Project Description
Tender for Repair / Maintenance Of Fire Fighting Pipelines, Hydrants, Valves, Pumps, Control Panels/ Cables At installation Hansa Under Ge (Nw) Vasco
BOQ
| Sl. No. | Item Description |
| 1 | Providing, laying, jointing, testing in replacement of 100 mm dia Cast Iron (CI) pipe of class as specified on prepared surface/available trench including alignment, lowering of pipes, jointing with spun yarn and lead/ rubber ring gasket as applicable, including all fittings, specials, bends, tees, sockets, collars, flanges, nuts, bolts and jointing materials complete. The item shall also include hydraulic testing of pipe line, rectification of minor leakages, painting/touch up of damaged portions and commissioning complete all as specified and directed by Engineer-in-Charge. |
| 2 | Supply, fixing and laying in replacement of MS pipes confirming to IS-1239 heavy grade including cutting, welding provn of fitings, flanges, elbows, tees, reducers with pipe supports and two coats of bituminous paint over a cost of primer (pipes to be used for pump suction and delivery, fire brigade inlets, sydrants ring main, wet riser sprinkler system and any other use as required at site including removing old all as specified and as directed:- |
| 3 | (a) 100mm dia |
| 4 | (b) 80mm dia |
| 5 | Supply, fixing and laying in replacement of GI pipe heavy duty including cutting, welding of fittings, flanges, elbows, tees, reducers with pipe supports and teo coats of bituminious paint over a cost of primer (pipes to be used for pump suction and delivery, fire brigade inlets, sydrants ring main, wet riser sprinkler system and any other use as required at site including removing old all as specified and as directed:- |
| 6 | (a) 100 mm dia |
| 7 | (b) 50 mm dia |
| 8 | (c) 40 mm dia |
| 9 | (d) 25 mm dia |
| 10 | Supply and fix in replacement of external (Yard) Hydrants comprising of:-(a) Stand post for Single outlet.(b) Single headed landing valve.(c) Shut off twin instantaneus type female connection with coupling outlet with 63mm gun landing valve, MS tee topping from underground main ring line, duck foot bend flanged, riser, cap chain and other accessories including removing old and all as required and specified |
| 11 | Supply and fix in replacement of hose rool of 20 mm fia and 30 meter conforming to IS 5132 |
| 12 | Supply and fix in replacment of 63 mm dia 15 meter long RRL hose conforming to IS 636 complete with male and female coupling including removing old and all as specified and as directed. |
| 13 | Supply and fix in replacement of gun metal pressure gauge (100 mm dia) of rating 0 to 21 Kg sqm gun metal isolating cock and connecting pipe including stop cock and all fittings complete all as specified and as directed. |
| 14 | Supply and fix following sizes of CI double flanged non return valve class - 1 conforming to IS : 5312 including removing old and all as specified and as directed. |
| 15 | (a) 150 mm dia |
| 16 | (b) 100 mm dia |
| 17 | (c) 80 mm dia |
| 18 | Supply and fix in replacement of gun metal gate valve conforming to IS 778 class - II all as specified and as directed of sizes :- |
| 19 | (a) 50 mm dia |
| 20 | (a) 25 mm dia |
| 21 | Suplying and fixing in replacement of pressure switch for aumatic operation of booster pump including necessary wiring with 2.5sqmm size copper conductor cable pvc insulated but unsheathed in and including flexible conduit all as required and specified. |
| 22 | Supplying and fixing testing and commissioning 100mm dia,butterfly valve/ gun metal draw out connection from under ground tank all as specified and directed. |
| 23 | Supply and fix in repair of 2 core 1.5 sqmm PVC insulated PVC sheathed copper cable all as specified and as directed. |
| 24 | Supply and fix in repair of Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB 1000 mtrs range all as specified and as directed. |
| 25 | Supply and fix in repair Fire Alarm Sounders / Sirens Electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB 1500 mtrs range all as specified and as directed. |
| 26 | Supply and fix in replacement of detectors Complying with and type certified to EN - 45 analogue Addressable type multi sensor heat and smoke detector combination type Photoelectric /Optical with base with self built intelligence as per IS: 11360 (To be provided below and above false ceiling) all as directed and specified. |
| 27 | Supply and fix in replacement of manual call point resettable type push button complete all as specified and as directed |
| 28 | Supply and fix addressable in replacement of electronic sounder cum strobe will all accessories and all as specified and as directed. |
| 29 | Material and labour for Servicing, testing and cleaning of smoke detectors, heat detectors, multi sensors and beam detectors including calibration and simulation testing complete all as directed. |
| 30 | Supplying and fixing in replacement of man fire control Panel 12 Zones addressable type with built in hooter, DC and battery charger, rectifier Zone care unit fire and fault indicator duly approved by TAC with battary backup unit with PA system. The main control panel shall consist of following:-(a) Cabinet main fabricated out of 14 SWG, MS Sheet, perspek front with Mottis board of glass epoxy, gold plated connectors terminal block withbatter unit. The cabinet shall be painted stoving dove grey.(b) Power supply unit transformer, rectifier, charger, control circuit with A-3 card, Mottis connector, relays for auto change over. Short circuit and over load protection and voltage regulator rated for 24 volts.(c) Control card A2 with A1, Ack, reset, buzzer, I/C control system, low battery indicator alarm and fault over tide facilities with heavy duty contacts.(d) Zonal cards with fault and alrm sensing I/C control circuits, testing facilities, Zone isolation and output relay each handling 4 Zones.(e) Exide battery 2x12 volts, 40AH. |
| 31 | Supply and fixing in replacement of repeater panel compatible with existing Addressable Fire Detection System (AFDS), complete with LCD/LED indications for Fire, Fault and System Status monitoring, suitable for remote annunciation and control of main fire alarm panel, housed in wall mounted CRCA enclosure including communication modules, power supply, standby battery, interconnections, programming and all accessories complete as directed. |
| 32 | Supply and fix in replacement of Beam Master detector with Transmitter and receiver with accessories and necessary connections all as specified and as directed |
| 33 | Material and labour in replacement of remote response indicator as per existing make and model complete all as specified and as directed. |
| 34 | Material and Labour for servicing of Fire pump Diesel Engine of capacity 80 to 90 HP of any make / model by carrying out the following maintenance as per manufacturers instructions including cleaning the engine, pump, completely by blowering and with cotton waste and testing on completion for entire satisfaction,complete all as specified and directed:-(a) Draining out engine oil from the sump by removing drain plug, cleaning the sump thoroughly and refilling the sump with new engine oil to required level (Note: Engine Oil will be measured and paid separately as 'Supply Only').(b) Supply and replace complete set of engine oil filters, fuel filters, Bypass filter, air cleaner element and water separator.(c) Draining out complete coolant water mixture from the radiator and re-filling the radiator with new coolant and water mixture with proportionate ratio.(d) Checking and Tightening all the fasteners of complete engine to the required torque, if required.(e) Cleaning of battery terminals.(f) Cleaning of radiator with air pressure. |
| 35 | Supply only air filter complete all as specified and as directed. |
| 36 | Supply only oil filter complete all as specified and as directed. |
| 37 | Supply only fuel filter complete all as specified and as directed. |
| 38 | Supply only engine oil complete all as specified and as directed. |
| 39 | Material and labour for Draining out of diesel from tank and storing in cleaned containers, cleaning the tank thoroughly by removing sediments settled at the bottom and refilling the drained out diesel duly filteredcompleted all as specified and as directed. |
| 40 | Supply only Battery 12 volts 150 AH heavy duty suitable for diesel fire engine after replacement of old unserviceable battery. |
| 41 | Supply and filling Coolant for Engine |
| 42 | Material and labour for servicing / repair of fire pump 40 HP by taking down pump and replacement of bearing, bush, check shaft alignment and correcting it including lathe work if required, icluding repair of impeller and casing by welding eroded parts and lathe work by smooth finish if required and replacement of nuts and bolts and testing on completion all as specified and as directed. |
| 43 | Material and labour for servicing / repair of jockey pump 15 HP by taking down pump and replacement of bearing, bush, check shaft alignment and correcting it including lathe work if required, icluding repair of impeller and casing by welding eroded parts and lathe work by smooth finish if required and replacement of nuts and bolts and testing on completion all as specified and as directed. |
| 44 | Supply and replacement of gland packing/mechanical seals, nuts, bolts, rubber gaskets and minor consumables required during maintenance of fire pumps complete all as directed. |
| 45 | Material and labour for rewinding of electric motor of motor service heavy duty includes dismantling, lowering down, transporting to work shop and back, erection, testing & commissioning etc. complete all as specified and directed by Engg-in-Charge. |
| 46 | Material and labour for preparation/scrapping and cleaning of existing surfaces of headers, delivery pipes, fire brigade inlets, hydrant ring main, wet riser and sprinkler system of firefighting sub station at 316 Sqn by removing rust, scales, old loose paint, dirt, oil and other foreign materials by manual/mechanical means, and applying one coat of red oxide primer on damaged/disturbed portions followed by two coats of approved quality bituminous paint complete to all exposed surfaces including scaffolding, surface preparation and finishing complete all as specified and directed by Engineer-in-Charge. |
| 47 | Material and labour for preparation/scrapping and cleaning of existing surfaces of fire fighting pipe lines, delivery pipes, fire brigade inlets, hydrant lines, wet riser and sprinkler system of Wardroom by removing rust, scales, old loose paint, dirt, oil and other foreign materials by manual/mechanical means, and applying one coat of red oxide primer on damaged/disturbed portions followed by two coats of approved quality bituminous paint complete to all exposed surfaces including scaffolding, surface preparation and finishing complete all as specified and directed by Engineer-in-Charge. |
| 48 | Cleaning and repainting of hydrant boxes/cabinets including numbering and marking complete all as specified and directed. |
| 49 | Cleaning of underground water storage sump of capacity 158000 Ltrs capacity having one compartment by following process as under :- (a) Dewatering the tank/sump with including all dirt dust and mud. (b) Desilting and removal of dirty water and sludge with wire brush inside wall and floor surfaces to remove impurities. (c) Cleaning of walls, ceiling and bottom of tank by high pressure water jet and bleaching powder. (d) Removing mud/impured material to a distance 10m away from sump. (e) writing capacity and date of cleaning (Cleaned on___) with white and black enameled paint. |
| 50 | Cleaning of underground water storage sump of capacity 20000-40000 Ltrs capacity having one compartment by following process as under :- (a) Dewatering the tank/sump with including all dirt dust and mud. (b) Desilting and removal of dirty water and sludge with wire brush inside wall and floor surfaces to remove impurities. (c) Cleaning of walls, ceiling and bottom of tank by high pressure water jet and bleaching powder. (d) Removing mud/impured material to a distance 10m away from sump. (e) writing capacity and date of cleaning (Cleaned on___) with white and black enameled paint. |
| 51 | Supply and fix industrial socket and plug of rating 63 Amp 3 poles, neutral and earth including MCB Module and MCB SPN/TPN of specific rating and breaking capacity in replacement all as specified and directed. |
| 52 | Supply and fix industrial socket and plug of rating 125 Amp 3 poles, neutral and earth including MCCB Module and MCCB FP of specific rating and breaking capacity in replacement all as specified and directed. |
| 53 | Material and labour for sub main wiring with four runs of single core 10 Sqmm FRLS Copper conductor PVC insulated unsheathed cable as per IS 694-1990 (third revision) drawn through & including non metallic rigid PVC casing caping / conduit medium grade of as required size (not less than 20 mm in width) with all accessories such as Tees, elbows, junction boxes etc, as required fixed concealed in wall along with Two run of 10 Sqmm single core FRLS insulated unsheathed copper conductor cable as continuous earth wire and connecting to existing main switch board/ distribution board and testing on completion etc complete all as directed. (Note :- Four runs of cable, One run of earth continuity conductor and two run of PVC casing caping/conduit shall be measred as one unit) |
| 54 | All as per item No 41 here in before, but two run of single core 4 sqmm and one run of 4 sqmm cables as earth continuity conductor but through all as directed. |
| 55 | All as per item No 41 here in before, but two run of single core 2.5 sqmm and one run of 2.5 sqmm cables as earth continuity conductor but in steel conduit all as directed. |
| 56 | Supply & Laying jointing, testing and commissioning LT XLPE cable, PVC insulated, PVC sheathed armoured LT 1100 volt grades heavy duty with aluminium stranded conductor through pipes, induct, on poles, in trenches etc including taking down complete of following sizes :- |
| 57 | (a) 185 Sqmm 3.5core |
| 58 | (b) 50 Sqmm, 3.5 core. |
| 59 | (c) 25 Sqmm, 3.5 core. |
| 60 | (d) 16 Sqmm, 4 core. |
| 61 | (e) 10 Sqmm, 4 core. |
| 62 | Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in hard/dence soil getting out and levelling of bottom surface to required level all as specified. |
| 63 | Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed |
| 64 | Removing excavated soil not exc 50 mtr ant depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed |
| 65 | Supply and filling in and speading clear sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. Note: Punned thickess i.e 18 cm shall be measured for paymeny purpose. |
| 66 | Supply and lay un-reinforced precast concrete cable covers, class LV , type- I with peak, size 250 mm x 150mm x 40 mm, all as specified and as directed. |
| 67 | Supply and lay Double walled corrugated pipe (DWC ), heavy duty 90 - 75 mm bore for cable protection as a guard pipe including required accessories etc. complete as specified and directed. |
| 68 | Repairs to existing fire point at E/M installations including excavation, PCC platform in 1:2:4 type B-1 (150mm thick), brick edging in CM 1:6, fabrication and fixing of MS angle iron frame (ISA 50x50x6mm), providing GI sheet roofing (22 gauge) with accessories, supply and fixing of 4 Nos. GI fire buckets (9 Ltr capacity, ISI marked) with MS hook brackets, one PVC water drum (200 Ltr capacity) with MS stand and tap, one MS sand bin of 200 kg capacity with hinged lid and locking arrangement, retro-reflective bilingual ‘FIRE POINT’ signage, filling of clean dry river sand, and painting all metal surfaces with one coat of red oxide primer and two coats of fire-resistant synthetic enamel red paint, all as specified and directed by Engineer-in-Charge. |
| 69 | Material and labour to carry out the Checking of the existing firefighting pipeline system for detection of any leakage, including hydrostatic pressure testing using approved methods and equipment. The work includes all necessary rectification such as replacement of defective pipeline sections, tightening of loose joints, resealing of fittings, and other associated minor works to make the firefighting system in operational condition, complete all as specified and directed by the Engineer-in-Charge.. Note : The pipe line and other items replaced shall be measured and paid separately under relevant items of BOQ. |
| 70 | Supply, installation, testing and commissioning LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequate size for MCBs, housed in a separate bus bar chamber and control wiring adequate size and length, outgoing MCCBs shall have extended bus bar links and Panel mounted on 50x50x5mm size MS angle iron frame duly painted including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation design subject to approval of GE as per site requirement. minimum clearance from ground level is 450mm including removing old unserviceable item complete all as specified and directed and comprising of following :- Note :- (i) contractor shall provide CPRI certification of the panel. (ii) All items incorporated in panel is ISI marked or IS specification . Make for MCCB :-Schneider/L&T/Legrand/Standard. Make for CT :- Nippen/AE , Make of LED Lamp:- Teknic, Make for amp meter and volt ,meter :- AE/Kaycee |
| 71 | (a) MCCB 200 Amps,FP, 36 KA, Adjustable type,415 volts,50Hz-01 No |
| 72 | (b) MCCB 160 Amps,FP,36 KA, Adjustable type,415 volts,50Hz - 2 Nos |
| 73 | (c) MCCB 100 Amps,FP,36 KA, Adjustable type, 415 volts,50Hz-02 Nos |
| 74 | (d) Digital voltmeter,with VSS -01 set,Digital, Ammeter,with CTs & ASS-01 set |
| 75 | (e) LED phase indication lamps RYB-01 set |
| 76 | (f) Aluminium bus bar of adequate rating -01 set |
| 77 | Supply, installation, testing and commissioning of LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequate size for MCBs, housed in a separate bus bar chamber and control wiring adequate size and length outgoing MCCBs shall have extended bus bar links and Panel mounted on 50x50x5mm size MS angle iron frame duly painted including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation design subject to approval of GE as per site requirement. The minimum depth, height, width of panel is 900x 900x450 mm respectively, minimum clearance from ground level is 450mm complete all as specified and directed and comprising of following :- Incoming : - (a) MCCB 100 Amps, FP, 36 KA, Adjustable type, 415 Volts, 50Hz-01 No.Outgoing : - (b) MCCB 63 Amps, FP, 36 KA, Adjustable type, 415 Volts, 50Hz-01 No.(c) MCCB 40 Amps, FP, 16 KA, Adjustable type, 415 Volts, 50Hz-03 Nos. (d) Digital Voltmeter with VSS- 01 Set, Digital Ammeter with CTs & ASS- 01 No. (e) LED phase indication lamps RYB - 01 Set.(f) Aluminium bus bar TPN 100 Amps rating - 01 Set.(g) 3 Phase street light timer - 01 No.Note :- (i) contractor shall provide CPRI certification of the panel. (ii) All items incorporated in panel shall be ISI marked or as per IS specification |
| 78 | Material and labour for Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick burried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to copper strip size 20 x 3 mm thick by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with funnel, wire mesh and protection to earthing strip shall be provided with GI pipe light grade 32 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust, bentonite powder 10 Kg and common salt mixed with 10% paddy field earth, PCC pit chamber in PCC 1:3:6 type C-1 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete all as specified and as directed.(Note:-Earth strip and protection pipe upto test point/equipment upto 7.5m is included in the rate quoted) |
| 79 | Material and labour for Earthing complete with GI earth plate, electrode,600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt, charcoal, bentonite powder 10 Kg, garden soil 10% and connected to GI earth strip 32x 6 mm thick dia by means of GI nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 40 mm dia upto 7.5 from the earth plate electrode & refilling of soil etc including necessary excavation & earth work in any strata and PCC chamber, including removing old earthing and all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 22, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysJul 24, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 14 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender