Tender For Provision Of Fire Down Comer System Booster Pump, Fire Detection And Pa System, Fire Extinguisher And Signages At Chc Building Botalama Buildings.
Tender Value
34.61 Lakhs
Estimated cost
Bid Submission
13 Jul 2026
8 days left
EMD
34700
Bank guarantee accepted
Document Fee
6000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Khordha → Odisha
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Fire Down Comer System Booster Pump, Fire Detection And Pa System, Fire Extinguisher And Signages At Chc Building Botalama Buildings.
BOQ
| Sl. No. | Item Description |
| 1 | TERRACE PIPING & ACCESSORIES -:Supply and Fixing of 1 Nos of 5000 ltr.triple layer plastic water storage tank for fire fighting hydrant system to be placed at terace level.Make:- Sinttex/Plasto |
| 2 | Supplying, installation, testing and commissioning of Electric Motor Driven Pressurization Terrace Pump having discharge of 450 LPM at 35 Mtr head complete with Pump Set, Electric Motor suitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame, with RCC foundation for motor as per the manufacturer's standard installation specification.The installation height of motor must be above 450 mm. Make-Wilo/KSB/Kirloskar/Grundfoss ( For Eye hospital,Trauma care & Infectious Ward) |
| 3 | Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of One (1)- 63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB, Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable for 7.5 HP motor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.as per direction of engineer in charge Control panel for fire pumps for auto action.make-Legrand/schneider/Siemens/ABB |
| 4 | Supplying, Installing, Testing and commissioning of 1100 V GRADE POWER/CONTROL CABLES :SITC of FRLS, PVC outer sheateh, steel armoured, aluminium, 1100v grade power cables with glands etc. The minimum size of the cables shall as mentioned below as per direction of engineer in charge. Size 4C x 16 Sqmm. Make - Polycab / KEI/Gloster/RR kabel/Havells/Finolex |
| 5 | 2 C x 1.5 Sqmm copper |
| 6 | Supply and laying of 6 swg GI wire on surface or recess as per the direction of Engineer-in-charge. |
| 7 | Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C.Make-Zoloto/AUDCO/Leader. 100 mm |
| 8 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. Make-Zoloto/AUDCO/Leader 100 mm |
| 9 | Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge.Make-Danfoss/Grundfoss/Indfoss |
| 10 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge.Make-H.Guru/G.Guru |
| 11 | Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. |
| 12 | SITC of Ball valve of 15 mm dia Make-Zoloto/Audco/Leader |
| 13 | Providing and fixing hydrant stand posts of 80 mm dia. With flanges and accessories and supply, fixing 63 mm dia SS Single headed Hydrant Valve in the courtyard IS:5290 Including 2 coats of approved enamel paint (red) over a coat of primer, complete with 2.1/2 Morris pattern instaneous couplings, etc. complete..Make-Minimax/Newage/Fireshield/Safex |
| 14 | Providing & fixing 63mm dia CP hose pipe as per IS 8423 TYPE A TAC/ LFA approved of 15 mtr. standard length of approved pattern and size including SS male and female Coupling duly bound with copper wire etc. complete.Make-Minimax/Newage/Fireshield/Safex |
| 15 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 16 | Providing and fixing Stainless Steel standard branch pipe dia 63 mm inlet with nozzle 20 mm dia outlet conforming to IS : 903, suitable for instantaneous connections to hose coupling etc. as required:.Make-Minimax/Newage/Fireshield/Safex |
| 17 | Providing and fixing TAC approved fire hose cabinet to house fire hydrant & hose, including all other related accerrories fabricated from M.S. sheet (16 Gauge) of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 nos. hoses. The hose box size is 750 mm x 600 mm x 300 mm . |
| 18 | Supplying & fixing first aid fire hose reel of thermoplast braided suitably reinforced 20 mm size & 30 m standard length with 5 mm tapering branch nozzle, 25mm dia. Pipe to connect to riser with cut off ball valve attachment. Hose to be swinging type wall mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts (Including drum and swivel arrangement) etc complete..Make-Minimax/Newage/Fireshield/Safex |
| 19 | Supplying, installation testing and commissioning of the following C class MS Pipe as per IS1239 for underground/over ground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. Complete to make the system operative as required by LFA / TAC authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for overheads pipes and providing and fixing pyp kote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc.Make-Tata/Jindal/Sail.Complete as per ASTM standards/IS: 10221 for corrosion protection of pipes for the underground installation.Note: The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete. size 100mm dia. |
| 20 | 80 mm dia. |
| 21 | 25 mm nominal dia |
| 22 | Supply, installing, testing and commissioning of 2 way fire brigade connection of cast iron body with 2 Nos. Gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for 100 mm dia MS pipe connection, conforming to IS904 as reqd. Make -Zoloto / Leader/Audco. |
| 23 | EXTERNAL HYDRANT SYSTEM-:Excavations for pipelines in trench and pit in open areas where disposal or surplus earth is done along the alignment, including trimming and dressing sides, leveling of beds of trenches to correct grades, cutting joint holes, refilling consolidation and dewatering of refilling in 15 cm layers & restoration & unmettalled or unpaved surface to it's original condition. The rate including the cost of necessary timbering dewatering of drain water, diversion of traffic, night signals, fixing caution boars, watching fencing etc.Upto 1.5m depth in all classes of soil |
| 24 | Supplying,installation,testing & commissioning of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge. |
