Defence Statutory Bodies & Commissions/Committees Closing in 6 days TDR #56275935

Tender For Repair Maintenance Improvement Of External Electric Supply And Allied Works Nasirabad And Ajmer Mil Station Under Ge Nasirabad.

Issued by Statutory Bodies & Commissions/Committees · Ajmer, Rajasthan
Tender Value
Ref. Documents
Estimated cost
Bid Submission
14 Jul 2026
6 days left
EMD
80000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ajmer → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair Maintenance Improvement Of External Electric Supply And Allied Works Nasirabad And Ajmer Mil Station Under Ge Nasirabad.

BOQ

Name of Work:- REPAIR MAINT IMPROVEMENT OF EXTERNAL ELECTRIC SUPPLY AND ALLIED WORKS NASIRABAD AND AJMER MIL STATION UNDER GE NASIRABAD.
Sl. No. Item Description
1Supply, laying, Jointing connecting in replacement of LT UG cable XLPE insulated,PVC bedded galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm 4 core laid in trenches / on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
2All as per serial item No. 1.00 above but for 06 Sqmm 2 Core.
3All as per serial item No. 1.00 above but for 16 Sqmm 4 Core.
4All as per serial item No. 1.00 above but for 25 Sqmm 4 Core.
5All as per serial item No. 1.00 above but for 35 Sqmm 3.5 Core.
6All as per serial item No. 1.00 above but for 50 Sqmm 3.5 Core.
7All as per serial item No. 1.00 above but for 70 Sqmm 3.5 Core
8All as per serial item No. 1 above but for 95 Sqmm 3.5 Core
9All as per serial item No. 1.00 above but for 120 Sqmm 3.5 Core
10All as per serial item No. 1.00 above but for 150 Sqmm 3.5 Core
11All as per serial item No. 1 above but for 240 Sqmm 3.5 Core
12All as per serial item No. 1.00 above but for 300 Sqmm 3.5 Core
13Supply, laying, Jointing connecting in replacement of LT UG cable XLPE insulated,PVC bedded galvanised steel strip or wire armoured, heavy duty electric cable with copper conductor, 1100 volts grade, cross sectional area 2.5 sqmm 4 core laid in trenches / on poles / walls / in ducts / passing through pipes and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
14Dismantling of Old unsv Poles/ Struts any type & Supply and fixing new steel tubular swaged poles, type 410 SP 31 (Overall length 9.00 m) complete with cast iron base plate, finial taper plug, bolts, nuts screws and washers including painting two coats of black bituminous paint internally and externally up to planting depth and remaining external portion with two coats of aluminum paints over a coat of red oxide primer and writing pole Nos with white paint on black back ground complete all as specified and as directed.
15Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
16All as per Item No. 4.00 above Exc 1.50 but n.exc 3.0m deep complete all as specified and directed
17Supply and spread sand in trenches as sand cushioning to underground cable for protection with dry fine river sand and provide required cover after punning down 18CM will be measured and paid complete all as specified and directed.(Note: Thickness of sand cushion after punning down will be measured and paid.)
18Supply and laying well burnt sub class ‘B’ bricks ( designated 75) locally available best quality, laid dry in trenches for protection of underground cable complete all as specified and directed.
19Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm as in soils complete all as specified and as directed.
20Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point as in soils complete all as specified and as directed.
21Supply and laying of DWC Double wall corrugated Duct Pipe as cable protection pipe in trench/wall/pole including all fittings complete all as directed for the following sizes (OD X ID) :-
22Size 40 X 32 mm
23Size 63 X 50 mm
24Size 90 X 75 mm
25M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded stone aggregate) in foundation of PCC poles/struts as specified including necessary form work, complete all as specified & directed.
26M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded stone aggregate) in foundation of stay assembly etc including necessary form work, complete all as specified & directed.
27M&L for plain cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) for coping around poles, including necessary form work finishing even and smooth without using extra cement, complete all as specified & directed.
28Supply and laying in replacement of GI tube light grade as in cable protection pipe including all fittings & taking down / taking out from trench complete all as directed for the following sizes :-
2925 mm bore
3040 mm bore
3180 mm bore
32Material and labour for cutting of road/ hard standing n exc 20cm width and n exc 60cm in depth for laying of cable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1 to match with existing surface complete all as directed.
33M&L for cleaning, scrapping, preparing of old painted steel tubular pole 9m long and applying one coat of aluminium red oxide primer and two coat of aluminium paint to pole and accessories / fittings whatever fixed on pole including marking/writing pole No on each pole with yellow SE paint with 5cm large bold letters on black background of suitable size at a height of 2m above GL complete all as specified and directed.
34Dismantling of unserviceable worn out / weathered / damaged ACSR conductor, service feeder of any size and type from pole after disconnecting jumpers and insulator bindings complete all as specified and directed.
35Dismantling cross arm of MS channel or angle section from pole anysize complete all as specified and directed.
36Dismantling insulators of any type and any size complete all as specified and directed.
37Dismantling stay assembly complete all as specified and directed.
38S&F in replacement MCCB 3 pole, 415 V, adjustable type 25 to 100 Amp with breaking capacity 16 KA complete all as specified and directed.
39S&F in replacement MCCB 3 pole, 415 V, adjustable type 125 Amp with breaking capacity 16 KA complete all as specified and directed.
40S&F in replacement MCCB 4 pole, 415 V, adjustable type 160 Amp with breaking capacity 36 KA complete all as specified and directed.
41S&F in replacement MCCB 4 pole, 415 V, adjustable type 200 Amp with breaking capacity 36 KA complete all as specified and directed.
42S&F in replacement MCCB 4 pole, 415 V, adjustable type 250 Amp with breaking capacity 36 KA complete all as specified and directed.
43S&F in replacement MCCB 4 pole, 415 V, adjustable type 400 Amp with breaking capacity 50 KA complete all as specified and directed.
44S&F in replacement MCCB 3 pole, 415 V, adjustable type 630 Amp with breaking capacity 50 KA complete all as specified and directed.
45M&L for earthing complete with galvanized iron earth plate electrode 600mm x 600mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connecting to GI strip 25x4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by 50mm dia GI pipe medium grade and connected to pole structure/ panel board/earthing test point all as shown in electrical plate No. 3 of SSR Part-I(2009) and testing on completion complete all as specified and directed.
46Supply and fix in replacement single pointed air termination aluminium rod 12mm dia 300mm long complete all as specified and directed.
47Supply & fix in replacement aluminium strip 25 mm x 3 mm complete with saddles and fixing screws for fitting the strip complete all as specified and directed.
48Supply and fix in replacement GI strip 32 x 6mm with saddles and fixing screws etc for roof conductor and down conductor above ground complete all as specified and directed.
49M&L for Test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25mm drilled and screwed including 03 Nos of 8mm dia 25mm long hexagonal head screw complete all as specified and directed.
50S&F in replacement of cable joining kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with joining material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
51M & L Spray of agricultural based chemical inside the installation to control the growth of unwanted herb etc including cleaning of the grass herbs bushes etc from the installation complete all as specified and directed.
52Design, supplying, installing, testing and commissioning in replacement of LT Indoor type, double door IP - 65 type panel board factory fabricated cubical type weather and vermin proof with locking arrangement made out of MS CRCA sheet 3.00 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamber and compartmentalised cabinet for housing and mounting MCCBs, metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & all outgoing controls and comprising with the following duly CPRI ApprovedIncomer - MCCB 4P 630A 36kA-1No, Out going:- MCCB 4P 400A 36kA-1No, MCCB 4P 200A 25kA-1No, MCCB 4P 160A 25kA -03 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nos main aluminum bus bar. Bus Bar shall be of 1.5 times of Incoming MCCB , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based three phase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed.
53Design, supplying, installing, testing and commissioning in replacement LT Outdoor type, double door IP - 65 type panel board factory fabricated cubical type weather and vermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamber and compartmentalised cabinet for housing and mounting MCCBs, metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & all outgoing controls and comprising with the following duly CPRI Approved-Incomer- Incomer - MCCB 4P 250A 36kA-1No, Out going:- MCCB 4P 200A 25kA-1No, MCCB 4P 160A 25kA -01 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nos main aluminum bus bar. Bus Bar shall be of 400A , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based three phase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed.
54Design, supplying, installing, testing and commissioning in replacement LT Outdoor type, double door IP - 65 type panel board factory fabricated cubical type weather and vermin proof with locking arrangement made out of MS CRCA sheet 3.15 mm thick suitable size of channel for base complete with aluminium bus bar inside sepreate chamber and compartmentalised cabinet for housing and mounting MCCBs, metering eqpt prewired with suitble size of copper conductor and duly powder coated and panel board fixed on angle iron frame which is made out of 50 x 50 x 6 mm thick angle iron duly marked the incoming & all outgoing controls and comprising with the following duly CPRI Approved-Incomer- Incomer - MCCB 4P 200A 36kA-1No, Out going:- MCCB 4P 160A 25kA-1No, MCCB 4P 100A 25kA -01 Nos, MCB TPN 63 A, 10 KA-01 No, 04 Nos main aluminum bus bar. Bus Bar shall be of 400A , all bus bars shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75x40mm duly painted with black paint. Microprocessor based three phase phase electronic 01 No.Digital Ammeter (0-300) with ASS-1No, Current transformer of rating 300/5A-1No, Digital Voltmeter with VSS(0-500)V-1No, RYB LED set-1, PCC foundation complete all as specified and directed.
55M&L for attending external electric complaints by opening / disconnecting the electrical connection of defective / burnt out underground LT cable of any size & any core from main switch / DB / junction box / LT panel / L T O/H line etc. and taking out the required length of cable from existing loop and remove/ cut the defective cable,replace the same with new cable as per existing size including providing necessary thimbles / connectors at cable end and reconnecting the cable in previous location with existing main switch / DB / Junction box / LT panel / OH line etc. and make electic connection as functionable in all repspects including testing on completion all as specified and directed by Engineer-in-charge. Note:- (A) The rate quoted shall deemed to be inclusive of the following: (i) Necessary earth work excavation in any type of soil, returning, filling and removing extra soil. (ii) Existing bricks, sand,GI protection pipe etc. shall be removed carefully and stacks neatly near site and same shall be re- laid after attending fault/defect. (iii) Distrubed surface of road, floor etc. shall be make good to match with existing surface. (iv) Required numbers of electrician and helper shall be deployed for attending complaints regulerly on daily basis and contractor shall collect the complaints details from complaint cell of AGE E/M No.1 and same shall be rectified/ attanded within an hour and report shall be submitted to Engineer-in-charge or their authorised representative. Continue to Below 38.01:-
56Continue Item No. 38.00 (B) Please note that payment shall be made to contractor one time only for this items. if any fault/ default occured again on the same location/ DB/junction box/panel during currency of contract, the same shall be rectified by the contractor without any extra cost to Govt. in terms of condition 46 of IAFW of genral condition of contracts. (C) Additional bricks,sand,GI pipe etc. as required for cable protection and cushioning shall be measured and paid separetely under relevent item.
57M&L for dismantling / disconnecting / removing the faulty / burnt out overhead conductor of any type / size from insulator of LT pole any type by making proper shutdown from department and removing of tree / branches if any fell on Over Head Line, loose the binding wire in each insulators and disconnecting cable connection as required, remove the burnt / damage conductor / earth wire and making necessary joint with new ACSR conductor of suitable size as per existing as directed, restretching all the loose spans of ACSR conductors, earth wire etc. with insulator and providing binding wire of existing size to tigheting and making LT/HT cable in existing position and make electric connection as functionable in all respects including testing on completion allas specified and directed by Engineer in charge. NOTE: The rate quoted shall deemed to be inclusive of the following:- (i) Tools and plants such as ladder,rope, cutter, axes, knife etc. as required for cutting and removing tree/branches if any fall on OH line. (ii) Insulator,binding wire etc. as required in addition to existing shall be provided by the contractor. (iii) Required numbers of Elecrician and helper shall be deployed for attending complaint regularly on daily basis and contractor shall collect the complaint details from complaint cell of AGE E/M No. 1 (iv) Additional ACSR conductor and earth wire shall be measured and paid separetely under relevant items.
58Supply and fix in replacement of LED Post top light fitting 45 Watt / 50 Watt, made in die-cast aluminum housing with decorative clear opal acrylic diffuser, IP 65 protection, spun aluminum powder coated canopy, low power Warm White (WW) LEDs connected in series and parallel combination with better heat dissipation arrangement with LED color temperature- 3000K ±300K, Highly efficient constant current electronic driver having operating voltage range from 140-280 Volt AC, provided with high voltage, open and short circuit protection, Voltage surge protection 5KV complete suitable for up to 60mm OD pipe entry with fixing bolts including taking down existing unserviceable post top light of any description complete all as specified and directed.
59Supply and fixing, in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
60Supply, fixing and testing in replacement Street light automatic Nature switch of capacity 3 KW single phase complete with high and low voltage and overload protection, degree of protection confirm to 1P-55 AC, SP complete with MCB and power contactor fixed on pole with 25 X 3mm MS strip clamp including provision of 6 sqmm 3 core cable for connection.complete all as specified and directed. Make - Kakatiya Energy system Model SWADEEP
61Supply, fixing and testing in replacement Street light automatic Nature switch of capacity 5 KW Three phase complete with high and low voltage and overload protection, degree of protection confirm to 1P-55 AC, SP complete with MCB and power contactor fixed on pole with 25 X 3mm MS strip clamp including provision of 6 sqmm 3/4 core cable for connection. complete all as specified and directed. Make - Kakatiya Energy system Model SWADEEP
62Supply and fix bracket in replacement for street light fittings made out GI pipe of light grade 1.2 m long 40 mm pipe each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 32 x 6 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with one coat of aluminium paint over a coat of red oxide primer including taking down old unserviceable bracket of any shape and size all as specified and as directed.
63S&F in repairs IP65/IP66 Thermoplastic Polycarbonate cable Junction box as per existing sample for street lights with 25 sqmm terminal of 32 Amps rating for mounted on din rail with locking arrangement fixed to PSC/Steel Poles by means of suitable size of clamps made of MS flat 20 x 4mm - 2 Nos with nut, bolts & double washers and including provn for fixing 01 No. single pole, MCB, 10 amps,10KA, ‘B’ series with ON/OFF flap complete all as specified and directed.
64Taking out old unserviceable indicating lamp and S&F R ,Y , B Phase LED indicating lamp complete all as specified and directed.
65Taking out old unserviceable Digital multi-function meter Supply & fix Digital multi-function meter 96mm x 96mm flush secure panel mounting type -voltage, current, frequency, power factor in 03 line LED backlight display having programmable CT ratio(all as per incommer MCCB) with selector switch complete all as specified and directed.Make : L & T and equivalent. Please Enable Macros to View BoQ information
66Taking out old unserviceable Digital multi-function meter Supply & fix Digital multi-function meter 96mm x 96mm flush secure panel mounting type -voltage, current, frequency, power factor in 03 line LED backlight display having programmable CT ratio(all as per incommer MCCB) with selector switch complete all as specified and directed.Make : L & T and equivalent. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56275935
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 14-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair Maintenance Improvement Of External Electric Supply And Allied Works Nasirabad And Ajmer Mil Station Under Ge Nasirabad.
Basic Detail
Tender No 8749/E8
Bidding Type Tender
Location
City Ajmer
State Rajasthan
Key Dates
Publish Date 02 Jul 2026
Submission Date 14 Jul 2026
Open Date 16 Jul 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 80000
Exemption Available
Document List
BOQ_869019.xls
d09e489c-60a0-4ebd-8d58-c1e8ce902afa.html
GeneralPages8749.pdf
Tendernotice_1 (1).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 02, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 14, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Jul 16, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 8 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_869019.xls

html

d09e489c-60a0-4ebd-8d58-c1e8ce902afa.html

pdf

GeneralPages8749.pdf

pdf

Tendernotice_1 (1).pdf

Disclaimer