Tender For Work Of Construction Of 33 Kv Lok Bandhu Bay At 132 Kv Substation Mohan Road Lucknow Under Etd-I, Lucknow
Tender Value
5.15 Lakhs
Estimated cost
Bid Submission
16 Jul 2026
3 days left
EMD
5200
Bank guarantee accepted
Document Fee
590
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Lucknow → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Work Of Construction Of 33 Kv Lok Bandhu Bay At 132 Kv Substation Mohan Road Lucknow Under Etd-I, Lucknow
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 04-Jul-2026 | Technical | Technical Bid | 16-Jul-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | SUPPLY OF MATERIAL |
| 2 | 75X10 mm MS Flat |
| 3 | 50X06 mm MS Flat |
| 4 | 25X06 mm MS Flat |
| 5 | P.G. Clamp made of LM - 6 Alloy having suitable for ACSR Moose to 'Panther' Conductor, complete with Bolt - Nut - Washers (4 No. Nut & Bolts), as per sample. |
| 6 | P.G. Clamp made of LM - 6 Alloy having suitable for ACSR Moose to 'Moose' Conductor, complete with Bolt - Nut - Washers (4 No. Nut & Bolts), as per sample. |
| 7 | P.G. Clamp made of LM - 6 Alloy having suitable for ACSR 'Panther' to 'Panther' Conductor, complete with Bolt - Nut - Washers (4 No. Nut & Bolts), as per sample. |
| 8 | Spacer made of Aluminum Alloy for ACSR 'Panther' Conductor with 100 mm spacing. |
| 9 | Spacer made of Aluminum Alloy for ACSR 'Moose' Conductor with 250 mm spacing. |
| 10 | Single Tension Fitting Suitable for Twin ACSR Moose Conductor |
| 11 | ERECTION OF MATERIAL |
| 12 | Erection of main and auxiliary structures |
| 13 | Main & Auxiliary Structure Lattice type |
| 14 | Erection of following Equipments as per instruction manual and technical specifications including shifting of materials from Central Stores to Erection Site including all associated works. |
| 15 | 33 KV Vacuum Circuit Breaker with Structure |
| 16 | 33 KV CT Ratio 800-400/1A, 3Core with Terminal Connector |
| 17 | 33 KV Current Transformer Junction Box |
| 18 | 33 KV PT with Terminal Connector |
| 19 | 33 KV PT Junction Box |
| 20 | 33 KV Bus Isolator with post insulator(manual) W/O E/S |
| 21 | 33 KV Post Insulator |
| 22 | 33 KV Line Isolator with post insulator(manual) With E/S |
| 23 | Jumpering, Stringing, Destringing etc. of various Equipments/ Bus Sections(Main bus & jack bus) |
| 24 | Jumpering of various equipments with Twin ACSR \\"Panther Conductor \\" in new 33 KV 'Lok Vandhu Bay' after due cutting and bending of conductor and fixing & tightening etc of the Conductor/ Clamps/Connectors/Spacers etc. |
| 25 | Laying of following sizes Control Cables in the Cable Trenches from Control and Relay Panels in Control Room to various Equipments, Junction Box etc. in Swithcyard as per cable schedule, including carriage of Cable Drums from Stores to work site & shifting back to stores including allother associated works required for the satisfactorily completion of the Job as per technical specification. |
| 26 | Laying of 2X2.5 sq. mm size Control Cable |
| 27 | Laying of 4X2.5 sq. mm size Control Cable |
| 28 | Laying of 6X2.5 sq. mm size Control Cable |
| 29 | Laying of 10X2.5 sq. mm size Control Cable |
| 30 | Interconnection & termination of of the above laid control cables between Control and Relay Panels & erected equipments i.e. CB, CT, CT Junction Box, PT, PT Junction, box.,isloator junction box etc. Including making necessary holes in Gland Plates or Boxes whereever required along with supply of Cable glands of appropriate size and providing of Ferrules for each core of the cables & its termination with crimping type Copper Lugs alongwith preparation of Interconnection Drawing and Commissioning of the Panel/ Feeders in co-ordination with T&C Wing includoing providing 02 sets of Hard Copies of as executed Interconnection Drawing including all other associated works required for the satisfactorily completion of the Job as per technical specification. (01 Job for Each Bay) |
| 31 | Cutting, Straightening and Laying 700 mm below inside ground & above ground of 25*6mm,50X6 mm & 75X10 mm size M.S. Flats (to be provided by the department) as per requirement for Earthing of newly erected equipments and Structures as above including welding with main Earthmat and with the object to be earthed including excavation, backfilling, painting of the Earthmat above groung level in Bus Green colour including all other associated works to complete the job satisfactorily as per Technical Specifications. |
| 32 | Earthing of aux. Structures and Equipments with 75X6 mm size M.S. Flat |
| 33 | Earthing of aux. Structures and Equipments with 50X6 mm size M.S. Flat |
| 34 | Earthing of cable trenches with 25 mm x 6 mm size M.S. Flat |
| 35 | Painting of Earthing strips above ground level with one coat of Red oxide and two coat of synthetic/ enamel paint and with black Bitumen paint below ground level as per etails below: |
| 36 | 75x10 mm (in green color) |
| 37 | 50x6 mm (in green color) |
| 38 | 25x6 mm (in black color) |
| 39 | Following Works are to be carried out for integration of 01 No. 33 KV Bay with existing Siertiens make SCADA system and all associated works at 132 KV Sub Station Mohan Road, Lucknow with all cost of men, misc consumables, T&P etc. to complete the job satisfactorily as per direction of the Supervising Engineer |
| 40 | 33 KV Bay (01 No.) Intergration at the existing Siemens make IEC 61850 based SCADA System |
| 41 | Configuration of ICD/ CID files of the Siemens make SIPROTEC 7SJ64 / ABB REF 620 / Siemens make REF 615 BCPU relay |
| 42 | Erection of New 33 KV Triple Feeder C&R Panel in control room of 132 Kv S/S including grouting,earthing & termination of control pannel as per cable Schedules including providing & fixing of Cable glands of appropriates sizes and ferrules etc. with all associated works as per technical specifications. |
| 43 | Stringing of Twin Moose Main Bus , the work laying ,Stringing of conductor,fitting of tension clamp,hoisting of isolator,cutting of conductor & also shifting of all material from store site to switchyard site and all other associated work,conductor fitting & disc insulator etc. shall be provided by department. |
| 44 | Laying & stringing of 33KV Main Bus of Twin Moose conductor having Existing length. (01 No. each Phase) |
| 45 | DISMENTALLING OF MATERIAL |
| 46 | Dismnteling of main Structure and equipment |
| 47 | Dismantling of 33kV PT |
| 48 | Dismantling of 33kV Bus section Isolator |
| 49 | Main & Auxiliary Structure Lattice type |
| 50 | Destring of 33kV Main Bus of Twin Moose Conductor for making Place of 33kV Lok Bandhu Bay(one no. each Phase) |
| 51 | Following Works are to be carried out at 132 KV Sub Station Mohan Road, Lucknow for the constrution of 33KV Lok Bandhu bay along with associated works including all cost of men, misc consumables, T&P etc. to complete the job satisfactory. |
| 52 | Safe loading,carriage of various equipments like- Control cable of various size,MS flat of variours size,33KV CT,33KV isolator,ACSR conductor etc.required for construction of 33KV Lok Bandhu Bay from various substation in lucknow to 132KV Substation Mohan Road , Lucknow and unloading at Storage place as per direction of supervising engineer including Cost of hydra,carriage Vehicle,man,misc. consumables,Tnp,making coil of cables before Loading etc.required for satisfactory completion of job (01 job for all items). |
| 53 | Proper Shifting, sorting, counting weighing, loading & stacking of Dismanteling Stubs/ Gantry Structures by the contracotr from site to Storage Location. |
| 54 | Proper Shifting, sorting, counting weighing, loading & stacking of Stubs/ Gantry Structures on Trucks arranged by the contracotr including transportation from storage location to the loading site. |
| 55 | Safe carriage of Auxiliary Structures loaded on trucks duly arranged by the Contractor from Stockyard/Stores of E.F.U. Naini Allahabad/any other Sub Station to 132 KV S/S Mohan Road (approx. dist 240 km), with all due care of safety & precautions during transit required for the job including the fare/ toll tax etc. of all the trucks. |
| 56 | Unloading of Structures at the 132 KV S/S Mohan Road including transportation of the structures from the unloading site to the main work site. |
| 57 | Supply & fixing of 150 Watt LED street light luminaries (outdoor type) of PHILIPS/CROMPTON GREAVES/ HAVELLS/BAJAJ make in single piece aluminium die cast, at designated height on gantry/beam on G.I. Light Bracket including guiding the cable to light fixtures from inside pipe/bracket, cable terminations and it’s testing and commissioning and earthing with 12 SWG Wire. |
| 58 | Supply & fixing of of G.I. light Bracket duly made of 54 mm dia/dia suitable for Sl. No. 1(a) , 1.2 meter long 'B' class GI pipe and bent at one end by Quarter Circle in 1.0 meter length at an angle of 30 degrees for fixing 120 watt LED Light fitting on Gantry with the help of G.I./ M.S. clamps as required (01 job per Light). |
| 59 | Supply &fixing of Lighting Junction Box of size 280X225X150 mm duly made of 16 SWG M.S. BP sheet and painted with smoke Grey Colour Synthetic Enamel Paint duly fitted with 01 no. 6 Amp SP MCB on anodized M.S. channel, 01 no. of Bakelite Fuse Fitting with 6 Amp capacity , 1 No. 6A Capacity NS6 type HRC Fuse, 01 no. Copper Neutral Link, Bakelite Terminal Block of 04 Terminals, Cable Glands suitable for 2C/4C X2.5 sq. mm size Including Incoming/ Outgoing Cables etc. and installation of Junction Box. on G.I Pipe Light Pole at designated height with the help of suitable M.S. Clamps alongwith Earthing of Junction Box. with 12 SWG G.I. Wire pole including cable Terminations with satisfacory Testing and Commissioning. |
| 60 | Supply & Fixing of Name Plates made of 2 mm thick Aluminium Sheet covered with 3M HIP Retro Reflective Sheet of following size with details/name written as per prescribed colour scheme to be fixed with the help of Nuts and Bolts at already installed Equipments' Structures in the Switchyard with all cost of Plates, Nut & Bolts, misc.materials like chains in case of breakdownshutdown plates etc., T&P and Labour as per Technical Specificaions & direction of the concerned Supervising Engineer: |
| 61 | Plates of size 300 mm X 200 mm |
| 62 | Providing & Fixing of 'R', 'Y' & 'B' Phase Plate Sets consisting of one Plate of Red, Yellow, Blue Colours in each Set & Plates of dia 250 mm duly made of 2 mm thick Aluminium Sheet with face fully covered in Red, Yellow & Blue Colours with 3M HIP Retro Reflective Sheet and the Phase Plates Set to be fixed with the help of Nuts and Bolts at already installed Equipments' Structures in the Switchyard with all cost of Plates, Nut & Bolts, misc.materials, T&P and Labour as per Technical Specificaions & direction of the concerned Supervising Engineer. |
| 63 | Supply and installation of Fiber Optics patch cords/LIU's and splicing work to make BCUs communication with existing fibre ring system Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 04, 2026
11:30 IST
Tender Published
Tender notice published.
Completed
Jul 16, 2026
18:00 IST
Corrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 3 daysJul 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender