Tender For Special Repair/ Replacement Of Conventional Tube Lights With Allied Works At Certain Places, Provn Of Cooling Appliances Window Ac And Allied Electrical Work At C Band Satcom Ups Room, Ac For Signal Equipment Room (L2), Flame Proof Light A
Tender Overview
Project Description
Tender for Special Repair/ Replacement Of Conventional Tube Lights With Allied Works At Certain Places, Provn Of Cooling Appliances Window Ac And Allied Electrical Work At C Band Satcom Ups Room, Ac For Signal Equipment Room (L2), Flame Proof Light And Exhaust Fan In Pol Store And Misc E/M Work Services At Cti, Stn Hq, Aftc & Afs Jalahalli
BOQ
| Sl. No. | Item Description |
| 1 | Taking down carefully copper/aluminium point wiring (light, fan,Power) complete fittings such as switches , ceiling roses pendents , regulators sockets light fittings etc removing materials to store for keeping in safe custody or for taking credit and making good disturbed surface of wall, floors , roof etc all as specified. |
| 2 | Material and labour for Point wiring complete with 1. 5 Sq mm single Core PVC insulated FRLS cable, 1100 volts grade unsheathed with multi stranded copper conductor drawn through and including PVC rigid non metalic conduit on surface/concealed with all fittings such as bend, end caps etc fixed on the surface of wall, ceiling, roof, steel structure etc. by means of suitable fixing accessories including provision of 1.5 Sq mm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor, modular metal pressed flush box concealed in wall,including suitable modules modular white top cover and plate for housing the switches, sockets, regulators etc. all as specified and as directed complet for One light point controlled by one switch one way 6 Amps all as specified and directed. |
| 3 | All as per item No. 2 but for One ceiling fan/Wall mounted fan point controlled by one switch one way 6 Amps and fan regulator |
| 4 | All as per item No. 2 but for One Exhaust fan point controlled by one switch one way 6 Amps |
| 5 | All as per item No. 2 but for One socket out let 6 Amps 3 pin on same board. |
| 6 | All as per item No. 2 here -in - before but for One 2/3 pin switch socket point controlled by 6 Amps switch on Independent board. |
| 7 | All as per item No. 2 here -in - before but for One 3 pin switch socket outlet combination, 15 Amps point with cables 4 sq mm all as specified and directed. |
| 8 | Supply and Fix modular switch 1 way 5/6 Amp,1 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian |
| 9 | Supply and Fix modular Socket, 5/6A - 2/3 pin combined 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian |
| 10 | Supply and Fix modular Socket, 5/15/ and 6/16A - 3/5 pin combined 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian |
| 11 | Supply and Fix modular switch 1 way 15/16 Amp,1 module, complete all as specified and directed. Make :Legrand/ Crabtree/ Anchor /Indoasian |
| 12 | Supply and Fix modular switch 2 way 5/6 Amp, 1 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor /Indoasian |
| 13 | Supply & fix in replacement of ceiling rose, 3 phase/ PVC/ polycarbonate insolated body all as specified and as directed. |
| 14 | S&F Modular fan regulator 120W, 2 Module for ceiling fan complete all as specified and directed. |
| 15 | Supply and fix of modular white cover plate with frame, 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian |
| 16 | Supply and fix of modular white cover plate with frame, 3 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian |
| 17 | Supply and fix of modular white cover plate with frame,4 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian |
| 18 | Supply and fix of modular white cover plate with frame,6 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian |
| 19 | Supply and fix of modular white cover plate with frame,08 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian |
| 20 | S&F in repair Sub main wiring with 2 runs of single core, 4 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 4.00 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza |
| 21 | S&F in repair Sub main wiring with 2 runs of single core, 6 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 6.00 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza |
| 22 | S&F in repair factory made powder coated distribution board TPN, 4 way double door MCB DB including bus bar, Neutral bar, standard DIN rail, earth bar complete complete all as specified and directed.Make : Indoasian/ Havells/ Legrand. |
| 23 | S & F TPN, MCB 40 to 63 Amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828, all as specified and directed. Make : Legrand/ L&T/ Indo Asian |
| 24 | S&F in repair factory made powder coated distribution board SPN 4 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian |
| 25 | S & F MCB SPN 240 volts upto 40 Amps 'C' series 10 KA breaking capacity complete fitting complete all as specified and as directed .Make : Legrand/ L&T/ Indo Asian. |
| 26 | M& L in repair PVC conduit medium grade of size 25 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed. |
| 27 | S & F in repair 3.0 mm thick hylum sheet for fixing switches, sockets, regulators etc, including making arrangement for the same incl re-fixing the serviceable / new switches, sockets etc including fixing with new brass screws with cup washers complete of size 4\\"x 4\\" all as specified and directed. |
| 28 | Supply and Fixing in repair 4 feet surface mounted batten type luminaire , lumen output of 2000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability . The luminaire and driver shall be BIS approved, complete all as specified and directed. Make : Philips/ Bajaj / CG/Havells. |
| 29 | Supply and Fixing in repair 2 feet surface mounted batten type luminaire , lumen output of 1000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability . The luminaire and driver shall be BIS approved, complete all as specified and directed. Make : Philips/ Bajaj / CG/Havells. |
| 30 | Taking down of old unserviceable ceiling fan of any size sealing cable end, dismantling blades and removing fan and blades to store for re-use or otherwise complete all as specified and directed. |
| 31 | Refixing existing serviceable ceiling fans 1200/1400 mm sweep after servicing, painting. of ceiling fan with one coat of synthetic enamel paint by spraying including greasing/oiling, filling cavities with filler after cleaning all dust etc. complete all as specified and as directed by Engineer-in-Charge. Note : cost includes for replacement of rubber bush ,hanging hook with new cotter pins etc |
| 32 | Supply and fix down rod for ceiling fan with 15/20mm dia (of length not less than 60cm and not more than 150cm) with hanging clamps for ceiling fan complete all as specified and directed. |
| 33 | Supply and Fix switch piano flush type 5/6 Amps 240 volts single pole one way, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian |
| 34 | Supply and Fix switch piano flush type 15/16 Amps 240 volts complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian |
| 35 | Supply and Fix shuttered socket outlet 3 pin 5/6 Amps, flush type, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian |
| 36 | Supply and Fix shuttered socket outlet 2 in 1, 3 pin, 5/6 and 15/16 Amps, complete all as specified and directed.Make : Anchor/Havells/L&T/Indoasian |
| 37 | Supply and Fix shuttered switch socket outlet 3 pin 5/6 Amps, flush type, complete all as specified and directed. Make : Anchor/Havells/L&T/Indoasian |
| 38 | S&F fan regulator stepped type electronic for ceiling fan complete all as specified and directed. |
| 39 | M&L in repair Sub main wiring with 4 runs of 6 Sqmm single core, PVC insulated, unsheathed 1100 Volts grade, multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on, walls, ceiling etc. as required including 6 Sqmm PVC insulated, unsheathed, multistranded, copper conductor, single core cable as earth continuity wire complete as specified and directed. Note : Four runs of cables and one run of earth wire including PVC conduit/ casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza |
| 40 | S&F factory made powder coated distribution board VTPN, 6 way double door MCCB DB including bus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DB with fitting fixture complete all as specified and directed.Make : Indoasian/ Havells/ Legrand. |
| 41 | S&F distribution board MCCB four pole, 100 Amp ultimate breaking capacity 16 KA conforming to IEC -61439-1, complete all as specified and directed. Make : Legrand/ L&T/ Indo Asian |
| 42 | S&F in repair factory made powder coated distribution board SPN 8 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian |
| 43 | S&F in repair factory made powder coated distribution board SPN 12 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian |
| 44 | S&F MCB single pole 240 volts 6 to 32 Amps, 10 KA rupturing capacity complete all as specified and as directed.Make : Legrand/ L&T/ Indo Asian. |
| 45 | S&F 35/36 W( WW/WH) LED recess /surface type 2x2 ft luminaire with classic design & glare free soft illumination. housing with white high reflection powder coated (RAL9016) CRCA sheet. Glare free, Opal diffuser for symmetrical light distribution fixed in separate CRCA sheet frame held in with housing by screws for easy maintenance. High efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle of 100° to ensure better uniformity. Powered by an independent Isolated, SELF Output electronic LED driver (SMPS based constant current supply) efficiency of 85% with built-in Surge protection 3Kv. System Lumen Output of 3000 lumens. Make : Philips/ Bajaj /CG/Havells. |
| 46 | Supply and fixing round/square shape 12 watt 220 volts AC recessed/surface type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete.Make : Philips/ Bajaj /CG/Havells. |
| 47 | S & F in repair 3.0 mm thick hylum sheet for fixing switches, sockets, regulators etc, including making arrangement for the same incl re-fixing the serviceable / new switches, sockets etc including fixing with new brass screws with cup washers complete of size 6\\"x 4\\" all as specified and directed. |
| 48 | S & F in repair 3.0 mm thick hylum sheet for fixing switches, sockets, regulators etc, including making arrangement for the same incl re-fixing the serviceable / new switches, sockets etc including fixing with new brass screws with cup washers complete of size 6\\"x 8\\" all as specified and directed. Please Enable Macros to View BoQ information |
| 49 | S & F in repair 3.0 mm thick hylum sheet for fixing switches, sockets, regulators etc, including making arrangement for the same incl re-fixing the serviceable / new switches, sockets etc including fixing with new brass screws with cup washers complete of size 6\\"x 8\\" all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 25 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender