Tender For Shifting Of Ht Lt Line And Decorative Pole Work From Chamunda Choraya To Varun Sagar At Varun Sagar Road , Ajmer.
Tender Value
3.26 Crore
Estimated cost
Bid Submission
22 Jul 2026
15 days left
EMD
6.52 Lakhs
Bank guarantee accepted
Document Fee
5000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ajmer → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Shifting Of Ht Lt Line And Decorative Pole Work From Chamunda Choraya To Varun Sagar At Varun Sagar Road , Ajmer.
BOQ
| Sl. No. | Item Description |
| 1 | SITC of 9000mm pole with single/double arm of circular mild steel pipe of two section (grade YST 210), Bottom section 139.7mm Dia x 3.6mm thick with 3SITC of 9000mm height pole 4arm with post top made of circular mild steel pipe of two section (grade YST 210), Bottom section 139.7mm Dia x 3.6mm thick with 3000mm Height & Top section 114.3mm Dia x 3.2mm thick with 4430mm Height. Decorative base made of Cast Iron (380mm Square x 1127mm Height) with door SITC of 9000mm pole with single/double arm of circular mild steel pipe of twosection (grade YST 210), Bottom section 139.7mm Dia x 3.6mm thick with 3SITC of 9000mm height pole 4arm with post top made of circular mild steel pipe of two section (grade YST 210), Bottom section 139.7mm Dia x 3.6mm thick with 3000mm Height & Top section 114.3mm Dia x 3.2mm thick with 4430mm Height.Decorative base made of Cast Iron (380mm Square x 1127mm Height) with door 432mm height x 102mm width. Decorative cast aluminium cone (230mm Dia x 150mm Height) coverd on the bottom & top section joint area. The four arm pelican orna bracket is a split constructed type, Bracket stem made of MS pipe 88.9mm Dia x 2.9mm thick, emerging from a forged ring upto a height 1420mm crowned at the top with post top luminiare. The artistically curved four arm made of MS Pipe 38.1mm x 2mm thick, spruced up with MS Scroll with gravity die cast aluminium leaf and MS floral embellishment, is firmly held to the stem by way of MS clamps and the arm bears cast iron knobs at one end and other end facilitates the fitment of pendant luminaire at 920mm on four side from the vertical axis of the bracket stem. Pole section welded by certified welders using high end MIG welding processes. PDC aluminium inner service door 348mm height x 110mm width shall be provided with the company logo embossed on the bottom of the door and safety rope. 9 mtr The control gear tray is prewired with 2.5 Sq.mm cable, 6A SP MCB and 32A Ramanuj stud type 4 way terminal block for loop-in / loop-out arrangement, 5A 2 Way terminal connector and provision for earthing. Any other internal cables and connections shall not be covered in the scope of supply. Mild steel mounting plate 300mm Square x 16mm thick Steel of grade E250 to IS 2062 : 2011. ADA Embosed on pole |
| 2 | SITC of 200W led pendant mounted compact street light. Type IV (Asymmetrical light distribution). Luminaire made of specially spun aluminum body of high corrosion resistance with a neck design for unique and better aesthetics and non corrosive stainless steel fasteners. Clear polycarbonate diffuser. The mounting arrangement nipple, coupling & Hex nut made of Stainless steel 304 suitable for mounting to internally threaded pipe of designation M30. Protection class IP65. Mechanical resistance IK08 (Polycarbonate diffuser). Available colour temperature 3000K / 4000K , Colour rendering index (CRI)>70. with expected service life of at least 50,000 operating hours. Prewired with LED driver and suitable for operating on 240V, 50Hz single phase ac supply. Driver efficiency >85%, Power factor >0.95, THD <10%, Surge protection 5KV. e. CE/ BIS Certified. Inhouse NABL accredited lab. The fixture shall be provided with Pure polyester powder coated Black & Gold finish as approved by department in-charge. |
| 3 | Note: Rates are including GST. |
| 4 | Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 5 | Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 6 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 7 | Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 8 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 9 | 3 core 185.0 Sq.mm |
| 10 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 11 | 11 KV End Termination Kit Indoor type |
| 12 | 3 core 120/150/185 Sq.mm |
| 13 | 11 KV End Termination Kit Outdoor type |
| 14 | 3 core 120/150/185 Sq.mm |
| 15 | 11 KV Straight Through Joint Kit |
| 16 | 3 core 120/150/185 Sq.mm |
| 17 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 18 | 50 mm |
| 19 | 110 mm |
| 20 | Supply and installation of spike of M.S. rod 20mm dia 3.0mtr. long for earthing of (tower/pole) drive into earth by mechanical means sturcture connection the spike with cross arm top hamper PCC pole, lattics tower to earth etc. complete as per technical specification of DISCOM. |
| 21 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 22 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 23 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 24 | 6 SWG G.I. ( Hot Dipped ) Wire |
| 25 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 26 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 27 | 100 mm dia. |
| 28 | 50 mm dia. |
| 29 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated stainless steel Outdoor enclosure of thickness of 2 mm and tank of stainless steel Outdoor enclosure of thickness 3mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for both Cable chamber and gas tank as per IEC 62271-200 and LBS to be rated for class E3 as per IEC 62271 - 103. Vacum Interrupter should be same as used during type test of RMU. Each feeder of RMU should have voltage presence indicator. and VCB feeder should consist of 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder, 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.Load break switch feeder shall have Fault Passage indicator, Right angle boots for all the feeder Modules, Remote trip, Emergency Stop, Cable cover interlocking, Trasnformer protection tapo card etc. All the type test certificates as per IEC and CEA from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) |
| 30 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 31 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 32 | Coupling Assembly to connect two different RMUs. |
| 33 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 34 | Supply and fixing of LT Distribution Kiosk confirming to IS:13947/1993/ IEC 60947 Pt.3 amended up-to-date and as per DISCOM specifications made of 2 mm thick powder coated CRCA sheet of 415 volts 3 phase 4 wire triple pole and neutral type, complete in all respect as required. Including Incoming Switch Disconnector Fuse unit, Aluminium Busbar with copper one piece U contacts base, brass studs and nuts, copper busbar for main and interconnection, MS Channel frame of 75 mm x 40 mm grouted with C.C. of M-10 grade to achieve the height of 1.5 feet above the road level suitable for required no. of outgoing. |
| 35 | 200 Amp. LT Distribution Kiosk for 63/100 KVA Transformer |
| 36 | Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth. |
| 37 | Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 38 | Excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 100 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically (Longest side is vertical to cable) along the cable , (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 39 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 40 | 185.0 Sq. mm |
| 41 | 3.5 core |
| 42 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 43 | 185.0 Sq.mm |
| 44 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 45 | 3.5 x 185.0 sq.mm |
| 46 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 47 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 48 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 49 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 50 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 51 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 52 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 53 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 54 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 55 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 56 | Electrolytic grade Aluminium bus bar 6010 grade |
| 57 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required. |
| 58 | 25mm x 25mm x 5mm |
| 59 | Labour charges for Dismantling the structure with pole mounted transformer of different capacity along with distribution boards and re- erecting the transformer on newly erected structure along with distribution boards and including testing and commissioning (as well as cabling connection complete as required) |
| 60 | Labour charges for dismantling of existing PCC/MS electrical Pole including MS channel, V cross arm, 11KV insulator, LT insulator, guard wires, stay wires, one span of ACSR conductors and other electric items, coming along and in the alignment of the road, then removal and re-rolling of the PCC /MS Pole as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge, clean the site good as per the requirement and dismantle material receipt duly signed by DISCOM Engineer submit the receipt to EIC as required. |
| 61 | Labour charges for dismantling of existing Lattice tower including MS channel, V cross arm, 11KV/33 KV insulator, guard wires, stud/stay wire, one span of ACSR conductor and other electric items coming along and in the alignment of the road, then removal and re-rolling of Lattice tower as well as other materials and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from DISCOM/ concering authority complete as required. |
| 62 | Labour charges for dismantling of existing street light electrical pole with street light fixture, underground cable, MS box and other electric items of the pole coming along and in the alignment of the road, then removal and re- rolling of MS/PCC pole of different sizes as well as other materials and handing over the same to DISCOM/UIT/MC store and as per the direction of Engineer Incharge and clean the site good as per the requirement and submit the receipt from concering authority complete as required. |
| 63 | Labour charges for dismantling of service line connection (weather proof cable/armoured cable) for single phase /three phase supply of industrial/domestic connections from existing PCC/MS pole and handing over the same to DISCOM store including transportation from site to store and stacking of dismantling material in store and provide temporary supply to domestic/industrial connections to the consumer where supply is disconnected and clean the site good as per the requirement and direction of Engineer Incharge complete as required. |
| 64 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 65 | 50.0 Sq. mm |
| 66 | 3.5 core |
| 67 | 16.0 Sq. mm |
| 68 | 4 core |
| 69 | Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles as per Drawing attach at Table P-05 with Following Procedure |
| 70 | A) Excavation of Pit for Foundation Size upto required depth from Ground level |
| 71 | B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. |
| 72 | C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness |
| 73 | D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. |
| 74 | E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal |
| 75 | F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. |
| 76 | G) Providing and Laying Reinforce cement Concrete of M-20 grade in Footing and Pedestal including Curing the foundation for minimum 7 days. |
| 77 | H) Providing and Fixing Nosing Angle 25 mm x 25 mm x 3mm with 2 no. of 100 mm long, 6 mm dia fastener |
| 78 | Pole Foundation for Octagonal pole from 10 Mtr. To 12 Mtr. |
| 79 | P & Fixing Powder coated CRCA sheet enclosures on existing Structure by means of nuts and bolts and making holes , Din rail etc. as required. |
| 80 | 2.0 mm thick |
| 81 | Providing & Fixing of Electromechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. |
| 82 | One day reserve (Electromechanical type ) |
| 83 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor confirming to IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. |
| 84 | 4 pole Power contactors with following AC 1 Rating |
| 85 | 160 Amp |
| 86 | Providing & Laying XLPE insulated & P.V.C. sheathed Un-Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing commissioning etc. as required of following size. |
| 87 | 4.0 Sq. mm |
| 88 | 2 core |
| 89 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 90 | Single pole MCB (With B / C curve tripping characteristics) |
| 91 | 50/63 A rating |
| 92 | Note: GST will be paid extra. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 02, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysJul 23, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender