ST poles ) complete with earthing , cement bottoming GI brackets, control box , cable etc (5 Nos.)
106Safety Tool kit
107Crimping Tool Kit complete set for cable of different sizes upto 630 sqmm
108Rubber Mats( 2 mtr x 2 mtr x 25 mm)
109Main Gate
110Conventional Earthing -GI Plate Earthing with 600mm X 600 mm X 6 mm, GI Plate, GI Flat 50 x 6 mm, GI Pipe, 40 mm Dia with Charcoal salt & good earth 10 ft deep pit etc. as per REC standards . Complete job
11133 KV Hand Gloves(set of 2)
11211 KV Hand Gloves(set of 2)
113RainCoats
114Safety Belt
115Gum boots
116Safety Helmet for electrician
117Digital Meggar 5000 mega Ohm
118Earth Resistance Tester
119Emergency light/ Torch 5 Watt chargeable
120Multimeter
12133KV high voltage live phase detector
122Extendable Aluminium Ladder 25 feet
123Aluminium Bus Bar 75 x 10 mm
124GI Flat 50 x 6 mm and 20 x 5 mm for risers and earthing of cable trenches and yard fencing.
125Earthing Rod (set of 3)
126Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 33 kV LINE ON 11 Mtr. ST POLES ( 12 KM approx)
127Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
128GI Channel iron X-arm of different sizes including clamps,Ties and braces for multi pole structures
129GI Channel iron V cross-arm with top bracket of different sizes including clamps,Ties and braces for single pole structures
13033kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
13133kV Polymeric composite Disc Insulator with fitting 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
132PG clamps for 100 mm2 ACSR Conductor
133Galvinized Nuts and Bolts
134Danger Plates with Clamps
135Anti-Climbing Device with Clamps
136Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip.
137Painting of Poles with Red Oxide and aluminium paint (min 2 coats each)
138Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles
139Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
140100 mm2 ACSR conductor
141Guard netting
142Creation of Isolation points along the line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles and MS Steel etc. Complete job.
143Out Sourcing of Manpower for Manning and operation of 33/11 KV R/Stn. Along with allied 33 KV Line for 3 Years
144Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 11 kV LINE ON 8 METER ST POLES ( 2 KM approx) To be vetted by AEE Sub Div. Darmarhi ED- Reasi
145Supply, Transportation, Erection of 8 Mtr Long ST Poles (ST410-SP15) including excavation of pit and back filling of soil & consolidating by ramming, watering etc.
146GI Channel iron X-arm of different sizes including clamps,Ties and braces
147GI Channel iron V cross-arm including clamps
14811kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
14911V Polymeric composite Disc Insulator with fitting 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
150PG clamps for 50 mm2 ACSR Conductor
151Galvinized Nuts and Bolts
152Danger Plates with Clamps
153Anti-Climbing Device with Clamps
154Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip.
155Painting of Poles with Red Oxide and aluminium paint (min 2 coats each)
156Cement bottoming 1:2:4 mix as per REC standards .45cum/pole (to be done during erection of poles)
157Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
15850 mm2 ACSR conductor
159Guard netting
160Creation of Isolation points along the line Complete job. Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0

AI Tender Summary

OUR REF NO 56313878
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 24-07-2026
Authority
Authority Name Power Development Department
Work Description Tender for Creation Of 6.3 Mva 33/11 Kv Receiving Station At Chassanatehsil Mahore Block Chassana Of District Reasi .Scheme Code : Pddss2627100648important Note : All Allied And Associated Works Required For Successful Execution Of Above Items Of Works Including Testing And Energisation , Specifically Mentioned Or Not In Above Description But Required At Site Shall Be Deemed To Be Included And Covered In The Quoted Rates.
Basic Detail
Tender No 18 of 2026-27
Bidding Type Tender
Location
City Reasi
State Jammu and Kashmir
Key Dates
Publish Date 08 Jul 2026
Submission Date 24 Jul 2026
Open Date 01 Jan 0001
Finance
Tender Value Ref. Documents
Tender Fee 5000
EMD 10.92 Lakhs
Exemption Not Available
Document List
315da60f-0a53-41c9-b429-0a7c8c592768.html
BOQ_1019001.xls
Checklist.pdf
Tendernotice_1.pdf
SBDChassana.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 08, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 24, 2026
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Upcoming · 12 days
Jul 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 12 days

Tender Documents

Download All (ZIP) ↓
html

315da60f-0a53-41c9-b429-0a7c8c592768.html

xls

BOQ_1019001.xls

pdf

Checklist.pdf

pdf

Tendernotice_1.pdf

pdf

SBDChassana.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders