Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #56299066

Tender For Special Repair/ Replacement Of Lt Feeder Pillar Box/ Panel, Switch Gear With Connected Works At Af Stn Jalahalli

Issued by Statutory Bodies & Commissions/Committees · Bangalore, Karnataka
Tender Value
Ref. Documents
Estimated cost
Bid Submission
24 Jul 2026
17 days left
EMD
95400
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bangalore → Karnataka
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Special Repair/ Replacement Of Lt Feeder Pillar Box/ Panel, Switch Gear With Connected Works At Af Stn Jalahalli

BOQ

Name of Work:- SPECIAL REPAIR/ REPLACEMENT OF LT FEEDER PILLAR BOX/ PANEL, SWITCH GEAR WITH CONNECTED WORKS AT AF STN JALAHALLI
Sl. No. Item Description
1Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth and getting out in soft/loose soil , complete all as specified and directed.
2Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed.
3Removing surplus excavated material (soil) not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed.
4Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
5Material and labour for well burnt bricks ‘B’ class as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed.
6Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :-(i) Earth work and excavation in any type of soil(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick ,complete all as specified and as directed.(iii) Removing excavated material out side MD land.(iv) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
7Supply & fixing GI tubing light grade 100 mm dia fixed on walls/pole/ laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
8Material and labour for Boring of holes under road, pavement hard standings by trenchless technology using ultra sound technique and necessary machine including supply of HDPE pipes upto 150 mm dia suitable for 0.4 Mpa working pressure, complete all as specified and directed.
9Material and labour for 3 ½ core 95 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
10Material and labour for 3 ½ core 185 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
11Material and labour for making straight through joint with suitable jointing kit consisting of water proof adhesives for UG cable of size 3.50 core 120 Sqmm to 185 Sqmm, complete all as specified and directed.
12Supply, installation, commissioning and testing of floor mounted, free standing OEM made type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of CPRI approved IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate for bedding upto a height of 45 CM above ground level, complete all as specified and directed and comprising of the following:- Please Enable Macros to View BoQ information
13Supply, installation, commissioning and testing of floor mounted, free standing OEM made type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of CPRI approved IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate for bedding upto a height of 45 CM above ground level, complete all as specified and directed and comprising of the following:- Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56299066
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 24-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repair/ Replacement Of Lt Feeder Pillar Box/ Panel, Switch Gear With Connected Works At Af Stn Jalahalli
Basic Detail
Tender No 8364/E8
Bidding Type Tender
Location
City Bangalore
State Karnataka
Key Dates
Publish Date 03 Jul 2026
Submission Date 24 Jul 2026
Open Date 31 Jul 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 95400
Exemption Available
Document List
8364GENPAGE.pdf
8364PS.pdf
BOQ_869347.xls
d9f401a5-1b01-4f78-a130-2339ef20d633.html
Tendernotice_1 (2).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 03, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Jul 31, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 24 days

Tender Documents

Download All (ZIP) ↓
pdf

8364GENPAGE.pdf

pdf

8364PS.pdf

xls

BOQ_869347.xls

html

d9f401a5-1b01-4f78-a130-2339ef20d633.html

pdf

Tendernotice_1 (2).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders