Tender For Repair/Maintenance To Lt Panels, Feeder Pillar Boxes, Earthing, Dg Sets, Amf Panels Oht Reservoir, Ug Sump, Rising Main Distribution And Other E/M Works At Af Stn Naraina Under Aor Of Ge (Af) Faridabad

Issued by Statutory Bodies & Commissions/Committees · New Delhi, Delhi
Tender Value
48 Lakhs
Estimated cost
Bid Submission
16 Jul 2026
10 days left
EMD
96000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maintenance To Lt Panels, Feeder Pillar Boxes, Earthing, Dg Sets, Amf Panels Oht Reservoir, Ug Sump, Rising Main Distribution And Other E/M Works At Af Stn Naraina Under Aor Of Ge (Af) Faridabad

BOQ

Name of Work:- REPAIR/MAINTENANCE TO LT PANELS, FEEDER PILLAR BOXES, EARTHING, DG SETS, AMF PANELS OHT RESERVOIR, UG SUMP, RISING MAIN DISTRIBUTION AND OTHER E/M WORKS AT AF STN NARAINA UNDER AOR OF GE (AF) FARIDABAD
Sl. No. Item Description
1Excavation in trenches in soft / loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 mtr depth for laying of cables/poles or foundation etc and getting out complete all as specified and directed.
2Returning, filling, including spreeding leveling watering and well ramming in layers not exceeding 25 cm apart complete all as specified and directed.
3Removing of surplus excavated soil to distance not exceeding 50 Mtr from starting point and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed.
4M&L for sand cushioning to XLPE cable with using clean dry and natural river sand with a layer of 8 cm thick before laying the cable and 15 cm thick layer after laying the cable and this then gently punned down to a thick of 10 cm above the top the upper most cable complete all as specified and directed.
5Supplying and laying un-reinforced precast concrete cable cover, class LV, Type 1 with peak, size 250 mm x 150mm x 40mm complete all as specified and directed.
6Supply, Laying,Connecting and testing in repairs cable XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 Volt grade cross sectional area 120 Sqmm 3.5 core complete all as specified and directed.
7All as per item No 06 above but Size 95 sqmm 3.5 core.
8All as per item No 06 above but Size 70 sqmm 3.5 core .
9All as per item No 06 above but Size 50 sqmm 3.5 core.
10All as per item No 06 above but Size 35 sqmm 3.5 core .
11All as per item No 06 above but Size 16 sqmm 4 core.
12All as per item No 06 above but Size 10 sqmm 4 core .
13Boring of Holes under road, Pavement, hard Standing by trenchless technology using ultra Sound technique and necessary machine with HDPE Pipe, PN 10,100 mm dia complete all as specified and directed.
14Supply, laying and fixing in position in repairs galvanized iron pipe 80 mm bore light grade fixed to pole with mild steel clamps of required size or laid through wall/under floor/under road/in trenches duly painted with two coat of black metallic paint after a primer coat of red oxide complete all as specified and directed.
15All as per item No 14 above but 50 mm dia.
16All as per item No 14 above but 40 mm dia.
17M&L for cable end termination kit out door, heat shrinkable type suitable for XLPE/ PVC cables of size 6 Sqmm to 16sqmm 4 core core with working voltage 1100 volts incl necessary excavation returning filling & removal complete all as specified and directed.
18All as per item No 17 above but Size 25-35 sqmm 4 core.
19All as per item No 17 above but Size 50-95 sqmm 3.5 core.
20All as per item No 17 above but Size 120 - 185 qmm 3.5 core.
21M&L for cable jointing kit straight through, heat shrinkable type suitable for XLPE/ PVC cables of size 6 Sqmm to 16 Sqmm 4 core with working voltage 1100 volts complete all as specified and directed.
22All as per item No 21 above but Size 25-35 sqmm 4 core.
23All as per item No 21 above but Size 50-95 sqmm 3.5 core.
24All as per item No 21 above but Size 120 - 185 qmm 3.5 core.
25S&F in repairs MCCB 4 pole 415 volts fixed type 400 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
26S&F in repairs MCCB 4 pole 415 volts fixed type 315 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
27S&F in repairs MCCB 4 pole 415 volts fixed type 250 Amps with braking capacity 25KA after taking out old U/S one complete all as specified and directed.
28S&F MCCB 4 pole 415 volts in repairs,fixed type 200 Amps with braking capacity 16 KA.after taking out old U/S one complete all as specified and directed.
29S&F in repairs MCCB 3 pole 415 volts fixed type 160 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
30S&F in repairs MCCB 3 pole 415 volts fixed type 125 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
31S&F MCCB 3 pole 415 volts in repairs,fixed type 63 Amps with braking capacity 16 KA.after taking out old U/S one complete all as specified and directed.
32S&F sheet metal enclosures DB Double door Verticle distribution type, 08 way, TPN DB , IP43, 415V & suitable for 4 POLE MCCB as incomming including shruded neutral bar & Pan assembly with earthing terminal as provided by manufacturer complete all as specified and directed.Note : - MCCB shall be measured and paid separately
33S&F sheet metal enclosures DB Double door Verticle distribution type, 06 way, TPN DB , IP43, 415V & suitable for 4 POLE MCCB as incomming including shruded neutral bar & Pan assy with earthing terminal as provided by manufacturer complete all as specified and directed.Note : - MCCB shall be measured and paid separately
34Supply & fixing in reapir of MCB SP 6 t0 32 type 'C' curve amps 230 Volt complete all as specified and directed.
35S&F in repairs Contactor, (4 Pole AC & DC Control) operational current AC1,160 Amps,poles composition- 4NO,DC control ref-LP1D80004 of TC complete all as specified and directed.
36S&F in repairs Contactor, (4 Pole AC & DC Control) operational current AC1,125 Amps,poles composition- 4NO,DC control ref-LC1DT125A of TC complete all as specified and directed.
37S&F in repair MNX 18, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed.
38S&F in repair MNX 95, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed.
39S&F in repair MNX 70, 3 pole contractor,2 NO+ 2 NC,415 volts AC, confirms to IS/IEC 60947 -4-1, in existing model and make including after taking out old unserviceable one, complete all as specified and directed.
40S&F MN contactor 18 Amps in existing model and make including after taking out old unserviceable one, complete all as specified and directed.
41S & F rubber insulation mat of size 1.8 mtr x0.9mtr wide 19mm thick red colour ISI marked embozzed for up to 15 KV complete all as specified and directed.
42M & L for repairing , servicing and replacement of LT panels unsv part including complete accesories such as partialy open door , door breakers , Unsv Al bus bar , unsv locking arrangement, repairing of LT Panel legs, welding work , neceassry PCC work , Excavtaion , removal , retruning filling including disconnection and reconnection of cables , of any size any capacity complete all as specified and directed.
43M&L for removing all connections from LT panel having feeders upto 04 Nos ( Total of incoming and outgoing) , any capacity, indoor or outdoor type, fpr repairs/ servicing. Cleaning properly all parts and removing dust, carbon deposits etc. Removing U/S thimbles if any of connections. Refixing serviceable items to the panel and making all connections including testing for proper functioning of the panel as per standard engineering pactice, complete all as specified and directed.Note :- Old U/S items shall be measured and paid separately.
44M&L for removing all connections from LT panel having feeders above 04 Nos upto 08 Nos (Total of incoming and outgoing) , any capacity, indoor or outdoor type, fpr repairs/ servicing. Cleaning properly all parts and removing dust, carbon deposits etc. Removing U/S thimbles if any of connections. Refixing serviceable items to the panel and making all connections including testing for proper functioning of the panel as per standard engineering pactice, complete all as specified and directed.Note :- Old U/S items shall be measured and paid separately.
45M&L for Painting of any size , any make LT panel after removing old dust partical,oily portion by rubbing with sand paper with spary pump, and writing /digital printing, capacity Descripton, date of installation,etc complete all as specified and directed.
46M&L for repair maintainance of oil cooled servo voltage stablizer of capacity 100 KVA to 400KVA 3 phase by isolating , disconnecting of input/output ,supply cable,opening of top of voltage stablizer,detecting of fault ,u/s component in control panel /dimmerstat /PCB etc,cleaning of serviceable parts /component complete all as specified and directed.Note:- The replacement spare parts shall be measured and paid separately.
47Supply only spare part of the Voltage stablizer 100 to 400 KVA KVA complete all as specified and directed by Engineer-in-Charge as following:-
48RC Network
49AC Synchronous Motor
50Spring loaded finger
51Microproccessor Based eletronic control board
52Rewinding of Auto Transformer ,50-100 KVA
53Selector switch
54Voltmeter digital type
55Amperemeter digital type
56S&F in repair of Onload Changover switch 200 Amp, 4 pole ,415 V,50 Hz in sheet metal enclosure complete all as specified and directed.
57S&F in repair of Onload Changover switch 400 Amp, 4 pole ,415 V,50 Hz in sheet metal enclosure complete all as specified and directed.
58S&F in repair / replacement of UNSV Aluminum thimbles of size 10sqmm to 70sqmm as per site requirements, complete all as specified and directed.
59S&F in repair / replacement of UNSV Aluminium thimbles of size 95Sqmm to 185sqmm as per site requirements, complete all as specified and directed.
60M&L danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for LT panel, 20x15 cm size complete all as specified and directed.
61S&F in repair PVC conduit 25 MM dia along with accessories in surface/recess I/C or cutting the wall and making good the same in case of recessed conduit as required complete all as specified and directed.
62Supply, installing testing and commissioning in replacement of size 900x900x450 (Apprx)factory made and tested (Including CPRI test cetified) indoor type floor mounted LT panel board, cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chamber with insulated AL busbar of rating 1.5 times the incomer MCCB for phase installed on porcelin/SMC insulators. The panel shall be dust and vermin proof IP-64 class protection and made out of 3.15 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with aproaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS IS 694 sheathed 1100V grade of appropriate size comprising of following:-INCOMING-(i) Mains MCCB 4 pole 400 Amps 50 KA with adjustable setting, 415 Volts with breaking capacity 36 KA. -01 No.(ii) Digital type voltmeter 0-500 volts and with selector switch-01 No.(iii) Digital Amp meter with CTs & built in selector switch-01 No.(iv) Indication lamp RYB-01 Set.OUTGOING-(i) MCCB 3 pole 200 Amps,, 415 Volts with breaking capacity 36 KA.-02 No.(ii) MCCB 3 pole 125 Amps, 415 Volts with breaking capacity 25 KA.-01 No. Note: Drawings for LT panel shall be got approved from GE before procurement.
63Supply and install and commmissionng of LT bus bar chamber CPRI approved out door type with sloping canopy of size 600x600x600mm made out of 3.15 mm thick CRCA sheet, panel shall be powder coated siemens grey shade mounted on 40x40x6 mm MS angle iron frame 90 cms height erected in ground with PCC foundation 1:4:8 with 40mm stone aggregate including supply and fixing insulated aluminium bus bar of size 50x 6mm for three phase and neutral 200 mm length respectively mounted on insulators and terminating with suitable cable with glands and provision of one MCCB 63 Amps,3 pole ,415 mps, 50 Hz of breaking capacity 25 KA as incomer complete all as specified and directed.
64M&L for Dehydration including filteration and cleaning of transformer oil of servo by centifugal dehydration machine till to achieve Di-electric strength 50 KV at 2.5 mm gap testing of sample before and after dehydration and filteration complete all as specified and directed.Note:- Contractor has to arrange the dehydration machine and testing kit without any extra cost to the deptt. Test report to be submitted after completion of job.
65Supply & Filling /pouring of transformer oil of low viscosity having dielectric strength not less than 60 KV complete all as specified and as directed. Note:- Dielectric strength test shall be carried out at site before poring/ filling in transformers in the presence of Engr-in-Charge on the site.
66M & L for earthing with steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less tha 1.5 mtr deep below normal grund level connected to galvanized iron strip size 32 x 6 mm as earthing lead by means of nuts, bolts and washers of steel after wlding of GIstrip to earth electrode to the full length of earht plate, 40mm dia GI tubing lightgrade protection pipe upto test point, 20mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover ofsize 30x30 cm made of RCC 1:3: with suitable handle, angle iron frame made of angle iron of size 40x40x4m, adequate qty of charcoal dust and salt layers all around the earth plate and filling of vegetables soil to the remaining 10% removal of surplus soil and retruning filling in all as required at site including test point made outof steel plate of size 75x75x6mm fixed to wall all as specified in plate No 3 of SSR Part-I and complete all as specified and directed by Engineer-in-Charge.
67M&L for Design ,development ,supply commisiong and testing burnished metallic brown 99.99% pure copper material specially develpoed for earthing purpose T point terminal exothermic/ nut bolt/ breezing . ground tubular effective chemical earthing (CPRI tested for 25KA current capacity for LT line ) highly anticorrosive long life eletrode with and including adequate protective coating to withstand servere weather condition in the earth pit of the standard size comprising of 40 mm 3m long copper rod as primary conductor and hollow copper tube of 80 mmx 3 m long with alosing base plate of 80 mm secondary conductor to install with suitable connecting terminal cofirming of IS 3043 1987 specification highly conductive packing material to be filled in earth pits for providing uniform low resisitivity anticorrosive ,hygroscope medium around the earth system for improving the efficiency of current dissipation with cystalline conductive mixture CCM 25 kg per bag sufficient quantities required at site complete RCC earthing pit cover material and labour complete bfc compound specified and as per ic 62561 acceptance chemical test Leaching, sulphur determination, corrosion, resistivity along with CPRI and chemical compound test report Note :-1. Excavation / drilling hole in hard rock is included in the rate quoted incld. T&P2. Min. resistance for earthing pit shall be less than 1 ohm.3. Drilling or earth work shall be included in the overall cost quoted by the contractor.
68S&F in repair copper strip 20mm x 3.15 mm complete with insulators and fixing screws etc for roof/wall above ground level including removing u/s strips complete all as specified and directed.
69S&F in repair aluminium strip 25 mm x 4 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level including removing u/s strips complete all as specified and directed.
70S&F in repair single pointed air termination aluminium rod,12 mm dia, 300 mm long complete all as specified and directed.
71S&F in repair porcelain strip holder on wall and roof of suitable size including removing broken u/s one complete all as specified and directed.
72M&L 32 mm GI pipe light grade of 1.3 mtr piece fixing in PCC cubical and complete connection of existing air termination rod complete all as specified and directed,
73M&L for PCC 1:3:6 type C1 (using 20 mm graded stone aggregate) as in coping and necessary form work, weathering slightly rounded or chamfered angles and throating etc complete all as specified and directed.
74M&L for General Servicing of DG sets 250 KVA , comprising of Cleaning & greasing of the parts, Tappet setting as per standard, Fan belt, tensioner pulley and lever adjustments, Tightening of all the nuts, bolts and clamps, Testing & checking of AC & DC Wiring, Self & Charging Alternator cleaning and testing, checking of working & minor fault removal, Checking of Supply & return fuel pipes from fuel tank to engine, Cleaning of hydraulic governer , Cleaning of radiator complete set. Checking of FIP timing by Fuel cut off method including Transportation, Labour charges & minor material required for servicing etc. as reqd complete all as specified and directed.Note - (i) Servicing through OEM authorised rep or service engineer from the manufacturer only.(ii) Cost of unserviceable items will be measured and paid seperately under relevant items.
75All as per item No 74 above but capacity of DG set 125 KVA.
76All as per item No 74 above but capacity of DG set 100 KVA
77All as per item No 74 above but capacity of DG set 75 KVA
78All as per item No 74 above but capacity of DG set 62.5 KVA
79All as per item No 74 above but capacity of DG set 40 to 50 KVA
80Supply only the following items of DG Set of various capacity :-
81Supply only Element lub oil filter Cartrige complete all as specified and directed.
82Supply only fuel filtter Cartage complete all as specified and directed.
83Supply only Pre Filter Assembly complete all as specified and directed.
84Supply only Air Filter for Set complete all as specified and directed.
85Supply only seal 'O' ring complete all as specified and directed.
86Supply only genuine Engine oil complete all as specified and directed.
87Supply only super plus Coolent complete all as specified and directed.
88Supply only distilled water complete all as specified and directed.
89Supply only Battery terminals , lugs , bolts complete all as specified and directed.
90Supply only Battery leads copper conductor multi wired 50 Sqmm, complete all as specified and directed.
91Supply only Battery leads copper conductor multi wired 70 Sqmm, complete all as specified and directed.
92Supply only Hinges for DG set door of any size, any type as required on site, complete all as specified and directed.
93M&L for Dismantling the radiator and fan from the engine for cleaning of copper tubes and cooling fins by descaling solution and using air compressor ,soldering on leakage, patch work and re-assembling the radiator and fitted with DG set properly including replacement of radiator hose pipe with clamps and bolt/nut with washer, leak check and pressure testing including transporting to repair workshop and bringing back for upto 125 KVA complete all as specified and directed.
94All as per item No 93 above but capacity 250 KVA
95Supply, replacement and testing of radiator assembly of DG Set upto 75 KVA complete all as specified and directed.
96Supply, replacement and testing of radiator assembly of DG Set 100 KVA complete all as specified and directed.
97Supply, replacement and testing of radiator assembly of DG Set 125 KVA complete all as specified and directed.
98Supply and replacement of low lube oil pressure sensor upto 250 KVA DG Set complete all as specified and directed.
99Supply and fixing in repair of Water Pump of Radiator suitable for DG set Radiator 125 to 250 KVA complete all as specified and directed.
100All as per item No 99 above but capacity from 40 KVA upto 100 KVA
101M&L for Removal & replacement of fly wheel gear ring suitable for upto 100 KVA DG set connection & testing complete all as specified and directed.
102All as per item No 101 above but capacity from 125 KVA upto 250 KVA
103M&L for removal & replacement of thermostat suitable for upto 100 KVA DG set connection & testing complete all as specified and directed.
104All as per item No 103 above but capacity from 125 KVA upto 250 KVA
105Supply and fixing in repair of AVR for DG set having capacity 100 KVA complete all as specified and directed.
106All as per item No 105 above but capacity from 125 KVA upto 250 KVA
107Supply, fixing and testing for smooth fuctioning Fan Belt suitable for DG set up to 100 KVA complete all as specified and directed.
108All as per item No 107 above but capacity from 125 KVA upto 250 KVA .
109Supply and fixing in all type of hose pipe with clamps , over flow pipe, copper tube fuel supply pipe, etc with clip and complete fittings suitable for DG set upto 100 KVA complete all as specified and directed.
110All as per item No 109 above but capacity from 125 KVA upto 250 KVA
111S&F fuel hose pipe from fuel filter to fuel pump for DG set upto 100 KVA complete all as specified and directed.
112S&F fuel pipe from fuel tank to fuel filter for DG Set 125 KVA to 250 KVA complete all as specified and directed.
113Supply and fixing mounting rubber bushing set of 6 for existing generator complete all as specified and directed.
114S&F of under/over voltage relay 3 phase 415V for DG set of capacity upto 250 KVA complete all as specified and directed.
115S&F in repair of Battary Charger 12V DC, 5 Amp of Autocut Electrical Battery Charger Unit SMPS with Constant Voltage Output with Battery Charging Transformer and Moulded Rectifier Unit etc suitable for smoothing functioning of DG set as required on site complete all as specified and directed.
116All as per item No 115 above but capacity Battary Charger 24V DC, 10 Amp.
117Supply & Fixing in DC 12V Stop Solenoid Coil suitable for DG Set complete all as specified and directed.
118Supply & Fixing in DC 24V Self Solenoid Coil suitable for DG Set complete all as specified and directed.
119Supply and replacement of Battery 12 Volt 100 AH suitable DG set complete all as specified and directed.
120Supply and replacement of Battery 12 Volt 180 AH suitable DG set complete all as specified and directed.
121M&L for repairing of self starter of DG set capacity 12 Volts including transporting upto workshop to carry out necessary replacement of burnt copper winding with new copper winding/ coil of existing gauge from rotor and stator coil, cleaning of slots, dryings varnishing and proper insulating to winding complete all as specified and directed.
122All as per item No 121 above but capacity 24 Volts.
123M&L for carrying out complete over hauling/servicing of DG set panel /AMF panel/control panel including checking and rewiring of faulty electrical circuit using 1.5 Sqmm FRLS copper conductor for DG set of any type/make /capacity and making all electric connection and testing for smooth operation complete all as specified and directed.
124Rectification of fault in AMF panel of DG set and testing on load ranging from 25 to 200KVA complete all as specified and directed.
125M&L for replacement of relay of AMF panel complete all as specified and directed.
126M&L for replacement of display panel of AMF suitable for DG set rating 40 to 100 KVA along with all connections and push buttons for mode change and start stop button complete all as specified and directed.
127M&L for replacement of display panel of AMF suitable for DG set rating 125 to 250 KVA along with all connections and push buttons for mode change and start stop button complete all as specified and directed.
128Supply and fixing in repair IOPS Module digital display controller unit suitable for exisitng DG Set complete all as specified and directed.
129S&F MCCB 3 pole 415 volts in repairs,fixed type 100 Amps with braking capacity 16 KA.after taking out old U/S one complete all as specified and directed.
130S&F in repairs MCCB 3 pole 415 volts fixed type 200 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
131S&F in repairs MCCB 3 pole 415 volts fixed type 250 Amps with braking capacity 36KA after taking out old U/S one complete all as specified and directed.
132S& F Panel LED indication lamps (R/Y/B) complete all as specified and directed.
133S&F Rotary switch of existing make L&T complete all as specified and directed.
134S&F in repairs digital volt meter ,415 volts,including after taking out old unserviceable one complete all as specified and directed.
135S&F in repairs digital Ammeter,415 volts grade,100 Amps rating,including and after taking out old unserviceable one complete all as specified and directed.
136M&L for attending of any breakdown of standby power supply in any location, whenever required round the clock, rectify the fault and restore the standby supply within three hours after receipt of complaint of any nature ie engine, alternator, control panel/AMF pael etc complete all as specified and directed.Note- (i) The cost of replaced spare parts will be paid and measure seperatly. (ii) If complaint is not attended by contractor with in five hours the penalty of Rs 500/- per hour to be imposed and amount of penalty will be deducted from RAR. (iii) The cost of transportation (to and from) for all kind of necessary equipment /T&P shall be arranged/brought by contractor to complete the job at site or at E/M Yard and no extra cost shall be paid to the contractor to this effect. (iv) Complaint shall be lodged by telephonically so contractor to specify the telephone/mobile No who will receive the complaint round the clock.
137Supply install testing and commisioning of Free standing floor mounted IP 42 automatic mains failure control panel suitable for 50KVA DG set including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto between AMF panel, LT Panel and DG Set including connection interconnection etc. 1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering5. Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA (Phase & Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor 10. Supply failure timer 11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories
138Supply install testing and commisioning of Free standing floor mounted IP 42 automatic mains failure control panel suitable for 100KVA DG set including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminium) and control (copper ) cabling of suitable size upto between AMF panel, LT Panel and DG Set including connection interconnection etc. 1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.2. Auto/Manual/Test/Off selector switch3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay).4. 3 Sets of current transformers 15 P 10 accuracy for protection and 15 VA class-I for metering5. Energy analyser unit to indicate current, Voltage( L-N & L-L), kW, kVA (Phase & Total), Frequency, KWH, PF.6. LED Indicating lamps for load on mains and load on set7. Fuse/ MCB for instruments8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor 10. Supply failure timer 11. Restoration timer12. Control unit with three impulse automatic engine start/stop and failure to start lockout.13. Impulse counter with locking and reset facility.14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning16. Protection for over/under Frequency, Loss of AC sensing, Over Current, Unbalancing load with suitable number of relays and accessories
139M& L for welding each canopy door to the outer unit for proper closing and opening including hinges and repainting complete all as specified and directed.
140M&L spray gun painting of generator upto 62.5 KVA in existing colour with smooth finishing compete all as specified and as directed.
141M&L spray gun painting of generator 75 KVA upto 125 KVA in existing colour with smooth finishing compete all as specified and as directed.
142M&L spray gun painting of generator 250 KVA in existing colour with smooth finishing compete all as specified and as directed.
143S & F in repairs Earth test box made of powder coated, 3.15 mm thick, CRCA sheet,20 cm x 20 cm x 10 cm size conforming to CPRI approved and IP-65 protection class,right hinge openable type including mounting arrangement such as making hole in wall,providing MS clamp,nut,bolt etc complete manufactured through approved manufacturers, complete all as specified and directed.
144Supply and fixing in replacement of unserviceable GI tubing medium grade with all fittings complete laid in trenches / on walls / on ceiling / roof etc incl necessary suitable size of MS clamps / saddling on walls / ceiling etc including taking down complete all as specified and directed.
145All as per item No 145 above but 100 mm dia.
146All as per item No 145 above but 80 mm dia.
147All as per item No 145 above but 50 mm dia.
148All as per item No 145 above but 40 mm dia.
149All as per item No 145 above but 25 mm dia.
150All as per item No 145 above but 20 mm dia.
151All as per item No 145 above but 15 mm dia.
152Supply and fix connected Gun metal gate valve ISI marked with iron wheel head screwed both ends for iron pipes and fixed for the following sizes including taking down of unserviceable gate valves complete all as specified and directed.
153All as per item No 153 above but 50 mm dia.
154All as per item No 153 above but 25 mm dia.
155All as per item No 153 above but 20 mm dia.
156All as per item No 153 above but 15 mm dia.
157Taking out existing unserviceable/ broken / damaged CI sluice valve from its existing position and Supply & fixing CI sluice valve stainless steel, spindle CI body class –I, PN-1.6 ISI marked both end flanged and drilled and fixed by means of new nuts, bolts and washer including providing rubber gasket of suitable thickness of following sizes complete all as specified and directed.
158All as per item No 158 above but 100 mm dia bore of pipe
159All as per item No 158 above but 80 mm dia bore of pipe
160All as per item No 158 above but 50 mm dia bore of pipe
161M&L for replacement of unservicable CI non return valve type IS 5312 flanged ends 100 mm dia complete all as specified and directed.
162M&L for replacement of unservicable CI non return valve type IS 5312 flanged ends 150 mm dia complete all as specified and directed.
163S&F brass foot valve of size 80mm suction pipe complete all as specified and directed.
164M&L for cleaning and degermination inside the RCC Underground reservoir tank of capacity from 30000 to 70000litre compressing the following seven stage cleaning and sterilization of water tanks through bacteriological treatment by using TERBAC G5/INCHLOR-5/NB-10, TERBAC-G-65/ INOXI-60/NB-69 and ULTRA VIOLET RAY all as specified and directed.(a) First Stage: Drain out the water by using exit valve or with high capacity dewatering system or any other suitable method approved by Engineer-in-Charge.(b) Second Stage: Cleaning all the algae formation inside the tank using TERBAC G-10/INCHLOR-5/NB-10.(c) Third Stage: Cleaning with fresh water by high speed jet pump with pressure of 5 PSI.(d) Fourth Stage: First bacteria screening i.e de-germination by Sterilization using TERBAC GS/INCHLOR-5/NB(e) Fifth Stage: Cleaning the floor of the water tank by heavy duty industrial vacuum cleaner and sludge sucker maximum 1200W with suitable heavy duty rugged motor to make tank/sump free of any foreign and loose particles of any nature.(f) Sixth Stage: Second bacteria screening ie by sterilization using UV RAYS by heavy duty UV radiation which shall have 360 degree of sterilization with in the tank to kill all suspended bacteria (The radiation shall be portable and effective for sterilization of drinking water tanks for diminution of floating and suspended bacteria)(g) Seventh Stage: Third bacteria screening is to sterilize the floor and wall of the water tank by using strong oxidizing agent TERBAC G65/INOXI-60/NB-69 to disinfect the tank from all harmful pathogens.
165Contractor will submit Govt. laboratory test certificate of TERBAC G5/INCHLOR-5/NB-10, TERBAC-G-65/ INOXI-60/NB-69 & TERBAC-G10 before using/ cleaning of tanks / sumps.(ii) Entire T&P etc complete should be arranged by the contractor at their own.(iii) The entire work should be carried out through specialist agency of tank clean process of any franchises or any other MES approved firm having experiance in executing of technology of seven stages sterilization.Necessary approval of agency shall be obtained before commencement of work from GE through Engr-in-Charge(iv) After cleaning of the tank, necessary completion certificate confirming the completion of sterilization of water tank shall be issued by the service provider.(v) After cleaning the tank \\"Date of cleaning\\" should be written over the outer surface of tank by synthetic enamel paint with lettering not less than 100mm height.(vi) All safety equipments required like safety helmets, Gumboots, safety belt, mask, safety googles and necessary insurance for safety of working labours to execute the work is responsibility of the contractor and rates quoted shall be deemed to be inclusive of the same.(vii) Contractor will be responsible for rectification of complaints occurred during cleaning the tank i.e no water in tank/over flow due to broken of float valve/blockage etc deemed
166Supply and mixing by using professional workers Calcium hypochlorite free flowing and free from lumps and without substance beyond acceptable limit as given in IS 10500 (2012) in treated and disinfected water packed in 20-25 kg/ 40-45 kg drums to avoid hazard in place of high ambient temperature with following parameters : (a) Available Chlorine : Min 65% residual chlorine (b) Max Stability (loss of chloride on basis of available chloride): 1/15(c) Min Particle Size (passing through 1.70 mm IS Seive) : 99.5% by mass (d) Max water insoluble Matter: 6%(e) Max Calcium Hydroxide : 4%(f) Max Sodium Chloride :15%
167Supply, installation, commissioning and testing of totally enclosed outdoor type LT Panel weldless cubical Kiosk in modular bolted construction type dust and vermin proof floor mounted type (IP-65 degree of protection ) made out of 3 mm thick CRCA sheet of recommended size.All sheet metal parts separately chemically treated with 7 tank treatment process. The panel having both side opening door with locking arrangement.all doors fixed with aluminium hinges with suitable size nut bolts and shall have flexible fixing of each switchgear and controlgrae compartment with cable alley tray of size not less than 30 cm. duly painted with two coats of synthetic enamel paint powder coated, bus bar 800 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50 HZ AC supply ,hibling , cable entry boxes , cable gland and LT panel shall be mounted on iron angle frame made out of 50 X 50X 6 mm frame with 4 no. legs size nit less than 45 cms fixed with nut bolts of suitable size (bottom portion of the panel) , LT panel shall be grouted in the trolly with suitable size of angles, nut, bolts, washers etc complete all as directed and suitable for and including the following .INCOMMER(i) MCCB 4 pole 415 volts 100 amp, rating thermal magnetic prottection unit with rupturing capacity 25 KA with Rotary handle complete , - 01 No as incomer.OUTGOING(ii) MCCB 4 pole 415 volts with rating thermal magnetic prottection unit rupturing cap 25 KA,with Rotary handle , 63 amps - 03 Nos for outgoing , (iii) Fully automatic star delta starter 02 Nos.(iv) MCB SPN 32 AMP 03 Nos . (v) Indicator set RYB -01 Set of 3 pcs only .(vi) Multifunction digital panel meter suitable to display amps, volts, frequency etc - 01 No including CTs of appropriate ratio. (Vii) MCB ,SP 10 amps 03 Nos ( for metering equipment )(viii) All accessories prewired with suitable size copper conductor cable or strip including foundation as per manufacturer instruction all as required and directed.
168S&F in replacement of DOL starter for 10 HP with complete protection complete all as specified and directed.
169S & F pneumatic timer 0.1-60 seconds time delay,suitable for mounting in starter panel ,12.5 HP capacity,415 volts AC complete all as specified and directed.
170S & F pneumatic timer 30-120 seconds star delta time delay model GIC complete all as specified and directed.
171S & F thermal over load relay,5-15 Amps range,240-440 volts complete all as specified and directed.
172S&F in replacement of 3 pole power contactor with NO / NC block suitable for MNX 50 to 110 complete all as specified and directed.
173S&F in replacement of 3 pole power contactor with NO / NC block suitable for MNX 40 to 45 complete all as specified and directed.
174Supply and fix in replacement amp meter digital type as per existing size and type complete all as specified and directed.
175Supply and fix in replacement volt meter digital type as per existing size and type complete all as specified and directed.
176S & F Volt Meter 0 to 500 Volts digital square type 4” complete all as specified and directed.
177S & F Ammeter 0 to 200 Amps digital Square type 4” complete all as specified and directed.
178S&F in repair CT 30/5 to 200/5 complete all as specified and directed.
179S & F Selector switch for Volt meter /Ampmeter complete all as specified and directed.
180S & F Indicating Lamp set of three (Red , Yellow & Blue) complete all as specified and directed.
181Supply and fix in repairs Decrin dozing pump 100 PSI 40 GPD Capacity and testing complete all as specified and directed.
182Supply and fix in replacement of circuit of speed of Dozing pump complete all as specified and directed.
183Supply and fix in replacement of injector Nozzle of Decrin dozing pump complete all as specified and directed.
184Supply and fix in replacement of Regulator Knob of dozing pump complete all as specified and directed.
185Supply and fix in replacement of power cord of dozing pump 2 mtr long plug top 5 AMP 240 volt AC complete all as specified and directed.
186Material and labour for \\"lifting and Lowering of any capacity\\" Submersible Pump Set of capacity 7.5 HP for repair/ Overhauling /rewinding /devolpment incl increasing the length of delivery pipe/or any other requiremwnt at site at tube well installation with man power/Chain Pulley arrangement including shifting to local workshop for repair and to bring back after repair at site including testing and commisioning complete all as specified and directed.Note :- Any minor part if required will be provided by contractor without any extra cost.
187M & L for Dismantling and strip opening of burnt submersible pump of capacity 7.5HP including cuttting removing burnt winding wire from stator assembly and preparing slots , rewinding the same with super enamled water proof copper winding wire of suitable gauge with necessary insulation materials varnising etc and reassembling stator rotor assembly with pump testing, commmisioning such as (i) Impeller GM . (ii) Distance bush SS.(iii) Guide Bush (iv) Neck ring gun metal (v) Impeller key (vi)Guide van (vii) Sand Guard including tranportation to local work shop etc ccomplete all as specified and directed.
188M & L for Dismantling and strip opening of burnt Booster pump motor of capacity upto 10 HP including cuttting removing burnt winding wire from stator assembly and preparing slots , rewinding the same with super enamled water proof copper winding wire of suitable gauge with necessary insulation materials varnising etc and reassembling stator rotor assembly with pump testing, commisioning including tranportation to local work shop etc complete all as specified and directed.
189M & L for Dismantling and strip opening of burnt Booster pump motor of capacity upto 20 HP including cuttting removing burnt winding wire from stator assembly and preparing slots , rewinding the same with super enamled water proof copper winding wire of suitable gauge with necessary insulation materials varnising etc and reassembling stator rotor assembly with pump testing, commisioning including tranportation to local work shop etc complete all as specified and directed.
190Supply and fixing in repair flat PVC insulated Sheathed, Copper conductor,4 sq mm ,3 core (flexible) cable,1100 Volts complete all as specified and directed.
191Supply and fixing in repair flat PVC insulated Sheathed, Copper conductor,6 sq mm ,3 core (flexible) cable,1100 Volts complete all as specified and directed.
192Attending of complaints by deploying sufficient labour for rectification of leakage of UG water pipe lines of size 200/150 mm bore of any description such as CI/DI/GI pipe line at any location including necessary excavation in any type of soil (approx 2 meter length,width 1.5 meter ,depth 1.5 meter) dewatering complete by using pump set as per site requirement, cutting existing pipe lines including repairs with suitable flanges, Joints or any other material etc complete all as specified and as directed.
193All as per item No 193 above but of size 100mm dia pipe line
194All as per item No 193 above but of size 50/40 mm dia pipe line
195All as per item No 193 above but of size 25/20 mm dia pipe line
196Construction of valve chamber in PCC 1:4:8 masonry built in CM(1:4) with MS covers 3 mm thick and locking arrangement including excavaton and earth works PCC (1;4;8) type D2 for foundation PCC bed/coping in cement concrete (1:2:4) type B1 plastering 15 mm thick with Cm 1:4 painting with one coat of bituminous black paint on all steel surface all as specifiedd complete all as specified and directed for the following sizes chambers :-
1971350 mm x 1000 mm x 1200 mm internal dimension
198900 mm x 900 mm x 1000 mm internal dimension
199900 x 600 x 1000 mm internal dimension
200Supply and mixing by using professional workers Alum crystal super quality complete all as specified and directed.
201S&F Water level Indicator for OH/UG tank, water level display wired sensor security system with alaram system having power input 230V, 50 Hz, including electrical cable for connection complete all as specified and directed.
202Supply only chlorine test kit with PH colured sample complete with all testing fitment and OT solution in rexine box complete all as specified and directed.
203M&L for chemical and bacteriological analysis of Raw water collected from all the pump house complete all as specified and directed.
204M&L for chemical and bacteriological analysis of chlorinated water collected from distribution line complete all as specified and directed by Engineer-in-Charge.
205Disconnecting & dismantling of pump set from the foundation breaking the existing defective PCC foundation in any size, shape M&L for PCC 1:2:4 type B-2 using 12.5 mm graded aggregate for foundation of any size of motor pump set from 50 HP to 75 HP capacity pump set and fitting pumping set in position with base frame painted with synthetic enamel black paint complete all as specified and directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56275868
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 48 Lakhs
LAST DATE 16-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maintenance To Lt Panels, Feeder Pillar Boxes, Earthing, Dg Sets, Amf Panels Oht Reservoir, Ug Sump, Rising Main Distribution And Other E/M Works At Af Stn Naraina Under Aor Of Ge (Af) Faridabad
Basic Detail
Tender No GE (FBD)/AF-T-39/2026-2027
Bidding Type Tender
Location
City New Delhi
State Delhi
Key Dates
Publish Date 02 Jul 2026
Submission Date 16 Jul 2026
Open Date 18 Jul 2026
Finance
Tender Value 48 Lakhs
Tender Fee 500
EMD 96000
Exemption Available
Document List
3c57c84f-0988-47eb-ad84-3c2828d3729f.html
BOQ_868769.xls
Tenderdocu39.pdf
Tendernotice_1 (1).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 02, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 16, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 10 days
Jul 18, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 12 days

Tender Documents

Download All (ZIP) ↓
html

3c57c84f-0988-47eb-ad84-3c2828d3729f.html

xls

BOQ_868769.xls

pdf

Tenderdocu39.pdf

pdf

Tendernotice_1 (1).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders