Defence Statutory Bodies & Commissions/Committees Closing in 11 days TDR #56240984

Tender For Repair / Replacement Of Lt Ug Cables And O/H Lines, Mccbs, Lt Panel Boards And Misc E/M Works At Chh Sambhajinagar Mil Station Under Ge(S) Ahilyanagar

Issued by Statutory Bodies & Commissions/Committees · Aurangabad, Maharashtra
Tender Value
44 Lakhs
Estimated cost
Bid Submission
21 Jul 2026
11 days left
EMD
88000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Aurangabad → Maharashtra
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair / Replacement Of Lt Ug Cables And O/H Lines, Mccbs, Lt Panel Boards And Misc E/M Works At Chh Sambhajinagar Mil Station Under Ge(S) Ahilyanagar

BOQ

Name of Work:- REPAIR / REPLACEMENT OF LT UG CABLES and O/H LINES, MCCBs, LT PANEL BOARDS AND MISC E/M WORKS AT CHH SAMBHAJINAGAR MIL STATION UNDER GE(S) AHILYANAGAR
Sl. No. Item Description
1Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains or laying of pipe/cables or for shafts, wells cesspits, man holes etc (not exceeding 1.5 m in width or 10 sqm on plan) and not exceeding 1.50m in depth in any kind of soil, including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m all as specified and directed.
2Returning, filling in excavated material (soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm all as specified and as directed.
3Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 50mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed.
4Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 63mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed.
5Supply and laying Double Walled Corrugated (DWC) HDPE pipe of nominal bore 110mm including 90 degree bends with coupler and rubber ring, conforming to IS :16205 Part 24 Type 450N, laid in trenches for cable protection complete, all as specified and as directed.
6Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 120 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
7Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 95 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
8Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 70 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
9Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 50 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
10Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 35 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
11Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 25 Sqmm, 3.5 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
12Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 16 Sqmm, 4 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
13Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 10 Sqmm, 4 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
14Supply and laying in replacement in trenches or fixing or passing through pipe, 1100 Volts grade, armoured, heavy duty LT UG cable of size 10 Sqmm, 2 core with XLPE insulated stranded aluminium conductor including cable gland, lugs, testing and commissioning complete all as specified and as directed.
15M&L, in replacement, heat shrinkable straight through cable joint kit suitable for 10 to 16 Sqmm 4 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed.
16M&L, in replacement, heat shrinkable straight through cable joint kit suitable for 25 to 50 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed.
17M&L, in replacement, heat shrinkable straight through cable joint kit suitable for 70 to 120 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed.
18M&L, in replacement, heat shrinkable straight through cable joint kit suitable for 150 to 185 Sqmm 3.5 core LT XLPE cable 1100 Volts grade complete with jointing material and accessories and testing including necessary excavation / earth work complete all as specified and as directed.
19S&F in replacement 80 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed.
20S&F in replacement 50 mm bore galvanised steel tubing, light grade, ISI marked, for protection of under ground cable on pole/wall/under road including clamps where reqd and taking out old unserviceable pipe complete all as specified and as directed.
21M&L for cutting existing road/hard standing surfaces to a depth 60 cm and 50 cm width and getting out for laying underground pipe including returning filling in, watering well ramming in layers not exceeding 25cm in soil and filling the trench top with 15cm thick PCC 1:2:4, type B1 (using 20 mm graded stone aggregate) and making good the disturbed surface complete all as specified and as directed.
22Dismantling of ACSR or AAC conductors of any size and any description from any height/ poles or any location complete all as specified and as directed by Engr in Charge.
23Dismantling of Unserviceable LT insulators Pin/ shackle/ Disc & loop type from existing OH lines complete all as specified and directed by Engr in Charge.
24Dismantling of unserviceable steel structure such as cross arms, bracings, supports, clamps etc from LT pole of any type/shape complete all as specified and directed.
25Dismantling of GI wire cradles,earth wire guarding , fabricated with galvanised steel wire 4mm dia hexagonal / rectangular shape of any type complete all as specified and as directed .
26Dismantling of LT stay Assembly all as specified and directed.
27Supply and fixing Cable route indicator made out cast iron and embedded LT Cable on the plate of size 80 mm dia 5 mm thick with angle iron support of 1.5m long including grouting lug of suitable size in PCC (1:3:6, C2) foundation of suitable size complete all as directed and directed by Engineer in Charge.
28M&L for taking out old burnt cables & thimbles from loop and fixing to LT Panel completely after making good condition with suitable lugs upto cable 16 to 120 sqmm fixing to MCCB's including necessary excavation work & minor spare parts i.e thimbles, nut, bolts ,para tape etc complete all as specified and directed.
29M&L for denting, welding/fixing of hinge to panel door of various capacity including painting of doors after welding, with Smoke grey paint & cleaning of exposed surface with brush, empry paper complete all as specified and directed by Engineer-in-Charge
30S&F 1100 volts grade heavy duty cable, 4 sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection twin core cable flat including taking down old unserviceable cable for the following sizes :-
31S&F 1100 volts grade heavy duty cable, 6 sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connection twin core cable flat including taking down old unserviceable cable for the following sizes :-
32Supply and fixing Danger notice Plate of 1.6 mm thick mild steel sheet , vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS Clamps, bolts and nuts of approved size, for LT ,20x15 CM size and directed by Engr in Charge.
33S&F in replacement FRP Junction box, light weight low corrosive suitable for pole mounting including MCB SP 6/10 amps , Box size not less than 250x200x100 mm including necessary connection for loop in and loop out cable connector and suitable size for cable glands complete all as specified and directed by Engr in Charge.
34S & F in replacement PVC insulated and over all PVC sheathed, stranded copper conductor wire 1.5 sqmm x 3 core ISI marked.complete from light fitting to pole junction box complete all as specified.
35S&F in replacement Voltmeter three phase class 0.5 with digital display including taking down old UNSV Voltmeter complete all as specified and directed by Engr in Charge.
36S&F in replacement ammeter three phase class 0.5 with digital display including taking down old UNSV ammeter complete all as specified and directed by Engr in Charge.
37S&F in replacement LED type indicator lamp (RYB) including taking down old UNSV indicator lamp set of three complete all as specified and directed by Engr in Charge.
38S&F in rep, MCCB 4 Pole , 63 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
39S&F in replacement , MCCB 4 Pole , 100 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
40S&F in replacement, MCCB 4 Pole , 125 Amps , 16 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
41S&F in replacement , MCCB 4 Pole , 160 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
42S&F in replacement , MCCB 4 Pole , 200 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
43S&F in replacement , MCCB 4 Pole , 250 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
44S&F in replacement , MCCB 4 Pole , 350 Amps , 36 KA current carring capacity with adjustable thermal magnetic release all as specified and as directed by Engr in Charge.
45S&F in replacement post top lantern LED type 25 watt 230 volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete including suitable size of GI Pipe as per lamp size including connection and testing complete all as specified and directed by Engr in Charge.Make : Havells Cat No. RUBYNXTPT25WLED730PSYMTOPC or equivalent model of makes specified.
46S&F in replacement garden light of Bamboo type -IP 65 of New generation, energy saving, environmental friendly, long life aesthetically designed aluminium landscape luminaire for diffused lighting with high power LED as light source with PCC Base of size 1 feet x 1 feet for fixing of lights with proper nut & bolts including elect connection wire complete all as specified and directed by Engr in Charge. Make : HAVELLS Cat No. TURINBLS10WLED857PSYMTOPC or equivalent model of makes specified.
47S&F in replacement LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed.Make : Havells Cat No ENDURASUNDOWNNXTSL90WLEDCWPASYBOPC or equivalent model of makes specified.
48S&F in replacement LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed.Make : Havells Cat No ENDURASUNDOWNNXTSL60WLEDCWPASYBOPC or equivalent model of makes specified.
49S&F in replacement LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete including PVC copper wire 1.5 sqmm of suitable length for connection of street light from Overhead conductor /junction box complete all as specified and directed.Make : Havells Cat No ENDURASUNDOWNNXTSL120WLEDCWPASYBOPC or equivalent model of makes specified.
50S&F in replacement bracket for street light,made out of GI Pipe medium grade of suitable size (40 mm dia and 1.2 mtr long) bent to shape ,fixed with and including necessary heavy duty clamps of suitable size including painting the clamps with two coats of synthetic enamel paint over a coat of primer all as specified and as directed.
51Supply and errection of steel tubular swaged poles complete with cast iron base plate , finial tapper plug , bolts,nuts & screws as specified type 410 SP - 31, 9.00 Mtr long including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with yellow and black paint alternately on external surface above PCC benching and painting with bituminous paint internally including writing the pole number in white letters on black background complete and externally for portion embedded in PCC, complete all as specified and directed. Note :- Excavation & earthwork and PCC in foundation of poles,coping etc shall be measured and paid under respective items
52M&L for PCC 1:4:8 Type D2 using 40mm graded aggregate for base foundation complete all as specified and directed by Engr in Charge.
53M&L for PCC (1:3:6) type C-1 with 20 mm gradded stone aggregate for coping of poles Pedestal including necessary form work complete all as specified and directed by Engr in Charge.
54Supply, install in replacement and testing out door wheather proof bus bar chamber of size 100 cm x 60cm x 30cm made out of 3.15mm CRCA MS sheet having one side openable hinged door shuter with locking arrangement/provn of two nos 80cm long 40x40x6mm anlge iron legs welded and 04 nos Aluminium bus bar of 200Amp rating including provn of one MCCB TPN 100 Amp 25 KA for controlling Electric supply complete erected on ground with necessary PCC 1:3:6 type C2 foundation complete bus bar chamber painted with two coats of approved enamel paints over one coat of primer including making cable connection with necessary gland , lugs/thimbles complete all as specified and as directed.
55Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated TPN Aluminium bus bars 1000 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board).
56Incoming: (a) MCCB 630 amps, 4 pole, 50 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply - 01 set (c) Multifunctional Digital square type intelligent panel meter to measure voltage, current, frequency and Power factor - 01Set. (d) Neon indicating lamps (R, Y & B) - 01 Set (03 Nos) Outgoing: (a) MCCB 400 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos. (b) MCCB 200 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 02 Nos.(c) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos(d) Astronomical timer switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos
57Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated TPN Aluminium bus bars 1000 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board).
58Incoming: (a) MCCB 630 amps, 4 pole, 50 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 1000 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply - 01 set (c) Multifunctional Digital square type intelligent panel meter to measure voltage, current, frequency and Power factor - 01Set. (d) Neon indicating lamps (R, Y & B) - 01 Set (03 Nos)Outgoing: (a) MCCB 400 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos. (b) MCCB 315 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos.(c) MCCB 250 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos(c) MCCB 200 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 02 Nos(c) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos(d) Astronomical timer switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos
59Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated TPN Aluminium bus bars 600 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board).
60Incoming: (a) MCCB 400 amps, 4 pole, 50 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply - 01 set (c) Multifunctional Digital square type intelligent panel meter to measure voltage, current, frequency and Power factor - 01Set. (d) Neon indicating lamps (R, Y & B) - 01 Set (03 Nos) Outgoing: (a) MCCB 200 amps, 4 pole, 36 KA with adjustable thermal release, 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 04 Nos.(c) Astronomical timer switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos
61Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated TPN Aluminium bus bars 600 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board).
62Incoming: (a) MCCB 400 amps, 4 pole, 50 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply - 01 set (c) Multifunctional Digital square type intelligent panel meter to measure voltage, current, frequency and Power factor - 01Set. (d) Neon indicating lamps (R, Y & B) - 01 Set (03 Nos) Outgoing: (a) MCCB 160 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 04 Nos. (b) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos.(c) Astronomical timer switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos
63Supply, install, testing and commissioning in replacement, factory made and tested (including CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted, compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber with insulated TPN Aluminium bus bars 600 amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 50x50x6mm angle iron , powder coated, Front and rear opening type with aprons for cable entry with double door shutter and locking arrangement with including cable gland, lugs, jointing material etc and jointing, connecting, testing and commissioning and including following items. (Notes : The rate quoted shall include for Cost of dismantling/ taking down old unserviceable LT feeder piller, earth work & excavation for angle iron frame for foundation of panel board upto 0.50 m below GL in any type of soil & PCC (1:4:8), D2 filling in foundation the ground clearance of panel board shall be 0.40 m GL to the bottom of panel board).
64Incoming: (a) MCCB 400 amps, 4 pole, 50 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 No. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators for incoming supply - 01 set (c) Multifunctional Digital square type intelligent panel meter to measure voltage, current, frequency and Power factor - 01Set. (d) Neon indicating lamps (R, Y & B) - 01 Set (03 Nos) Outgoing: (a) MCCB 100 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 05 Nos. (b) MCCB 63 amps, 4 pole, 25 KA with adjustable thermal release, 50 Hz, 415 volts grade - 01 Nos.(c) Astronomical timer switch 1P Module, 24 hours program, Programmable every 15 min., backup of 100 hours, current capacity 16A, with 1 changeover (1 CO) complete with all accessories - 01 Nos
65M&L in repairs/replacement earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level, connecting with GI strip of size 32mm x 6 mm, by means of nut bolts, check nuts and washer and the GI Earth strip connected upto main earth point/DBs alongwith 40mm dia GI light grade protection pipe including provision of concrete pit in PCC (1:2:4) type B-1 using 20 mm graded stone aggregates with 40 mm thick RCC (1:2:4) cover with reinforced with XPM (weight not less than 4 Kg / Sqm) and frame of angle iron 25mm X 25 mm X 3mm with lugs 2 Nos and with 6 mm dia MS bar handle made to shape,
66with GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point all as specified including testing on completion. Note : Rate of GI earthwire and GI protection pipe upto 7.5 mtr length shall be deemed to be included in this item. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56240984
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 44 Lakhs
LAST DATE 21-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair / Replacement Of Lt Ug Cables And O/H Lines, Mccbs, Lt Panel Boards And Misc E/M Works At Chh Sambhajinagar Mil Station Under Ge(S) Ahilyanagar
Basic Detail
Tender No 8343/E8
Bidding Type Tender
Location
City Aurangabad
State Maharashtra
Key Dates
Publish Date 01 Jul 2026
Submission Date 21 Jul 2026
Open Date 23 Jul 2026
Finance
Tender Value 44 Lakhs
Tender Fee 500
EMD 88000
Exemption Available
Document List
8343Tenderdocuments.pdf
BOQ_868560.xls
c44bb6d9-183b-4264-83cb-10b8c83c9a17.html
Tendernotice_1 (1).pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 01, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 11 days
Jul 23, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 13 days

Tender Documents

Download All (ZIP) ↓
pdf

8343Tenderdocuments.pdf

xls

BOQ_868560.xls

html

c44bb6d9-183b-4264-83cb-10b8c83c9a17.html

pdf

Tendernotice_1 (1).pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders