Tender For (1)Installation Of 25 Kva Substation Along With Ht/Lt For Bsnl 4G Usof Site At Kachwari Khansahib.(2)Installation Of 25 Kva Substation Along With Ht/Lt For Bsnl 4G Usof Site At Sugen Yarinar.(3)Installation Of 25 Kva Substation Along With
Tender Overview
Project Description
Tender for (1)Installation Of 25 Kva Substation Along With Ht/Lt For Bsnl 4G Usof Site At Kachwari Khansahib.(2)Installation Of 25 Kva Substation Along With Ht/Lt For Bsnl 4G Usof Site At Sugen Yarinar.(3)Installation Of 25 Kva Substation Along With Ht/Lt For Bsnl 4G Usof Site At Ompora.(4).Installation Of Ht Underground Cable For Bsnl Ufo Site At Doodhpathri Under The Jurisdiction Of Electric Division Budgam Kpdcl.Note:-1.All Participating Bidders Have To Furnish Tender Fee And Earnest Money Pledged To Executive Engineer,Kpdcl,Ed-Budgam,Kpdcl.No Bidder Shall Be Exempted From Depositing Of Tender Fee And Earnest Money Even If Agency/Bidder Is Msme. 2.Bidder Shall Use The Select Button To Quote His Bid In Excess +% Or Less -%.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commisioning of 11/0.433kV, 25 kVA 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable. No |
| 2 | Supply, installation, testing and commisioning of 9 mtr (410 SP-33) long Steel Tubular Poles complete with base plate(350x350x5mm), top cap, Earthing Channel(75x40x6mm) including digging of pit positioning etc, complete in all respect as per Standards. |
| 3 | Supply, laying, stringing, tensioning, binding of 30 Sqmm ACSR Conductor complete in all respects as per standards. |
| 4 | Supply,Carraige upto site and fixing of GI V cross-arm with top Bracket including clamp duly fabricated as per site requirement including clamps(50x8 mm), GI Nuts & Bolts,washers etc complete in all respects as per standards. |
| 5 | Supply,Carraige upto site, fixing and installation of GI Channels of different sizes including clamps and braces. |
| 6 | Supply,Carraige upto site,Installation,testing and Commissioning of 11kV Polymeric composite Pin Insulators 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm complete in all respects as per standards. |
| 7 | Supply,Carraige upto site,Installation,testing and Commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm complete in all respects as per standards. |
| 8 | Supply, Carraige upto site, installation, testing and Commissioning of Gapless Surge Arrestor 9 kV, 10 kA, LA with polymer housing, Stn. Type complete in all respects as per standards. |
| 9 | Supply, Carraige upto site, installation, testing and Commissioning of 11 kV G.O AB Switch 3-phase, 3 pole 200-Amp, vertical Type with fittings complete in all respects as per standards. |
| 10 | Supply, Carraige upto site, installation, testing and Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A complete in all respects as per standards. |
| 11 | Supply, Carraige upto site, laying, stringing, tensioning, binding of 35mm² (1Ckt )1.1kV Grade, XLPE Insulated Stranded Conductor FRLS type cable complete in all respects as per standards. |
| 12 | Supply,Carraige upto site, fixing of Aluminium Thimbles of size 35 Sqmm. |
| 13 | Supply,Carraige upto site, fixing and Commissioning of Aluminium Solderless Clamps of size 35 Sqmm. |
| 14 | Supply, Carraige upto site, installation, testing and Commissioning of LT Distribution Box for 25 kVA DTR with 40 Amp MCCB 3P 16 kA for incomer & 25 Amp MCCB 3P 16 kA/10 kA 1 No each (=2No.) for Outgoing Circuits complete in all respects as per standards. |
| 15 | Earthing of substation-Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 25 mmx3 mm, for connection of transformer body,G.O set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover complete in all respects as per standards. |
| 16 | Supply, Carraige upto site,laying ,stringing,tensioning , binding of 1.1 KV grade, 4-core 16 Sqmm armoured FRLS Type cable of sizes |
| 17 | Cement bottoming 1:2:4 mix as per Standards 0.5cum/0.45 cum pole comlete in all respects. |
| 18 | Earthing of steel tubular poles complete by GI pipe 40mm or GI rod 20mm 3.0 mtr long through GI strip 25x3 as per standards. |
| 19 | Painting of Poles with one coat of Red Oxide and two coats of alimunium paint to give uniform shine. |
| 20 | Supply and fixing of GI barbed wire Anti climbind Device with clamps complete in all respects as per Standards |
| 21 | Supply and fixing of danger plates with clamps complete in all respects as per Standards |
| 22 | Supply, Carraige upto site, laying, binding of 11 KV grade, 3-core XLPE,50 Sqmm armoured, FRLS cable of sizes complete in all respects as per Standards |
| 23 | Supply,Carraige upto site,Installation,testing and Commissioning of 11 KV grade 3-core 50 sqmm cable jointing kits of sizes |
| 24 | Route Marker |
| 25 | Warning Tap |
| 26 | Supply,Carraige upto site,Installation,testing and Commissioning of Heat shrinkable 11 KV grade 3-core 50 Sqmm cable termination kit (indoor / outdoor type) of sizes |
| 27 | Excavation in any type of soil including hard laterite soil |
| 28 | Back filling of available excavated earth |
| 29 | Sand for cushioning of HT underground cables |
| 30 | Mechanical transport 30kms of sand |
| 31 | RCC protective cover of size 300 mm (width) x 300mm (Length) x 60 mm (Thickness) for underground cables . |
| 32 | Brick Masonary Chamber (900x900x1050)mm with RCC top slab, Cast Iron cover in CI Frame (38Kg) after 500 mtrs |
| 33 | Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip (25x3 )mm |
| 34 | Supply of Safety Helmet as per Standard |
| 35 | Supply of Bamboo ladder 18ft long. |
| 36 | Supply and fixing of 3 Phase energy meter 20-80 Amp,DLMS Compliantof accuracy class 1.0 complete in all respects as per Standards Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 16 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender