Housing Urban and Rular Development Local Bodies Closing in 7 days TDR #56250804

Tender For Supplying And Installation Of Inverter Ductable Ac In Library Building At Post Graduate Govt. College, Sector-11, Chandigarh. (Ibm Scheme No. G3/2025/25031). (Sitc Of Water Cooler Scroll Chilling Machines). (2 X 48 Tr)

Issued by Local Bodies · Chandigarh, Chandigarh
Tender Value
95.48 Lakhs
Estimated cost
Bid Submission
09 Jul 2026
7 days left
EMD
1.90 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Chandigarh → Chandigarh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Supplying And Installation Of Inverter Ductable Ac In Library Building At Post Graduate Govt. College, Sector-11, Chandigarh. (Ibm Scheme No. G3/2025/25031). (Sitc Of Water Cooler Scroll Chilling Machines). (2 X 48 Tr)

BOQ

Name of Work:- Supplying and Installation of inverter ductable AC in Library building at Post Graduate Govt. College, Sector-11, Chandigarh. (IBM Scheme no. G3/2025/25031). (SITC of Water Cooler Scroll Chilling Machines). (2 X 48 TR)
Sl. No. Item Description
1EQUIPMENT
2WATER COOLED SCROLL CHILLING MACHINES
3Supply, Installation, testing and commissioning of water cooled DX Chiller of 48.0 TR and unit shall consist with hermatic sealed scroll type compressors suitable for R-407c/R410-a refrigerant. Shell and tube water cooled Condenser, Insulated Shell and tube DX Evaporator, Micro Processor Controller as supplied by OEM as part of Chiller Package. The Unit mounted starter panel with double door construction shall be single Power point type complete with IP 55 Degree protection complete with Under/Over load, voltage, phase loss and phase reversal protection, Single Phase Preventers, communication card which can accept 4-20 mA or 2-10 V dc analog signal. Each Chiller package comprise of Min 2 compressors.
4The unit shall be complete with Discharge Service valves to isolate refrigeration circuits, vibration Isolators to isolate chiller from building structure, pressure gauges Electronic expansion valves, solenoid valves, anti-freeze thermostats, refrigerant piping with Insulation for suction line, accessories of Safety valve, angle valve, liquid line indicator, water flow switch, Relief valve, Isolating valves and including MS stand to install the chiller units fabricated out of suitable size of structural steel sections etc. all as per OEM. All accessories housed in a single chasis design.
5The noise level measured at a distance of 3 Mtr from the machine at anywhere in the plant room shall not exeed 80 dBA +-5%
6The chilled water type AC plant will be suitable for operationon 3 phase AC 50 Hz supply .
7The said Chiller package shall have stepped control of 100/50% of rated capacity since scroll comoressors works at full capacity only.
8The chiller shall be as per specifications. The water chilling machine shall meet the following design parameters
9The Chiller shall be 3 Star Rated and above as per BEE
10Chilled Water leaving Temp. : 44°F (6.7ºC)
11Chilled Water entering Temp. : 54°F(12.2ºC)
12Evaporator fouling factor :0.0005(FPS)
13Condenser Water Leaving Temp. : 97.5°F(36.40º C)
14Condenser Water Entering Temp. : 90.0°F(32.22º C)
15Fouling factor of condenser : 0.001(FPS)
16IKW/TR: 0.87 at 100% Load
17Cooling capacity : 48.0TR
18Water-cooled Scroll Chilling Machine as described above.
19The price should include all clearance
20charges, unloading and shipment till site
21Including Insurance Charges ,Unloading at site, placement of Chilling machine on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned chiller.
22(2 W + 0 S)
23Chiller 48TR (Actual Capacity) (2W+0S)
24Make Carrier/Trane/York/Voltas/Blue Star/ Daikin
25Note : Vendor Shall Supply all chiller of same make at site ,different brands are not allowed
26Hot water generator
27Supplying, installation, testing and commissioning of electrical HW generator equipped with sufficient number of electrical immersion heaters. The Hot Water Generator shall be of following capacity made of 8mm MS sheet and dish end made of 10mm MS having 16 gauge stainless steel lining with heaters arranged in banks and controlled by electronic Controller and Thermostats so that hot water is generated at 70 degree C with nominal variation including 75mm thick resin bonded fibre glass insulation of 24 kg/Cum density finished with 1.25mm thick aluminum sheet cladding including necessary electrical panel having suitable incoming and outgoing switchgears for heaters, automatic controls such as manual reset high temperature water outlet, step controller and recycling relay, 'ON' 'OFF' switch thermostats, pilot light, low water cutoff and other controls as per manufacturers recommendations including inlet and outlet connections for water as per specifications complete with pressure release valve, low level cut-out. Autovent sight-glass, foundation for Hot water generator as per specifications complete as required. All basic controls and terminals shall be located in an integral control cabinet factory wired and tested. The generator shall be suitable for 415 (+)/(-) 10% volts, 50 cycle, 3 phase power supply. The entire generator shall be factory assembled and tested at 350 PSI pressure.
28The price includes loading/ unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of HWG on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned HWG.
29100.0 KW Actual Capacity Hot water generator with Multiple Bank
30Make : Rapid Cool/KEPL/Emerald
31PUMP SETS
32PRIMARY VARIABLE SPEED PUMPING SYSTEM
33Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Ductile Iron.Impeller - 316 SS - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - 316 SS .Flush Line - Braided Stainless SteelMechanical Seal - Outside Balanced (the pump design shall meet the requirement of servicing / changing the mechanical seal without disturbing the pump shaft alignment) with external flushline. Motor Type - TEFC Squirrel Cage, Efficiency Class - I FIVE, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply, RPM as per OEM standard.
34VFD - Integrated motor mounted over Pump with IP- 55 protection. pump should operate through sensorless control or wireless DPT control.Pump Efficiency should be more than 75% Integrated fliter to meet EN61800-3 for RFI Control, Integrated DC link Reactor equivalent in performance to a 5% AC line reactor.All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless alogorithms,( Per pump,1 flow meter and 2 pressure gauges to be supplied and integrated with motor mounted VFD driven pump for the display of flow and head on VFD). Pump manufacturer to supply Ultrasonic flow meter and digital pressure gauges along with the pumps supplied or can display individual flow and head per pump on respective VFD using sensorless alogorithms
35The price includes all clearance charges, unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of PUMPs on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned pumps.
36The system shall be complete in all respects and suitable for following ratings andduty.
37Min 230 USGPM * 25 M Head or as per actual at site with Min Efficiency. 75% for Chilled water circuit (1Working + 1Standby)
38Make :Xylem,Grundfoss,Armstrong
39CONDENSOR WATER PUMPS (FIXED SPEED)
40Supply, installation, testing and commissioning of PN16 rated Vertical Inline Split Coupled ( Long coupled Type ) single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron.Impeller - Gunmetal Bronze - Statically and Dynamically BalancedCasing Gasket - Confined Non Asbestos FiberPump Shaft - SS 316/416.Flush Line - Braided Stainless SteelMechanical Seal - Outside Balanced (the pump design shall meet the requirement of servicing / changing the mechanical seal without disturbing the pump shaft alignment) Motor Type - TEFC Squirrel Cage, Efficiency Class - IE3, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply
41The price includes loading/ unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of PUMPs on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned pumps.
42384 USGPM * 18 M Head or as per actual at site with Min Efficiency. 75% (1Working + 1Standby)
43Make :Xylem,Grundfoss,Armstrong
44Cooling Tower ( CTI Certified)
45Supply, installation, testing and commissioning of CTI Aproved standard Rectangular type FRP Induced Draught Counter flow cooling tower with Double Cell , Motors suitable for VFD's with necessory accessories, Motors shall be IP65 and efficiency of IE3 , FRP water basin, PVC fillings with integral louvers and drift eliminators, hot water distribution by gravity complete with statically and dynamically balanced axial flow Fans, Direct driven fans with TEFC induction motor and temperature sensor suitable for operation on 415 + 10% volts, 50 Hz. AC supply, suction screen, make up with float valve and quick fill arrangement, overflow and drain connections, suitable inspection ladder, access arrangement for cooling tower interior, MS supporting structure, anti-vibration mountings ,cement concrete foundation, steel/ mesonary supporting structure complete as per specifications as required. Design shall be as below ,IP 55 rated Locable Isolator Switch with cooling tower along with all Isolators for CT Complete in all repsect .
46WBT : at 85º F
47WB Approach : 2.77º C Maximum
48Hot water IN : 97.5 ºF
49Hot water OUT : 90ºF
50Min Water Flow Rate : 384 USGPM
51The price should include all clearance charges, unloading and shipment till site Including Insurance Charges ,Unloading at site,RCC Foundation, placement of Cooling Tower on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Cooling Tower.
52Heat Rejection Capacity : 14,97,600 BTU/HR
53Make : Mihir,Paharpur,Bell, Delta
54AIR HANDLING UNITS
55CEILING SUSPENDED/FLOOR Mounted AHU'S (AHRI/Eurovent Certified)
56Double skin Low height & Low Noise Ceiling/FM mounted air handling units made of min 46+2mm thick Thermo-Accoustic panels ,Thermal Break Profile, extruded aluminum profiles with 0.6mm thick pre-coated GI Outer Sheet, 0.6mm thick Plain GI intermediate sheet inside layer with polyurethene foam (PUF) CFC Free insulation of density 40+-2 kg/m3 factory injected between them by injection moulding machine & 0.6mm Plain GI Perforated Inner sheet , filter section with G4 filter, coil section with 6 row chilled/Heating water coil, 22G SS304 drain pan with required thickness nitrile rubber insulation,Light, factory or at site mounted drain pump ,blower section with DIDW Aerofoil/ Backward/ Forward curved fans, Vibration isolators, Fan section access door, fire retardant canvass connection at fan outlet,Min IE-3 motor (TEFC type) and damper at the outlet of unit. All dampers shall be low leakage aluminum aerofoil design and suitable for manual / motorised operation.The selections for Ceiling mounted units shall be done considering the optimum Efficiency & Low Noise level with compact design of the units and AHRI/Eurovent Certified , complete as per specifications of following capacity:
57CFM TYPE SP CC /TR
584000 CS 40 6RD/12
595000 FM 40 6RD/15
60Make: Systemair,Edgtech,Flaktwood,Zeco
61WATER COOLED CASSETTE ACS
62Supply, installation, testing & commissioning of Water cooled Cassette Unit suitable for both heating/cooling with copper tube and aluminium finned cooling coil, low noise fan and motor with ON/OFF and 3 speed control and suitable for 1 phase, 230 + 6%V, 50 Hz electric supply, with cordless remote/corded control, fabric filter, drain pump, and decorative front grille. The Unit shall be complete with stainless steel duly insulated main and auxiliary drain pan. The unit shall be complete with electrical terminal strip, wiring in conduit upto thermostat box or any other advance technology. Unit shall have copper pipes for coil connection complete . The unit shall also have fresh air pocket provision. The front grill shall be 4 way type. The noise level at low speed shall be in the range of 38 to 42db & at high speed upto 45db. Noise levels are at a distance of 2M from the unit. (Note :Tonnage Variation allowed upto ±5%) : Note: Vendor should include the cost of of copper pipe connection upto 1m along with all accessories complete in all respect
632.5 Tr Four way
64EXPANSION TANK
65Supply, Installation ,Testing and commissioning of MS.Open expansion tank with minimum thicknessof 3.0mm as per the specifications.The Open vessel expansion tank shall be complete with all accessories so as to make it ready for installation and commissioning on site.The tank shall be insulated with the approved method of insulation, and shall be complete with water make-up connection and system .The expansion tank will be supplied,Non return Valve ,Float valve,Ball Valves and interconnecting piping etc.
662000 Ltr . Open Expansion Tank duly insulated and with all accessories.
67AIR SEPARATOR
68Supply,installation,testing and commissioning of Microbubble Air & Dirt Separator,with matching flanges, bolts, nuts & gasket, PN16 complete with flanged connection and as per the specifications as detailed earlier in the relevant section of specifications , and duly insulated with 50 mm thick TFF expanded polysterene and cladded with 26G aluminum sheet.
69125 mm Dia Air Separator , duly insulated.
70Make : Honeywell, Sant,Anergy
71Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
72SITC Water Flow Switches (Brass body) . Make : Anegy, RC
73SITC Auto Air Vent Valve 1/2\\" . Make : Anergy, RC
74PICV Valves
75Supply, Installation, Testing & Commissioning of Insulated Two- way ball type pressure independent control valve with flanged end ISO7005-2, flow capacity as desired, Min.PN16, equal percentage flow characteristic, body GGG50 ductile iron with stainless steel ball. Non spring return rotary type modulating actuator, torque as required, close-off min pressure 700 kPa, power supply 24 V AC/DC, control signal 2-10 V DC, feedback signal 2-10 V DC, IP54.
7640 mm dia
7732 mm dia
7815mm dia
79Make: Honeywell, Siemens,Danfoss,Belimo
80Thermostat
81SITC of Thermostat along with all accecorries and connecting wires between Thermostat and sesnsors & AHU Valves etc. complete in all respect
82Brass Ball Valves
83SITC of Brass Ball Valves of dia 25mm with Strainer
84SITC of Brass Ball Valves of dia 25mm without Strainer
85Make: RC, Anergy,Sant
86VALVES/CONTROLS - PN-16 without Insulation , Make :Advance,Honeywell,Zoloto
87Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.
88BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
89125 MM DIA
90Y- STRAINERS (PN-16)
91Providing and fixing in position the following Insulated Y-Strainers
92125mm dia
93POT- STRAINER(PN-16)
94Proiding and Fixing of Pot strainer with drain valve complete in all respect of following dia
95150 mm
96SITC Water Flow Switches (Brass body) complete with copper control wiring at chiller outlet of each machine
97AUTO AIR VENT
98Supply, installation ,testing and commissioning of Auto Air vents,at the specified locations in the chilled water piping , alongwith isolation ball valves, as per approved makes
99Auto air vent with isolating ball valves (15 mm dia)
100CONDENSATE DRAIN PIPE
101Providing and fixing and in position the following PVC pipes (Min. Thickness 3.0mm) for condensate drain duly insulated with minimum 6.0 mm 'O' Class Nirile rubber & duly secured with adhesive tape as per specification ,cut to required length and installed with all joints , including the necessary fittings. (For all the AHU/FCU units upto the main header in the shaft dor vertical risers
10265 mm dia
10350 mm dia
10440 mm dia
10532 mm dia
10625 mm dia
107Make : Diplast/Polypack/Astral/AKG
108Factory Fabricated Spril Oval/Round
109SITC of Factory fabricated Powder Coated Spiral Oval Duct Pre/site Insulated from Inside with 9.0mm thick Nitrile 'O' Class Insulation (payble separately) fabricated GSS Ducting complete with hanging arrangement of fasteners, GI threaded rods of sizes:. However The duct shall be fabricated at site for to make Collors/bends/plenums/suit pieces Only
110GI Sheet thickness - 24 Gauge
111GI Sheet thickness - 22 Gauge
112(Make: Ductofab,Zeco,Pioneer Airtech (Sheet Make: Tata, Sail,Jindal)
113Fresh Air/Exhaust Air Louvers
114Supply, Installation, Testing and Commissioning of extruded aluminium louvres with frame bird screeen 50 mm pre-filter with frame, mounting arrangement etc. as per specifications and drawings.
115Fresh Air/Exhaust Louvers
116Make:SystemAir/Caryaire/Ravistar/Pinaire
117MECHANICAL INSULATION
118DUCT LINE ACOUSTIC TREATMENT
119Supply, Installation, Testing and Commissioning of Acoustic lining inside ducts/plenum using open cell nitrile rubber foam having microban anti-microbial/ anti fungal product protection and of 160-180 kg / m³ density as per ASTM D3575, class 1 ratingn As per BS476,PART-7, cut to required sizes and to be stuck to the inside of duct surfaces with adhesive as approved by the manufacturer. (Rubber based solvent). as per specifications
12015mm thick sound board for Floor Mounted AHU's
12110mm thick sound board for CS AHU's
122Make :K Flex,Armacell,Aerofoam
123DUCT LINE THERMAL INSULATION(Inside Conditions)
124SITC of Physically / Chemically crosslinked polyethylene foam, with factory reinforced alupet foil facing, ANTI MICROBIAL/ANTI FUNGAL,HFC & CFC free , Negligible VOC level with Class O fire properties,with very low fire propagation of < 5.5 and passing E-84 at < 25/50, as per technical specification, the density of the foam should be not less than 25-30kg/m3 and the maximum thermal conductivity K should be 0.032W/mK@ 23 Deg C , the permeability resistance factor u shouldn't be less than 14000. The product shall have temperature range of –20oC to 115oC
1259mm thick
126Make :K Flex,Armacell,A Flex ,Aerolam
127ASSOCIATED ELECTRICAL WORKS
128Main Electrical Panel
129Main Electrical Panel (CPRI Approved manufacturer at leat 70 K)
130Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of following LT panels fabricated out of 14 guage CRCA sheet steel in cubical formationwith reinforecment of suitable size angle iron and channel T iron flats. All steel material used in the construction of panels shall be powder coated. A solid busbar shall be provided at the bottom/Top of the panel with two connecting eyes for termination. The boards shall be suitable for 415 volts, 50 Hz, 3 phase , 4 wire supply system. All the hardware used in the fabrication of the panel shall be galvanized with zinc passivation. The panel shall be compartmentalized to accommodate one feeder in each compartment. A vertcal cable alley of suitable width shall be provided to serve on or two vertical feeder sections. Also the opening between the busbar chamber and the feeder section shall be shrouded with bakelite / hylam sheet with min.3 mm thickness., The panel manufacturer shall have min 70 KA CPRI Certification
131The panel drawing shall be approved before taking up the fabrication and Shall have compitable BMS for future requirment.
132Main A.C. Panel
133Incomer
134INCOMING SUPPLY : MCCB 500-630 Amps 65 KA 4 PoleMicro processor based Adjustable type with Rotary Mechanism & all Protections along with spreader links,etc : 1 No.
135Multi Fuction VAF/VIF Meter (96mmX96mm Size) ,Indication Lamps LED Type RYB, Control MCB SP for Control (3 Nos),CT's 600/5 (3 Nos) and Control Terminal (8.0 Nos.) etc.
136Outgoing
1372 No. 125-160 Amps TP+NL MCCB with adujustable release 50 KA with ROM & Spreader links S/c, O/L & other protections outgoing for chillers.
1381 Nos. 200-250 Amps TP+NL MCCB with adustable release 50 KA with ROM & Spreader links S/c, O/L & other protections for 100 KW Hot water generator (interlocking electrically done to operate either chillers or HWG at a time)
1392 Nos. 0-63 Amps MCCB 25KA TP+NL with ROM & Links outgoing for Primary chiller water pumps (2 Working & 0 Standby)
1402 Nos. 0-63 Amps MCCB 25KA TP+NL with ROM & Links outgoing for condenser water pumps with upto 15 KW Star Delta starter (2 Working & 0 Standby)
1412 No. 0-63 Amps 25 KA MCCB with ROM & Links outgoing for Cooling Tower motor (1 DOL starters on each cooling tower of upto 7.5 KW each with incomer MCB TP seprate for each starter)
1422 Nos. 63-100 Amps 36 KA MCCB TP+NL outgoing with ROM & Links
143All starter shall have following accessories :
1441 No. overload relay
1451 No. Ammeter with CTs.
1461 No. single phase preventer
1472 Nos. ON/OFF indicating lights
1482 Nos. ON/OFF push buttons
149Hardware (PVC Channels/MCB Channels/Fibre- Glass/Gaskits/Sleeves/nuts/Bolts/washers/cooling fans/etc)
150Complete Wiring inclusive of thimbles,etc
151Unloading at site, RCC foundation ,placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.
152Sub Panel for AHU Motors up to 5.5 KW
153SITC of Wall mounted sub panel boards for AHUs, Blower with switch, starters, lamps inter connections, current operated single phase preventer, A/M switch etc. as per specifications and drawings and as required.
1541 No. incoming upto 32Amps 4 pole TP+NL MCB with Digital Mutli function Meter Class 1.0 with CT of suitable rating
155RYB Indicators
1562 Nos. Push Buttons On/Off
1571No. single phase preventor
1581 nos. DOL starter with Power contactor and MPCB as incomer of the starter with SPP with Digital Ampere Meter Class 1.0 with CT of suitable rating
1591 No MCB DP
160Panel Make : Adlec/Siemens/Tricolite/Unitech Power System/Vrindavan Electricals
161Sub Distribution Panels for AHU's
162SITC of panel board made of 1.6mm for non load bearing /2.0 mm thick steel sheet for non load bearing sections duly powder coated complete with Metering, indicating lights, CTS contactors, A/M Switch for remote controls operation complete as per specifications and drawings and as required.The panel manufacturer shall have min 70 KA CPRI Certification
163Incomer
1641 Nos. 100-125 Amps 36 KA MCCB TP+NL with ROM & Links
1651 No. 400 Amps aluminium conductor bus bar duly sleeved
1661 no. Multifunction meter with CTs as per requirment
1673 Nos. phase indicating lamps
168Outgoing
1697 Nos MCB suitable for 1.1 to 3.7 KW or suitable DOL Starter for AHU having contactors, LED indicators for on/off , O/L Relay, SPP, etc. as per coordination chart
1701 Nos MCB suitable for 5.5 to 7.5 KW or suitable DOL Starter for AHU having contactors, LED indicators for on/off , O/L Relay, SPP, etc. as per coordination chart
1711 nos MCB TPN 32 Amps 'C\\" Curve Spare and complete Wiring inclusive of thimbles,etc
172Hardware ( PVC Cahnnels/MCB Channels/Fibre- Glass Gaskets/Sleevs/nuts/bolt/washers/cooling fans etc Including complete wiring,thimbles etc.
173Unloading at site, placement of Panel on the foundation, co-ordination during execution, rendering necessary guidance for execution, supervision, testing, commissioning and startup of above mentioned Panel.The panel drawing shall be approved before taking up the fabrication from EIC
174Panel Make : Adlec/Siemens/Tricolite/Unitech Power System/Vrindavan Electricals
175CABLING (POWER
176Power Cabling and Earthing
177Supply, installation, testing & commisioning of Aluminum/CU conductor cables PVC sheathed, armoured cables of 1.1 KV grade with termination glands and GI earthing, identification tags, clamps and saddles etc.
1783.5Cx300 Sqmm Al
1793.5Cx240 Sqmm Al
1803.5Cx150 Sqmm Al
1813.5C x70 Sqmm Al
1824C x35 Sqmm Al
1834.0Cx16 SqmmAl
1844.0Cx10 Sqmm Al
1854.0Cx 06 Sqmm Al
1864.0Cx04 Sqmm CU
1874.0Cx2.5 Sqmm CU
1882Cx04 Sqmm (Cu Conductor flexible)
189Make : Havell's,Ecko,Finolex,Polycab
190Control Cabling
191Supply, installation, testing & commisioning of Copper conductor , PVC insulated, PVC sheathed armoured cable of 1.1 KV grade (Which is Interconnecting wiring for the fire alarm system with the AHU and the smoke dampers and AHU to Control Consol Panel
1923C x 1 Sqmm
1932C x 1 Sqmm
194Make : Havell's,Ecko,Finolex,Polycab
195Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with twonumbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required.
196450mm(W) x50 mm(D) and 2.0 mm Thickness
197300 mm width X 50 mm depth X 1.6 mm thickness
198450 mm width X 50 mm depth X 2.0 mm thickness
199Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenientsections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required.
200450mm(W) x50 mm(D) and 2.0 mm Thickness
201300mm(W) x 50 mm(D) and 1.5 mm Thickness
20250mm(W) x 50 mm.(H) and 1.5 mm Thickness
203Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
204Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required
205Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
206Providing and fixing 6 SWG dia G.I. wire on surface or in recessfor loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required.
207Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required
208INSULATED CHILLED WATER PIPING (expandedpolystrene insulation)
209Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping plumbing inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.),cut to required length, and installed with welded joints (USE RECTIFIER AS SPECIFIED), duly insulated with fire retardant quality expanded polystrene moulded pipe section of density 20 kg/cu.m after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type3, grade 1 roofing feltstrip(as per IS:1322 as amended up to date) at joints repairing of damage to building etc. as per specifications and as required complete in all respect.
210Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. (Insulation Make : Beardsell, Lloyed)
211125 MM Pipe DIA with 50 mm Thick Insulation
212100 MM Pipe DIA with 50 mm Thick Insulation
21380 MM Pipe DIA with 50 mm Thick Insulation
21465 MM Pipe DIA with 50 mm Thick Insulation
21550 MM Pipe DIA with 50 mm Thick Insulation
21640 MM Pipe DIA with 50 mm Thick Insulation
21732 MM Pipe DIA with 50 mm Thick Insulation
21825 MM Pipe DIA with 50 mm Thick Insulation
219Pipe Make : Tata, Hisar Jindel
220SITC of Insulated VALVES/CONTROLS - PN-16 including cost of MS Flanges as per the Table(Make: Advance, Sant, Zoloto)
221Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.
222BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating for chilled water /hot water circulation as specified.
223125 MM DIA
224100 MM DIA
22580 MM DIA
22665 MM DIA
22750 MM DIA
228BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.
229100 MM DIA
23080 MM DIA
23165 MM DIA
23250 MM DIA
233NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.
234100 MM DIA
235Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.
23680 MM DIA
23750 MM DIA
238Providing & Fixing in position the industrial type pressur gauges with gun metal/brass valves complete as required
239Make : Guru,Fiebig
240Providing & Fixing in position the mercury in glass industrial type thermometers
241Make : Guru,Fiebig
242CONDENSOR WATER PIPING
243Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.
244Note:-i)The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. ii) For under ground pipe : The pipe will be covered by applying 2-4mm thick Tarfelt sheet with required Adhesive ,Accessories etc
245150 MM DIA
246125 MM DIA
247Make : Tata, Jindel Hisar
248VALVES/CONTROLS - PN-16 without Insulation , Make :Advance, Sant,Zoloto
249Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.
250BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet& O - ring & PN 16 pressure rating as specified.
251150 MM DIA
252125 MM DIA
253NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation as specified.
254125 MM DIA
255Ducting
256Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, Splitler dampers,vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required and shall also confirm to the BIS specifications.
257Thickness 0.63 mm sheet
258Thickness 0.80 mm sheet
259Thickness 1.00 mm sheet
260Sheet Make: Tata, Sail,Jindal
261Grilles/Diffusers/Dampers
262Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications
263Supplying & fixing of powder coated extruded aluminium Supply Air Grills(curved/Flat) with aluminium volume control dampers as per specifications
264Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required
265Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
266Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
267Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
268Fire damper
269Actuator Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56250804
AUTHORITY Local Bodies
TENDER VALUE 95.48 Lakhs
LAST DATE 09-07-2026
Authority
Authority Name Chandigarh Administration Engineering Department
Work Description Tender for Supplying And Installation Of Inverter Ductable Ac In Library Building At Post Graduate Govt. College, Sector-11, Chandigarh. (Ibm Scheme No. G3/2025/25031). (Sitc Of Water Cooler Scroll Chilling Machines). (2 X 48 Tr)
Basic Detail
Tender No PH7/2026/08
Bidding Type Tender
Location
City Chandigarh
State Chandigarh
Key Dates
Publish Date 01 Jul 2026
Submission Date 09 Jul 2026
Open Date 09 Jul 2026
Finance
Tender Value 95.48 Lakhs
Tender Fee Ref. Documents
EMD 1.90 Lakhs
Exemption Not Available
Document List
BOQ_114811.xls
e7624cad-93f4-47a8-b76d-693535ace6ab.html
Tendernotice_1 (11).pdf
Tendernotice_2 (4).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 01, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 09, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 7 days