| 25 | Supplying and laying 25 mm X 5 mm G.l strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm) |
| 26 | Supply and Fixing of Structural steel like MS Beam (ISMB) 200 X 100, MS Channel (ISMC) 100 X 50 X 5, MS Angle ISA 65 X 65 X 6, MS Angle ISA 40 X 40 X 5, MS Sheet 2500 mm x 1250 mm x 2 mm & Plate 200 x 200 x 12 mm including one coats of primer and two coats of signal red colour with all accessories at terrace level for foundation of 5,000 ltr PVC tank. Make: SAIL/RINL/MSP |
| 27 | GI Shed over fire pump to protect the fire pump from rain water in terace level. |
| 28 | Supply and Installationof u pvc (32mm) Pipe & Solvent |
| 29 | Pvc ball valve 32 mm |
| 30 | Supply and Installation of GI hex nipple both side threaded for tank connection 100 mm |
| 31 | Supply and Installation of GI socket 100 mm |
| 32 | Supply and installation of float valve |
| 33 | SIGNAGES: SITC flexyl of Photoluminescent based Glow-in-the-dark sheeting with luminious properties enclosed in a weather-proof UV stabilized film with UV screen printing by imported inks pasted over 3 mm Thick Cast Acrylic Sheet with the Protection of 3 mm Thick Cast Acrylic from Front side with stud type mirror screw with lifespan of 5 years, visible upto 4-6 hrs in total darkness for floor indication, fire exit, hydrant, hose reel, fire extinguisher, MCP, fire alarm panel, in case of fire, lift, alarm valve signages |
| 34 | SIGNAGES: SITC flexyl of Photoluminescent based Glow-in-the-dark sheeting with luminious properties enclosed in a weather-proof UV stabilized film with UV screen printing by imported inks pasted over 5 mm Thick Cast Acrylic Sheet with the Protection of 3 mm Thick Cast Acrylic from Front side with stud type mirror screw with lifespan of 5 years, visible upto 4-6 hrs in total darkness for fire evacuation plan, fire action(For all floors) |
| 35 | Fire detection system-Supply, installing, testing and commissioning of of 2 Loop Network Panel Micro processor based 2 wire fault tolerant loop,with inbuilt network port (each loop accessing 99 or more detectors and 99 or more modules ) fire alarm/detection control panel. The Panel shall have 10000 or more event log history . Panel shall be capable of having 1600 or more configurable zones .The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module when ever any alarm is triggered. The panel shall have 7 Inch Touch Screen unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects.The Panel Shallbe Sheet Steel Painted, selaed to IP30. The Panel Shall have provision for 40 or more Zones with Individual LED Indicators expdable upto 200 Zones or higher. The panel shall have a built in power supply and battery charger along with maintenance free 7 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required.and as per specifications. conforming to BS5839 Standards and Duly Approved by EN54 The panel shall support detection logics like coincidence & verification detections for the false alarm management. The Panel shall adjust the sensitivity between day and night to maintain the better detection/reponse time. The Panel shall be capabale of programming through PC ; Touch Screen of USB .This panel having facility of MODBUS protocol over TCP/IP for BMS integration.The panel should have provision for inbuilt RJ45 connection terminal for connecting to the LAN with inbuilt BACNET Protocol. Make- Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 36 | Supplying, installing, testing and commissioning of OEM make ( 2 loop )Cloud based service through universal gateway, which shall be enabled through internet. Remote health monitoring solution shall utilize cloud based software-as-a-service web application & supplementary network gateway hardware. System shall provide secure web access to cloud-based web application using any of the web browsers like Google Chrome (preferable), Internet Explorer etc. from any computer/ tablet/ smartphone connected over internet via defined credentials username and password. It shall also have the facility to monitor the cloud service over the mobile apps. The cloud-based web application shall capture all fire alarm system data points as received from the system via supplementary gateway hardware of the same make as Fire Alarm Panel. The software shall display real time view of fire system effectiveness, multi-location unified view, custom dashboard, device level information, scheduled reporting, e-mail of critical alarms. The cloud service shall be capable of monitoring 250000 datapoints scattered across multiple install bases spread across multiple geographical locations. The Gateway Card shall be UL Listed.It should have 5 nos. or more user license. Internet/Wi-Fi Connectivity Required.The cost is inclusive of 2 years subscription charges.Software and panel shall be of same make. |
| 37 | Supplying, installing, testing and commissioning of adressable multi sense smoke detector with inbuilt isolator module/isolator base,base, junction box and other accessories.Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 38 | Supplying, installing, testing and commissioning of addressable Manual call point with built in Monitor Module with all accessories complete. The device shall be UL/EN/FM approved..Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider |
| 39 | Supplying, installing, testing and commissioning of addressable Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |
| 40 | Supplying, installing, testing and commissioning of addressable Hooter at 85 dBA @ 3m for Audible annunciation and 75cd flashing at 1 Hz for visual indication with all accessories etc., complete. Make-Honeywell(MAX) /Siemens/Bosch/Edward/NOTIFIER/GST/Schneider Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 13, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysJul 14, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer