Educational and Research Institute Government Departments Closing in 15 days TDR #56284988

Tender For 12 Months Annual Term Contract For Day-To-Day Electrical Works Execution In All The Buildings At Aiims Mangalagiri C Us, Aiims Mangalagiri, Andhra Pradesh.

Issued by Government Departments · Guntur, Andhra Pradesh
Tender Value
85 Lakhs
Estimated cost
Bid Submission
18 Jul 2026
15 days left
EMD
1.70 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Guntur → Andhra Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for 12 Months Annual Term Contract For Day-To-Day Electrical Works Execution In All The Buildings At Aiims Mangalagiri C Us, Aiims Mangalagiri, Andhra Pradesh.

BOQ

Name of Work:- 12 Months Annual Term Contract for Day-to-Day Electrical works execution in all the buildings at AIIMS Mangalagiri C us, AIIMS Mangalagiri, Andhra Pradesh.
Sl. No. Item Description
1CHAPTER : 1 (Wiring \ switches\sockets \ PVC conduit)
2Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. (Group-C)
3Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. (Group-C)
4Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
5Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
6Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 2 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
7Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.
82 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
92 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
102X4sq.mm+1X4sq. mm earth wire
112X 6sq.mm+ 1 X6sq. mm earth wire
122X 10sq.mm + 1X 6 sq. mm earth wire
132X 16 sq. mm +1 X 6 sq. mm earth wire
144X 4sq.mm+ 2X 4 sq. mm earth wire
154 X 6 sq. mm + 2 X 6 sq. mm earth wire
164 X 10 sq. mm + 2 X 6 sq. mm earth wire
174 X 16 sq. mm + 2 X 6 sq. mm earth wire
18Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required
195/6 A switch
2015/16 A switch
213 pin 5/6 A socket outlet
226 pin 15/16 A socket outlet
23Telephone socket outlet
24Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/PVC conduit as required.
251 run of cable
262 run of cable
273 run of cable
28Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
2925 mm
3032 mm
3140 mm
3250 mm
33Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
34Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
351 or 2 Module (75mmX75mm)
363 Module (100mmX75mm)
374 Module (125mmX75mm)
386 Module (200mmX75mm)
398 Module (125mmX125mm)
4012 Module (200mmX150mm)
41Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.
421 or 2 Module
433 Module
444 Module
456 Module
468 Module
4712 Module
48Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required.
49Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
50Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in non residential buildings).
51Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 Amodular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required.
52Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
53Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
54Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
55Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.
56Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
57Upto 450 mm sweep
58510 mm sweep
59Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
60Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 2 nos. 3 pin 5/6 A modular socket outlet and 2 nos. 5/6 A modular switch,connections etc. as required. (For light plugs to be used in non residential buildings).
61Supplying and fixing PVC batten/ angle holder including connections etc. as required.
62Dismantling of ceiling fan and painting the same with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins, reinstalling the same as required.
63CHAPTER-2 MCCB, MCB & DB'S
64Providing and fixing the following capacity TP&N disconnector fuse switch unit inside the existing panelboard with ISI marked HRC fuses, including drilling holes in the cubicle panel, making connections, etc., as required.
6532 A TP&N
6663 A TP&N
67100 A TP&N
68125 A TP&N
69160 A TP&N
70200 A TP&N
71315 A TP&N
72400 A TP&N
73Providing and fixing following rating and breaking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
74100 A, 16 KA,TPMCCB
75125 A, 16 KA,TPMCCB
76150 A, 16 KA,TPMCCB
77200 A, 16 KA,TPMCCB
78200 A, 25 KA,TPMCCB
79250 A, 25 KA,TPMCCB
80250 A, 35 KA,TPMCCB
81315 A, 35 KA,TPMCCB
82400 A, 35 KA,TPMCCB
83500 A, 35 KA,TPMCCB
84630 A, 50 KA,TPMCCB
85800 A, 50 KA,TPMCCB
86100 A, 30 KA,FPMCCB
87125 A, 36 KA,FPMCCB
88200 A, 36 KA,FPMCCB
89250 A, 36 KA,FPMCCB
90250 A, 50 KA,FPMCCB
91400 A, 50 KA,FPMCCB
92630 A, 50 KA,FPMCCB
93Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
946-way, Double door
958-way, Double door
9612-way, Double door
9716-way, Double door
98Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
994 way (4 + 12), Double door
1006 way (4 + 18), Double door
1018 way (4 + 24), Double door
102Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
1034 way (4 + 12), Double door
1048 way (4 + 24), Double door
10512 way (4 + 36), Double door
106Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
107Single pole
108Single pole and neutral
109Double pole
110Triple pole
111Triple pole and neutral
112Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
113Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
11440 amps
11563 amps
116Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
11740 amps
11863 amps
119100 amps
120Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
12125 amps
12240 amps
12363 amps
124Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
12540 amps
12663 amps
127Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required.
128Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32amps 415 volts \\"C\\" curve TP MCB complete with connections, testing and commissioning etc. as required.
129Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
130Supplying and fixing 20 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 amps \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
131Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 amps \\"C\\" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
132Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
133Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
134CHAPTER-3 EARTHING
135Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
136Earthing with copper earth plate 600 mm X 600 mm X3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.
137Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
138Providing and fixing 25 mm X 5 mm copper strip on the surface or in recess for connections etc., as required.
139Providing and fixing 25 mm X 5 mm G.I. Strip on surface or in recess for connections etc. as required.
140Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
141Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
142CHAPTER-4 LIGHTNING CONDUCTOR
143Providing and fixing of lightning conductor finial, madeof 25 mm dia 300 mm long, G.I. tube, having singleprong at top, with 85 mm dia 6 mm thick G.I. baseplate including holes etc. complete as required.
144Fixing of lightning conductor finial (single prong) withbase plate including holes etc. complete as required.
145Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as
146Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
147Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
148Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I.bolts, nuts,chuck nuts and spring washers etc.complete as required.
149Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
150Laying copper/ G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
151CHAPTER-5 LIGHTNING CONTROLS
152Supplying, Installation, Testing and commissioning ofPassive Infrared (PIR) technology based occupancysensor having high performance, non regulating programmable type, suitable for connected load upto10Amp , for mounting height up to 3 meter and for5 m diameter coverage area along with necessaryfixing arrangements i/c programming at site etc.complete as required.
153Supplying, Installation, Testing and commissioning of Passive Infrared(PIR) technology based occupancy sensor with day light dimming(lighting level shall be regulated as per availability of natural day light in anarea along with occupancy detection.) having high performance, regulating programmable type, suitable for connected load upto 10Amp , formounting height up to 3 mtr and for 5 m diameter coverage area along with necessary fixing arrangements i/c programming at site etc. complete as required.
154Supplying, Installation, Testing and commissioning of Microwave technology based occupancy sensorhaving high performance, non regulating programmable type, suitable for connected load upto 10Amp , for mounting height up to 3 meter and for5m X 20m coverage area along with necessary fixing arrangements i/c programming at site etc.complete as required.
155Supplying, Installation, Testing and commissioning astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sunrise or twilight(Auto ON, Auto OFF, Automodes) with manual override facility with 12/24 hourdisplay format with suitable battery and indication forrelay status i/c programming at site complete as required.
1561 output per phase and suitable for single phase supply
1572 output per phase and suitable for single phase supply
1583 output(1output per phase) and suitable for three phase supply
159CHAPTER-6 LED LIGHT
160LED Down lighter (SMD Type) (System lumen efficacy ≥120<135lm/Watt) - Supplying, installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI >80, UGR (Unified GlareRating) <19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70%of initial Lumen maintained till life ends, CCT3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. Complete in all respects i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with a Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by the Engineer-in-Charge as per requirements. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder-coated die-cast/Extruded aluminium Body including trim .
1615 - 7 watt
16212 -15 watt
16318 watt
16422 watt
16530 watt
166LED Down lighter (COB Type) (System lumen efficacy ≥120 lm/Watt ) - Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round / square/ Rectangular) COB Type of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt,frequency 50/60 hz, Operating temp range -5 0Cto 40 0C, internal surge protection of 2.5 KVwith Short & Open circuit protection ,THD < 10% ,P. F.≥0.95, IP20, CRI >80 , UGR (Unified GlareRating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), lifetime of minimum 50000 Burning Hours with, 70%of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. \\"complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector
1678 - 10 watt
16812 -15 watt
16918 watt
17022 watt
17130 watt
172LED Panel light 2x2 ft. (System lumen efficacy ≥120 <135 lm/Watt) - Supplying, Installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) <19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) - Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
17336 watt
17440 watt
175LED Batten light (System lumen efficacy ≥105 <120 lm/Watt) - Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C,internal surge protection of 2.5 KVwith Short & Open circuitprotection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) - Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm)
17618-22 Watt
17724 -26 Watt
17836 watt
17940 watt
180LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt). Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angleas per IESNA type I/II/III as per the width of the roadand the project requirement, suitable to fit in up to65mm dia pipe, life time (LED,Driver & electricalcircuitary) of minimum 50000 Burning Hourswith 70% of initial Lumen maintained till lifeends as per LM80 extrapolation IES TM-21-11report, CCT 3000°K / 4000°K / 5700°K /6500°K (Asper ANSI Bin), SDCM(Standard Deviation ColorMatching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single-core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
18150 Watt
182100 Watt
183120 Watt
184150 Watt
185200 Watt
186LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 and <135 lm/Watt). Supplying, Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built-in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI>70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beamangle 30 deg-120deg as per the application and theproject requirement, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000Burning Hours with 70% of initial Lumen maintained till life ends as per LM80extrapolation IES TM-21-11 report, CCT 3000°K /4000°K / 5700°K /6500°K (As per ANSI Bin),SDCM(Standard Deviation Colour Matching) <5,Maximum power consumption should not more than the specified rating and Fixture shall be ofrelevant BIS standard complete in all respect i/external connections with 1.5 sq.mm FRLS/HFFR/ PVC insulated copper conductor single core cableand earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C).
18750 Watt
188100 Watt
189150 Watt
190200 Watt
191250 Watt
192CHAPTER-7 BLDC FAN
193Brush Less Direct Current (BLDC) Fan with Remote - Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal(Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body. Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app-based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1941200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
1951400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum)
196Brushless Direct Current (BLDC) Fan without Remote - Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.
1971200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
1981400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum)
199CHAPTER-8 MV CABLE LAYING
200Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
201Upto 35 sq. mm
202Above 35 sq. mm and upto 95 sq. mm
203Above 95 sq. mm and upto 185 sq. mm
204Above 185 sq. mm and upto 400 sq. mm
205Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
206Upto 35 sq. mm
207Above 35 sq. mm and upto 95 sq. mm
208Above 95 sq. mm and upto 185 sq. mm
209Above 185 sq. mm and upto 400 sq. mm
210Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of the following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
211Upto 35 sq. mm
212Above 35 sq. mm and upto 95 sq. mm
213Above 95 sq. mm and upto 185 sq. mm
214Above 185 sq. mm and upto 400 sq. mm
215Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
216Upto 35 sq. mm
217Above 35 sq. mm and upto 95 sq. mm
218Above 95 sq. mm and upto 185 sq. mm
219Above 185 sq. mm and upto 400 sq. mm
220Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
221Upto 35 sq. mm (clamped with 1mm thick saddle)
222Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
223Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
224Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
225Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
226Upto 35 sq. mm (clamped with 1mm thick saddle)
227Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
228Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
229Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
230CHAPTER-9 MV CABLE JOINTING & END TERMINATION
231Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
2323 X 16 sq. mm
2333 X 25 sq. mm
2343 X 35 sq. mm
2353 X 50 sq. mm
2363 X 70 sq. mm
2373 X 95 sq. mm
2383 X 120 sq. mm
2393 X 150 sq. mm
2403 X 185 sq. mm
2413 X 225 sq. mm
2423 X 240 sq. mm
2433 X 300 sq. mm
2443½ X 25 sq. mm
2453½ X 35 sq. mm
2463½ X 50 sq. mm
2473½ X 70 sq. mm
2483½X 95 sq. mm
2493½ X 120 sq. mm
2503½ X 150 sq. mm
2513½ X 185 sq. mm
2523½ X 240 sq. mm
2533½X 300 sq. mm
2544 X 16 sq. mm
2554 X 25 sq. mm
2564 X 35 sq. mm
2574 X 50 sq. mm
258CHAPTER-10 HVAC(ONLY PLUMBING,DUCTING & AHU)
259Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class 'O' applied by suitable adhesive , as per specifications and as required complete in all respect.
26032 mm
26119 mm
262INSULATED VALVES Supplying, fixing, testing and commissioning of the following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified
263200 mm dia
264150 mm dia
265125 mm dia
266100 mm dia
26780 mm dia
26865 mm dia
26950 mm dia
27040 mm dia
271VALVES WITHOUT INSULATION Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications. Supplying, fixing, testing and commissioning of following sizes Motorized Butter fly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric signal and providing similar transduced feedback output to control system as required.
272350 mm dia
273300 mm dia
274250 mm dia
275200 mm dia
276150 mm dia
277125 mm dia
278100 mm dia
27980 mm dia
28065 mm dia
28150 mm dia
282DUCTING, GRILLS,DIFFUSER AND INSULATIONSupplying, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation with IS : 655 and approved drawings and specifications of following sheet thickness complete as required.
283Thickness 0.63 mm sheet
284Thickness 0.80 mm sheet
285Thickness 1.00 mm sheet
286Thickness 1.25 mm sheet
287Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber (Class \\"O\\") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
28832 mm
28919 mm
290CHAPTER 11 UNITARY SYSTEM
291HI - WALL SPLIT SYSTEMS - Supplying , Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180 260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only
2921.5 TR with 5 Star BEE Rating
2932.0 TR with 5 Star BEE Rating
294CHAPTER 12 TOWER TYPE SPLIT UNITS
295Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size. R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required.Cooling Only
2963.8 TR with 5 Star BEE Rating
2974.6 TR with 5 Star BEE Rating Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56284988
AUTHORITY Government Departments
TENDER VALUE 85 Lakhs
LAST DATE 18-07-2026
Authority
Authority Name All India Institute Of Medical Sciences
Work Description Tender for 12 Months Annual Term Contract For Day-To-Day Electrical Works Execution In All The Buildings At Aiims Mangalagiri C Us, Aiims Mangalagiri, Andhra Pradesh.
Basic Detail
Tender No AIIMS MG/Engineering Dept/NIT/2026-27/08
Bidding Type Tender
Location
City Guntur
State Andhra Pradesh
Key Dates
Publish Date 03 Jul 2026
Submission Date 18 Jul 2026
Open Date 20 Jul 2026
Finance
Tender Value 85 Lakhs
Tender Fee Ref. Documents
EMD 1.70 Lakhs
Exemption Not Available
Document List
33f14826-05cf-429c-b119-4599cf803777.html
BOQ_962325.xls
TenderDocument.pdf
Tendernotice_1 (2).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 03, 2026
11:30 IST

Tender Published

Tender notice published.

Today
Jul 18, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 15 days
Jul 20, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 17 days