Tender For Repair/Maint/Rewiring Of Otm Area Of Hq J&Bsa, Stn Hq, Deo, Lao, Pao (Or), Ssi, Mes Ib & Mes Office And Repair/Maint Of Oh, Ug Sump & Chemicals At Danapur Under Ge Danapur Cantt

Issued by Statutory Bodies & Commissions/Committees · Patna, Bihar
Tender Value
45 Lakhs
Estimated cost
Bid Submission
23 Jul 2026
15 days left
EMD
90000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Patna → Bihar
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maint/Rewiring Of Otm Area Of Hq J&Bsa, Stn Hq, Deo, Lao, Pao (Or), Ssi, Mes Ib & Mes Office And Repair/Maint Of Oh, Ug Sump & Chemicals At Danapur Under Ge Danapur Cantt

BOQ

Name of Work:- REPAIR/MAINT/REWIRING OF OTM AREA OF HQ J&BSA, STN HQ, DEO, LAO, PAO (OR), SSI, MES IB & MES OFFICE AND REPAIR/MAINT OF OH, UG SUMP & CHEMICALS AT DANAPUR UNDER GE DANAPUR CANTT
Sl. No. Item Description
1Taking down carefully copper / aluminium point wiring (light, fan, switch,socket or power, Bell & Two way point) complete with fitting such as switches, sockets, ceiling rose,sketch light fittings etc, and making good the disturbed surface of walls and floors etc complete all as specified and directed.
2Taking down carefully main switches DB's/ MCB DB's and making good the disturbed surfaces of walls etc complete all as specified and directed.
3Taking down carefully copper / aluminium sub main wiring including teak wood batten / conduit and making good the disturbed surface of walls as directed.
4M & L for Point wiring with PVC insulated PVC unsheathed electric FRLS cable 1100V grade single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in & including non metallic rigid PVC conduit ISI marked medium grade not less than 20 mm dia with all conduit accessories in concealed wiring system by cutting of wall and making good disturbed surface of wall (cutting except on ceiling for fan point only, on ceiling PVC conduit on surface will be used) & 1.5 sqmm green PVC insulated unsheathed copper conductor as a earth wire connected to earth dolly by providing lugs excluding MS boxes for mounting switches, sockets, fan regulators etc for one light/fan point controlled by one switch complete all as specified and as directed.
5Same as item No 4 above but one bell point controlled by one bell Push
6Same as item No 4 above but one 5 Amps socket out let point controlled by one switch on same board with other switches.
7Same as item No 4 above but one 5 Amps socket out let point on independent board controlled by one switch.
8Same as item No 4 above but wiring including earth wire with 2.5 sqmm single core copper conductor for one socket out let 15/16 amps point on the independent board.
9Same as item No 4 above but wiring including earth wire with 4 sqmm single core copper conductor for one socket out let 15/16 amps point on the independent board.
10M & L for Point wiring with PVC insulated PVC unsheathed electric FRLS cable 1100V grade single core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area drawn in existing concealed conduit and 1.5 sqmm green PVC insulated unsheathed copper conductor as a earth wire connected to earth dolly by providing lugs including MS boxes for mounting switches, sockets, fan regulators etc for one light/fan point controlled by one switch complete all as specified and as directed.
11Same as item No 10 above but one 5 Amps socket out let point controlled by one switch on same board with other switches.
12Same as item No 10 above but one 5 Amps socket out let point on independent board controlled by one switch.
13Same as item No 10 above but wiring including earth wire with 2.5 sq mm single core copper conductor for one socket out let 15/16 amps point on the independent board.
14Supply and fixing switch piano flush button single pole one way 5 amps, 240 Volts complete all as specified and directed.
15Supply and fixing socket outlet flush type 5 Amps, 5 pin, 240 Volts complete all as specified and directed.
16Supply and fixing switch piano flush button single pole one way 15 Amp 240 volt complete all as specified and directed.
17Supply and fixing socket outlet flush type multipurpose 2 in 1, 3 pin 5 and 15 Amp, 240 volts complete all as specified and directed.
18Supply and fixing bell push single pole, 6 Amps, 240 Volts, flush type complete all as specified and directed.
19Supply and fixing Ceiling rose surface bakelite 63.5 mm dia three terminal complete all as specified and directed.
20Supply and fixing for batten/angular fittings complete all as specified and directed.
21Supply and fixing for electronic Fan regulator socket type compatible with BLDC fan complete all as specified and directed.
22Supply and fixing in repair Bell, AC 240 Volts,single pole,ding dong type complete all as specified and directed.
23Supply and fixing in repair white/color finished single mounting modular plates with inner & outer cover suitable for housing modular accessories suitable for one module box complete all as specified and directed.
24Same as item No 23 above but suitable for 2 modules
25Same as item No 23 above but suitable for 3 modules
26Same as item No 23 above but suitable for 4 modules
27Same as item No 23 above but suitable for 6 modules
28Same as item No 23 above but suitable for 8 modules
29S&F sheet metal boxes concealed in wall suitable for housing modular accessories for 1 or 2 modules complete all as specified and directed.
30Same as item No 29 above but suitable for 3 modules
31Same as item No 29 above but suitable for 4 modules
32Same as item No 29 above but suitable for 8 modules
33Supply and fixing in repair modular Switch 6 Amps single pole, one way complete all as specified and directed .
34Supply and fixing in repair Modular Socket outlet, multi purpose, 5 Pin 6 Amps flush type complete all as specified and directed .
35Supply and fixing in repair Modular Bell push flush type,6 Amps fixed complete all as specified and directed
36Supply and fixing in repair Modular Socket outlet, multi purpose, 6 pin 16 Amps universal socket complete all as specified and directed .
37Supply and fixing in repair Modular Switch 16 Amps single pole, one way complete all as specified and directed .
38Supply and fixing in repair modular fan regulator of four step type compatible with BLDC fan complete all as specified and directed.
39S & F in replacement of switch piano flush button single pole one way 5/6 Amp 240 volt complete all as directed.
40S & F in replacement of switch piano flush button single pole one way 15/16 Amp 240 volt complete all as directed.
41S&F in replacement of socket outlet flush type multipurpose 2 in 1, 3 pin 5/6 and 15/16 Amp, 230 volts complete as directed.
42S&F in replacement of unservicable socket outlet flush type multipurpose 2 in 1,3 pin 5 .Amp, 230 volts complete as directed.
43S&F in replacement of switch socket outlet combination flush type multipurpose 2 in 1, 3 pin 5 and 15 Amp, 230 volts complete as directed.
44S&F in replacement of switch socket outlet combination flush type with box multipurpose 2 in 1, 3 pin 5 and 15 Amp, 230 volts complete as directed.
45S&F in replacement bell push single pole one way 5 Amp, 240 volt flush type as directed.
46Supply and fixing in repair plastic laminated bakelite sheet cover of Hylam brand 2.8 mm thick including cutting holes for switches, sockets etc as pre requirement including fixing with machine screws and washer for size 250 mm X 300mm complete all as specifed and directed.
47Same as item No 46 above but of size 200mm X 250 mm
48Same as item No 46 above but of size 200mm X 150 mm
49Same as item No 46 above but of size 150mm X 100 mm
50Same as item No 46 above but of size 100mm X 100 mm
51Supply and fixing in repair Cast Iron/ pressed steel terminal rectangular sunken boxes 60 mm deep for mounting, switches, sockets, fan regulator, etc. with 3mm thick plastic laminated sheet cover of size 250 x 300 x 50 mm complete all as specified and directed.
52Same as item No 51 above but of size 200mm X 250 mm
53Same as item No 51 above but of size 200mm X 150 mm
54Same as item No 51 above but of size 150mm X 150 mm
55Same as item No 51 above but of size 100mm X 100 mm
56Supply and fix vertical TPN distribution board 4 way suitable for 160 Amp MCCB with 160 Amp MCCB as incomer double door steel sheet, powder coated, fitted with bus bar, din rail, neutral link, Earth bar complete all as specified and directed.
57S&F sheet metal enclosure for MCB DB double door type, triple pole and neutral 4 way 415Volts with 100/125 Amps rated bus bar of suitable size plate and common neutral link, epoxy powder coated, factory made complete without MCB and with enclosure blank plates for unused way complete all as specified and directed.
58S&F sheet metal enclosure for MCB DB double door type, single pole and neutral 12 way 240 Volts with 100/125 Amps rated bus bar of suitable size plate and common neutral link, epoxy powder coated, factory made complete without MCB and with enclosure blank plates for unused way complete all as specified and directed.
59S&F sheet metal enclosure for MCB DB double door type, single pole and neutral 8 way 240 Volts with 100/125 Amps rated bus bar of suitable size plate and common neutral link, epoxy powder coated, factory made complete without MCB and with enclosure blank plates for unused way complete all as specified and directed.
60Supply and fixing MCB SPN 40 to 63 amps 10 KA, C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed.
61Supply and fixing MCB SP 240 volts 5 to 32 Amps, 10 KA breaking capacity, 'C' type including connection with suitable size aluminium / copper lugs complete all as specified and directed.
62Supply and fixing MCB TPN 50 to 63 amps 10 KA ,C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed.
63Supply and fixing MCB TPN 100 amps 10 KA, C-series including connection with suitable size aluminium / copper lugs complete all as specified and directed .
64Supply and Fixing wall/surface mounting luminaires integrated LED Batten 18/20/22 W, 6000 K,100 lumens/watt , 230V with extruded Aluminium housing 4 feet long with frosted PMMA/PC diffuser & integrated electronic driver complete including Electrical connection with PVC three core copper flexible wire & all necessary fixing arrangements all as specified and directed.
65Supply and fixing wall/surface mounting luminaires (Mirror Light) integrated LED Batten( 2 feet) 10/12 W, 6500 K, 230V ,100 lumens/watt,with PVC housing & integrated electronic driver complete including Electrical connection with PVC three core copper flexible wire & all necessary fixing arrngements all as per specified and directed.
66S&F in repairs of surface/recess type square/round LED 12W downlighter complete all as specified and directed.
67S & F wall light metal finish with frosted glass cover indoor type energy efficient ideal for relaxing compatible with B22 bulb base type excluding bulb complete all as specified and directed.
68Supply and fix wall mounting fans 400 mm (white) string controlled oscillating type including provn of flexible three core cable from ceiling rose to terminal for making connection, fitting on wall including all necessary fixing accessories complete all as specified and as directed.
69Supply and fix electric water heater,storage type with stainless steel inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate,NRV, connection piece etc. complete all as specified and directed.
70Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250mm complete all as specified and directed.
71S&F recessed mounting fitting 36/42 watt ultra modern design architectural LED luminaire which provides soft-light and glare free symmetrical illumination suitable for Armstrong / Grid Ceiling including LED driver and 36/42 watt lamp incl all accessories complete all as specified and directed.
72Supply and fixing LED light fitting for bldg security lighting energy saving & environmental friendly long life versatile pressure die-cast housing with individual high power LED as light source and lens embedded PC cover of capacity 35 watt 240 volts AC 50 Hz , IK 07 and IP 66 protection suitable for 40/25 mm dia GI pipe bracket including three years on site warranty from manufacturer complete all as specified and directed.
73M & L for security wall light bracket made out of GI pipe light grade 40 mm dia 0.9 metre length bent to shape and reduced to required size at top upto 1.5 metre length by cutting, welding and well finishing including MS clamp of flat iron of size 40x6 suitable length 2 sets complete with drilling, hole, fixing with nuts bolts and washers including painted with two coats of aluminium paints over a coat of red oxide primer including dismantling one complete all as specified and directed.
74S&F in replacement sub main wiring with two single core PVC insulated (FRLS) unsheathed multistranded copper conductor of size 4 sqmm nominal cross sectional area and one run of 4 sqmm nominal cross sectional area PVC insulated (FRLS) unsheathed multistranded copper conductor green colour as continuous earth wire drawn in and including not less than 20mm dia 'medium grade' PVC concealed conduits (ISI marked) and fittings complete all as specified and directed.NOTE:- One unit length shall measured as two run of main wire and one run of conduit & earth wire.
75S&F in replacement sub main wiring with two single core PVC insulated (FRLS) unsheathed multistranded copper conductor of size 6 sqmm nominal cross sectional area and one run of 6 sqmm nominal cross sectional area PVC insulated (FRLS) unsheathed multistranded copper conductor green colour as continuous earth wire drawn in and including not less than 20mm dia 'medium grade' PVC concealed conduits (ISI marked) and fittings complete all as specified and directed.NOTE:- One unit length shall measured as two run of main wire and one run of conduit & earth wire.
76S&F in replacement sub main wiring with two single core PVC insulated (FRLS) unsheathed multistranded copper conductor of size 2.5 sqmm nominal cross sectional area and one run of 2.5 sqmm nominal cross sectional area PVC insulated (FRLS) unsheathed multistranded copper conductor green colour as continuous earth wire drawn into existing conduit complete all as specified and directed.NOTE:- One unit length shall measured as two run of main wire and one run of earth wire.
77Supply and fixing in replacement for 1.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed.
78Supply and fixing in replacement for 2.5 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed.
79Supply and fixing in replacement for 4 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed.
80Supply and fixing in replacement for 6 sqmm single core copper,multistandard PVC insulated (FRLS) unsheathed, cable 1100 volts grade complete all as specified and directed.
81S&F in replacement 1100V grade heavy duty cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connection ,one twin core cable flat or circular stranded 10 sqmm aluminiuam conductor complete all as specified and as directed.
82S&F in replacement service cable PVC insulated aluminium conductor served with inner sheathing of PVC tape and overall PVC sheathed in service connection ,one twin core cable flat or circular strande 4 sqmm aluminiuam conductor complete all as specified and as directed.
83M&L for Rigid non metallic PVC conduit ISI marked, medium grade, inclusive of all fitting such as tees,bends. Junction boxes, elbows saddles. Pipe hooks,couples and lock outs etc 25 mm external dia, fixed on surface mounted complete and making good disturbed surfaces in repairs all as directed.
84M&L for Rigid non metallic PVC casing caping ISI marked, medium grade,not less than 25 mm base size inclusive of all fitting such as tees,bends. Junction boxes, elbows saddles hooks,couples and lock outs etc fixed on surface mounted complete and making good disturbed surfaces in repairs all as directed.
85Supply & fixing in repair AC Box, socket, with single pole MCB 25 Amps 240 volts fixed in repairs complete all as specified and directed.
86Supply and fixing in repair of Earthing for panel with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised earth lead wire 4.0mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead strip protected by GI pipe 40 mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed.
87M&L for draining out existing water from RCC OH tank of following capacity and staging after scraping, cleaning inside surfaces with steel brush, removing the sediment ring material accumulated at the bottom of the tank, cleaning throughly the inside surfaces with bleaching powder and wash the same with clean water and applying one coat of cement base paint @ 0.30 Kg per sqm and marking the date of cleaning with synthetic enamel paint on external surface including two coats of synthetic enamel paint on all pipes of different sizes such as rising main, delivery pipe, over flow pipe & wash out pipe etc. as per colour code complete all as directed.
881.00 Lakh gallon at 18.3 metre staging.
890.50 Lakh gallon at 18.3 metre staging.
900.50 Lakh gallon at 12.2 metre staging.
91M&L for clearing of OH tank premises area and Pump houses including removal of bushes,weeds,loose soil, debris, plastic waste and other unwanted materials, levelling of ground surface and disposal of rubbish outside the premises complete all as directed for following.
921.00 Lakh gallon at 18.3mtr staging.( Area - 21.00mtr x 19.70 mtr = 413.70 Sqr mtr x 2 Job)
930.50 Lakh gallon at 18.3mtr staging.( Area - 21.80mtr x 21.00mtr = 457.80 Sqr mtr x 2 Job)
940.50 Lakh gallon at 18.3mtr staging.( Area - 25.50mtr x 22.70mtr = 578.85 Sqr mtr x 2 Job)
950.50 Lakh gallon at 12.2mtr staging.( Area - 05.25mtr x 09.5mtr = 49.87 Sqr mtr x 2 Job)
960.50 Lakh gallon at 18.3mtr staging. ( Area - 31.40mtr x 25.20mtr = 791.28 Sqr mtr x 2 Job)
970.50 Lakh gallon at 18.3mtr staging.( Area - 16.80mtr x 12.40mtr = 208.32 Sqr mtr x 2 Job)
980.50 Lakh gallon at 12.2mtr staging. .( Area - 64.10mtr x 21.30mtr = 1365.33 Sqr mtr x 2 Job)
99Pump house No 1 (Area- 40.00 mtr x 15.50 mtr = 620 Sqr mtr x 2 Job)
100Pump house No 2 (Area- 60.00 mtr x 20.70mtr = 1242 Sqr mtr x 2 Job)
101Pump house No 3 (Area- 35.00 mtr x 25.50 mtr = 892.50 Sqr mtr x 2 Job)
102M&L for cleaning of static semi under ground rain water sump of size 4.5 mtrs dia and 15 mtrs depth and removing the muds, sediment material accumulated at the bottom of the tank including scraping, cleaning inside surfaces with steel brush, cleaning throughly the inside surfaces with bleaching powder and wash the same with clean water and applying one coat of cement base paint @ 0.30 Kg per sqm and marking the date of cleaning with synthetic enamel paint on external surface including two coats of synthetic enamel paint on MS top cover, pipes etc complete all as specified and directed.
103Same as item No 89 above but size 3.5 mtrs dia and 15 mtrs depth.
104Same as item No 89 above but size 2.5 mtrs dia and 10 mtrs depth.
105M&L for clearing of static semi under ground rain water collection well premises area, including removal of bushes,weeds,loose soil, debris, plastic waste and other unwanted materials, levelling of ground surface and disposal of rubbish outside the premises complete all as directed for following.
106UG sump of size 4.5 mtrs dia and 15 mtrs depth ( Area 42.30 mtr x 28.50 mtr = 1205.55 Sqr mtr x 2 Job )
107UG sump of size 3.5 mtrs dia and 15 mtrs depth. ( Area- 20.30 mtr x 12.00 mtr = 243.6 Sqr mtr x 2 Job )
108UG sump of size 2.5 mtrs dia and 10 mtrs depth.( Area- 10.30 mtr x 07.00 mtr = 72.10 Sqr mtr x 2 Job )
109Supply of industrial grade Calcium Hypochlorite Granules with minimum 65% available chlorine content, in dry granular form, suitable for water disinfection.The chemical shall comply with relevant standards (IS 1168 or equivalent), with low moisture content (<1%) and high chlorine availability, complete all as specified and directed.
110Supply of Bleaching Powder (Ca(OCl)₂) in powder form, suitable for water disinfection and treatment of potable water, swimming pools, and wastewater treatment systems, available Chlorine Content Minimum 33–35%, complete all as specified and directed.
111Supply of high-quality Copper Sulphate Pentahydrate (CuSO₄·5H₂O) in crystalline or powder form, Minimum 98% Pure, Copper content>25-26%, Water soluble, Free from iron or other heavy metal contamination complete all as specified and directed.
112Supply and replacing the existing old/damaged water quality testing kit from pump house/swimming pool and supplying new portable digital water quality testing kit suitable for testing free chlorine, pH value, total alkalinity and residual disinfectant, complete with reagent solution/tablets, calibration solution, test vials, carrying case, instruction manual and all necessary accessories complete all as specified and directed.
113Carry out physico-chemical, biological testing of water of bore well at different pump house i.e PH-1, PH-2, PH-3 & CDA/NCC Patna from Govt Lab/Govt Authorised Laboratory all as directed and submitting the report to Eng-in-charge complete all as specified and directed. Note: Rates quoted is deemed to be included for testing of one sample. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56260149
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 45 Lakhs
LAST DATE 23-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint/Rewiring Of Otm Area Of Hq J&Bsa, Stn Hq, Deo, Lao, Pao (Or), Ssi, Mes Ib & Mes Office And Repair/Maint Of Oh, Ug Sump & Chemicals At Danapur Under Ge Danapur Cantt
Basic Detail
Tender No CA NO GE/DNR/T-35 of 2026-27
Bidding Type Tender
Location
City Patna
State Bihar
Key Dates
Publish Date 02 Jul 2026
Submission Date 23 Jul 2026
Open Date 30 Jul 2026
Finance
Tender Value 45 Lakhs
Tender Fee 500
EMD 90000
Exemption Available
Document List
BOQ_868786.xls
cfca4312-ac66-4a5a-876a-1f8e01c97829.html
Credit9071.pdf
ParticularSpecification9071.pdf
Tender9071.pdf
Tendernotice_1 (1).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 02, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 23, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 15 days
Jul 30, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 22 days

Tender Documents

Download All (ZIP) ↓
xls

BOQ_868786.xls

html

cfca4312-ac66-4a5a-876a-1f8e01c97829.html

pdf

Credit9071.pdf

pdf

ParticularSpecification9071.pdf

pdf

Tender9071.pdf

pdf

Tendernotice_1 (1).pdf