Tender For Construction Work Of 132 Kv Gss At Sop Along With Oil Filteration And P&F Of Yard Light
Tender Value
30.13 Lakhs
Estimated cost
Bid Submission
16 Jul 2026
10 days left
EMD
60275
Bank guarantee accepted
Document Fee
2950
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Sawai Madhopur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Work Of 132 Kv Gss At Sop Along With Oil Filteration And P&F Of Yard Light
BOQ
| Sl. No. | Item Description |
| 1 | Laying of earth mesh with 25mm/28mm dia M.S Rod at a depth of 0.80 meter from top level of foundations, including excavation of trench of required depth and backfilling of the same, transportation of M.S Rods from site store to locations, welding of M.S Rod to M.S Rod along the length, at crossings and with earth electrodes as per drawing, application of bitumen compound and covering with bitumen impreganated tape on all welding joints, for the type of soil prevalent at 0.80 mete below top level of foundations (M.S Rod of above size & M.S flat as required shall be made available by RVPN).(a) In case electricity is made available by RVPN without charges(i) Any soil ,soft rock other than hard rock |
| 2 | Laying of earth mesh with 25mm/28mm dia M.S Rod at a depth of 0.80 meter from top level of foundations, including excavation of trench of required depth and backfilling of the same, transportation of M.S Rods from site store to locations, welding of M.S Rod to M.S Rod along the length, at crossings and with earth electrodes as per drawing, application of bitumen compound and covering with bitumen impreganated tape on all welding joints, for the type of soil prevalent at 0.80 mete below top level of foundations (M.S Rod of above size & M.S flat as required shall be made available by RVPN).(a) In case electricity is made available by RVPN without charges(ii) Hard Rock with Blasting subject to permission or without Blasting |
| 3 | Laying of earthing risers of 50x6mm/50x10mm/50x12mm size M.S Flat at a depth of 0.80 m,eters from top level of foundations, including excavation of trench of required depth and backfilling of the same, transportation of M.S Flat from site store to locations, preparation of risers bending as per requirement ( after heating if necessary), fixing on and welding / bolting to equiopment/ structure and peaks of structures, laying in the trench, welding to the earth mesh of M.S Rods as per drawing, including welding of extra length of M.S Flat of required, application of bitumen compound and covering with bitumen impregnated tape on all welded joints, painting of all surface of risers above ground level with red oxide and green paint, for the type of soil prevalent at 0.80 meter below top level of foundations ( M.S Rod of above sizes & M.S Flat as required shall be made available by RVPN)(A) In case electricity is made available by RVPN without charges(i) Any soil ,soft rock other than hard rock |
| 4 | Placing of earth electrods of 25/28mm dia M.S Rod of length 7.50 meters (approx) to a depth of 8.00 meters from the top level of foundations, including drilling of 200 mm dia earth pit having a throughout bore of 200 mm dia to a depth of 8.00 meters from the top level of the foundations in all types of rocks by DTH system and overburden, including back filling of pit with Bentonitc slurry (with cost of Bentonite slurry ), including its preparation, transportation of M.S Rod and Bentonite from site store to location, cutting of M.S Rod Rod to desired length welding of earth electrode to earth mesh of M.S Rod as per drawing, application of bitumen compound and covering with bitumen impregnated tape on all welded joints (M.S Rod of above sizes & M.S Flat as required shall be made available by RVPN)(i) In case electricity is made available by RVPN without charges. |
| 5 | ERECTION OF SUB-STATION STEEL STRUCTURES columns, Beams ,lighting mast and equipment structures (excluding Circuit Breakers and nuts & bolts, washers etc from site store to locations Their assembly, placing on foundation, fixing of template, with Foundation, fixing of template,. with foundation bolts as required Leveling and preparing for grouting as required but excluding Grouting, erection after grouting and tightening & punching of nuts & bolts. (Maximum height of structures up to 20 meters) |
| 6 | BUS - BAR WORKSTRINGING of 220KV,132KV, 33KV & 11KV Bus Bar of ACSR conductor, including transportation of conductor,disc Insulator and tension hardware from site stores to location laying And cutting required length of conductor, cleaning and assemblyof disc insulators as required along with fitting of bolted type or compression tape tension hardware as made available (compression machine shall be provided by RVPN on rent free basis) making up at one end, stringing of conductors between the beams with specified sag and tension, also equalizing sag and fitting spacer T-Clamps for twin conductor for three plates of conductors in each bus-section.(Per jumper basis)i) Any Single Conductor |
| 7 | BUS - BAR WORKSTRINGING of 220KV,132KV, 33KV & 11KV Bus Bar of ACSR conductor, including transportation of conductor,disc Insulator and tension hardware from site stores to location laying And cutting required length of conductor, cleaning and assemblyof disc insulators as required along with fitting of bolted type or compression tape tension hardware as made available (compression machine shall be provided by RVPN on rent free basis) making up at one end, stringing of conductors between the beams with specified sag and tension, also equalizing sag and fitting spacer T-Clamps for twin conductor for three plates of conductors in each bus-section.(Per jumper basis)ii) Any double Conductor |
| 8 | JUMPERS OF ACSR conductor ( 3 nos Y- type)between bus To equipment or between equipment to equipment or between bus, including transportation of conductor, disc insulators and hardware from site stores to locations, cleaning and assembly of disc insulators as required along with fitting of suspension hard- ware and erection as required, cutting required length of conductor making connections, fixing of spacers & spacer T-Clamps as required, tightening of clamps/connectors, dressing etc, for three phases. (Per jumper basis)i) Any Conductor |
| 9 | STRINGING of Earth wire(size 7/3.15 mm or 7/4.00mm) Including transportation of earthwire, tension hardwares Etc.from site store to locations laying and cutting required Length of earthwire,fitting of bolted type or compression Type hardware as made available (compression machine Shall be provided by RVPN on rent free basis) making up at One end stringing of earthwire between structure peaks with Specified sag and tension, jumpering and connecting earth Bonds, for single earthwire. |
| 10 | ERECTION OF SUB-STATION EQUIPMENTSI) Erection of 33/0.4 KV Station transformer upto 500 KVA on existing masonary platform including transportation of transformer & accessories from site store to location erection of Horn Gap fuse set jumpering from isolator to Horn Gap to transformer. |
| 11 | ERECTION OF SUB-STATION EQUIPMENTSErection of Current Transformer/Potential Transformer/ Capactive voltage Transformer /Series Reactor /Residual Voltage Transformer /Neutral Current Transformer with Clamps & connectors, on already erected steel structure including transport-Tation of base frame,fixing of terminal connectors,tightening of nuts & bolts etc. complete in all respect.ii) 132KV CT/PT/CVT/ |
| 12 | ERECTION OF SUB-STATION EQUIPMENTSErection of Current Transformer/Potential Transformer/ Capactive voltage Transformer /Series Reactor /Residual Voltage Transformer /Neutral Current Transformer with Clamps & connectors, on already erected steel structure including transport-Tation of base frame,fixing of terminal connectors,tightening of nuts & bolts etc. complete in all respect.iii) 33 KV CT/PT |
| 13 | ERECTION OF SUB-STATION EQUIPMENTSErection of Lightening Arrestor on already erected steel structure Including transportation of Lightening Arrestor,clamps & connectors Surge counter etc. from site store to locations fabrication of base frame Fixing of terminal connectors, surge counter, tightening of nuts and Bolts etc. complete in all respect.ii) 132 KV |
| 14 | ERECTION OF SUB-STATION EQUIPMENTSErection of Lightening Arrestor on already erected steel structure Including transportation of Lightening Arrestor,clamps & connectors Surge counter etc. from site store to locations fabrication of base frame Fixing of terminal connectors, surge counter, tightening of nuts and Bolts etc. complete in all respect.iii) 33 KV |
| 15 | ERECTION OF SUB-STATION EQUIPMENTSErection of Isolators(Motorised/Non motorised) on already, erected steel structures including transportation of base frame, P.I's contacts mechanism box clamps & connectors etc from site store to locations minor fabrication as required and fixing of termnial connectors etc adjustment / aligment of isolator and its earth blade, if provided for their smooth operation and final adjustment if required after jumpering including erection of PI.ii) 132 KVa) Without Earth Blade |
| 16 | ERECTION OF SUB-STATION EQUIPMENTSErection of Isolators(Motorised/Non motorised) on already, erected steel structures including transportation of base frame, P.I's contacts mechanism box clamps & connectors etc from site store to locations minor fabrication as required and fixing of termnial connectors etc adjustment / aligment of isolator and its earth blade, if provided for their smooth operation and final adjustment if required after jumpering including erection of PI.ii) 132 KVb) With Single Earth Blade |
| 17 | ERECTION OF SUB-STATION EQUIPMENTSErection of Isolators(Motorised/Non motorised) on already, erected steel structures including transportation of base frame, P.I's contacts mechanism box clamps & connectors etc from site store to locations minor fabrication as required and fixing of termnial connectors etc adjustment / aligment of isolator and its earth blade, if provided for their smooth operation and final adjustment if required after jumpering including erection of PI.iii) 33 KVa) Without Earth Blade |
| 18 | ERECTION OF SUB-STATION EQUIPMENTSErection of Isolators(Motorised/Non motorised) on already, erected steel structures including transportation of base frame, P.I's contacts mechanism box clamps & connectors etc from site store to locations minor fabrication as required and fixing of termnial connectors etc adjustment / aligment of isolator and its earth blade, if provided for their smooth operation and final adjustment if required after jumpering including erection of PI.iii) 33 KVb) With Single Earth Blade |
| 19 | ERECTION OF SUB-STATION EQUIPMENTSErection of Wave trap on already erected structure beam, Including transportation of wave tap, disc insulaltors,hardware Clamps and connectors,etc. from site store to locations,cleaning & assembly of disc insulators along with fitting of suspension Arrangement and erection, fixing of terminal connectors etc.ii) 132 KV |
| 20 | ERECTION OF SUB-STATION EQUIPMENTSErection of 220 KV or 132 KV circuit breakers, including transportation of equipment, structure members, nut & Bolts, Clamps & connectors, accessories etc. from site store to location assembly of support structure, their placing on foundation, levelling and prepairing for grouting as required, But excluding grouting, assembly/ placing of support colums / poles.Mechanism box/ control cubicles and other accesories as per manufecturers drawings, fitting of SF6 gas pipe lines, fabrication of air / oil pipe line as required, Electrical wiring from pole to control cubicle, fixing of terminal connectors as required, But excluding commissioning of CB, for all types of operating mechanism, as required.ii) 132 KV |
| 21 | ERECTION OF SUB-STATION EQUIPMENTSErection of 33 KV, 11 KV CB including transportation of equipment, structure members, nut & Bolts, Clamps & connectors, accessories etc. from site store to location assembly of support structure, their placing on foundation, levelling and prepairing for grouting as required, But excluding grouting, assembly/ placing of support colums / poles.Mechanism box as per manufecturers drawings, fitting of terminal connectors etc. But excluding commissioning of CB.i) 33 KV or 11 KV outdoor type (VCB / SF 6) |
| 22 | ERECTION OF SUB-STATION EQUIPMENTSErection of post Insulators on already erected structures including transportation of P.I's nuts & bolts, clamps & connectors etc from site store to locations, fabrication of base frame & assembly if required, fixing of clamps etc.ii) 132 KV |
| 23 | ERECTION OF SUB-STATION EQUIPMENTSErection of post Insulators on already erected structures including transportation of P.I's nuts & bolts, clamps & connectors etc from site store to locations, fabrication of base frame & assembly if required, fixing of clamps etc.iii) 33 KV or 11 KV |
| 24 | ERECTION OF SUB-STATION EQUIPMENTSErection of 132 KV class EHV transformer (Tank already placed on foundation with wheels.) including transportation of accessories from site store to locations, erection of HV, IV,LV & neutral bushings, main & OLTC conservators, radiators, equalizing pipe line marshalling kiosk etc. as per manufacturers drawing, prepairation of oil, oil filling , dehydration of transformer (filter machine, Oil tank & operating staff shall be provided by RVPN) electrical wiring from indivisual equipment e.g. Buchholz relay, MOLG, OSR, etc. to marshalling kiosk, etc. But excluding testing & commissioning of transformer.a) if electricity is available & arranged by RVPN without charges.i) Transformers received oil filled |
| 25 | ERECTION OF SUB-STATION EQUIPMENTSErrection of control & Relay Panles complete in all respect including transportation from site store to control room placing on foundation / cable trench as per layout, interconnection between Control & Relay panels and with existing panels, fixing of side/ top covers and doors earthing to existing earth strip in control room connection of bus wiring to existing panel and between control & relay panel as required.ii) Duplex Panel |
| 26 | ERECTION OF SUB-STATION EQUIPMENTSErrection of control & Relay Panles complete in all respect including transportation from site store to control room placing on foundation / cable trench as per layout, interconnection between Control & Relay panels and with existing panels, fixing of side/ top covers and doors earthing to existing earth strip in control room connection of bus wiring to existing panel and between control & relay panel as required.iii) Simplex Panel, DC Panel, RTCC Panel, PLCC Panel etc |
| 27 | ERECTION OF SUB-STATION EQUIPMENTSErrection of control & Relay Panles complete in all respect including transportation from site store to control room placing on foundation / cable trench as per layout, interconnection between Control & Relay panels and with existing panels, fixing of side/ top covers and doors earthing to existing earth strip in control room connection of bus wiring to existing panel and between control & relay panel as required.iv) LT Panel |
| 28 | ERECTION OF SUB-STATION EQUIPMENTSErection of Marshalling Kiosk/ Line Matching Unit (LMU) / Line Matching & Distribution Unit (LMDU) complete in all respect including transportation from site store to location, placing on foundation / cable trench as per layout preparing for grouting of foundation bolts but excluding grouting etc.i) 220 KV or 132 KV Marshalling kiosk |
| 29 | ERECTION OF SUB-STATION EQUIPMENTSErection of Marshalling Kiosk/ Line Matching Unit (LMU) / Line Matching & Distribution Unit (LMDU) complete in all respect including transportation from site store to location, placing on foundation / cable trench as per layout preparing for grouting of foundation bolts but excluding grouting etc.ii) 33KV Marshalling Kiosk |
| 30 | ERECTION OF SUB-STATION EQUIPMENTSErection of Marshalling Kiosk/ Line Matching Unit (LMU) / Line Matching & Distribution Unit (LMDU) complete in all respect including transportation from site store to location, placing on foundation / cable trench as per layout preparing for grouting of foundation bolts but excluding grouting etc.iii) PLCC LMU / LMDU |
| 31 | ERECTION OF SUB-STATION EQUIPMENTSErection of Battery Charger complete in all respect including transportation from site store to location placing on foundation / cable trench as per layout etc.i) 110 Volt DC, 200 AH |
| 32 | ERECTION OF SUB-STATION EQUIPMENTSErection of Battery Charger complete in all respect including transportation from site store to location placing on foundation / cable trench as per layout etc.iii) 48 Volt DC, 200 AH |
| 33 | BATTERY SETAssembly, erection and commissioning of Lead Acid Battery Set including transportation of cells, battery Stand, nuts & bolts etc. from site store to battery room, assembly of stand, placing the cells on stand, making their interconnection, initial charging and discharging and final charging as per procedure recommended by battery manufacturer.a) If electricity is available & arranged by RVPN without chargesi) 110 Volt DC, 200 AH |
| 34 | BATTERY SETAssembly, erection and commissioning of Maintenance Free Maintenance Free VRLA Type Battery Set including transportation of cells, battery Stand, nuts & bolts etc. from site store to battery room, assembly of stand, placing the cells on stand, making their interconnection, initial charging and discharging and final charging as per procedure recommended by battery manufacturer.iii) 48 Volt DC, 400/200 AH |
| 35 | LAYING AND TERMINATION OF CABLESControl Cablesi) Laying of PVC insulated unarmoured / armoured control cables of 1.1 KV grade with copper conductor in cable trenches as per specification as required, including transportation of cable drums from site them on cable racks / cable trays / cable batten & dressing including removing and re-fixing trench covers as required making necessary connection testing cable marking on both the termunating ends etc. as required for all sizes from 2cx2.5 sq mm to 20cx2.5 sqmm, 4cx6sq mm.a) Unarmoured control cable |
| 36 | LAYING AND TERMINATION OF CABLESControl Cablesii) Fixing of control cable in position with single compression nickel plated brass cable glands confirming to IS: 12943 & having three metal washers and one rubber ring, including preparation of cable and drilling of corresponding holes in gland plates etc. as required, & including cost of cable glands, for each cable gland of size.a) 19 mm unarmoured control cable |
| 37 | LAYING AND TERMINATION OF CABLESControl Cablesii) Fixing of control cable in position with single compression nickel plated brass cable glands confirming to IS: 12943 & having three metal washers and one rubber ring, including preparation of cable and drilling of corresponding holes in gland plates etc. as required, & including cost of cable glands, for each cable gland of size.c) 25 mm unarmoured control cable |
| 38 | LAYING AND TERMINATION OF CABLESControl Cablesii) Fixing of control cable in position with single compression nickel plated brass cable glands confirming to IS: 12943 & having three metal washers and one rubber ring, including preparation of cable and drilling of corresponding holes in gland plates etc. as required, & including cost of cable glands, for each cable gland of size.e) 32 mm unarmoured control cable |
| 39 | LAYING AND TERMINATION OF CABLESControl Cablesiii) Termination of wires of cables with copper conductor using copper terminal ends ( pin or ring type as required of Dowell's or equivalent make as approved by the Engineer- In-Charge ) duly crimpede with crimping tool including making wire ends ready f or crimping ferulling & dressing of wire etc. as required including cost of terminal ends for all wires for each cable at both ends for cable at both ends of the following sizea) 2.5 sqmm for any number of core |
| 40 | LAYING AND TERMINATION OF CABLESControl Cablesiii) Termination of wires of cables with copper conductor using copper terminal ends ( pin or ring type as required of Dowell's or equivalent make as approved by the Engineer- In-Charge ) duly crimpede with crimping tool including making wire ends ready f or crimping ferulling & dressing of wire etc. as required including cost of terminal ends for all wires for each cable at both ends for cable at both ends of the following sizeb) 4 sqmm for any number of core |
| 41 | LAYING AND TERMINATION OF CABLESL.T POWER CABLES i) Laying of P.V.C insulated P.V.C sheathed armoured/ unarmoured L.T. power cable of 11 KV grade with aluminium conductor as per IS: 1255 in ground/ cable trench/ wall/ surface including transportation of cable drums from site store to locations and excavation of 30 cm x 75 cm size trenches providing 25mm thick under l;ayer of sand & 2nd class brick covering & refilling earth in remaining portion, fixing as per approved/ available spacing by means of M.S.U- clamps etc. as per specification as required including making necessary connections & testing etc. as required of the following sizes.d) 3 half core x 300 sq.mm |
| 42 | LAYING AND TERMINATION OF CABLESL.T POWER CABLESii) Fixing of power cables in position with single compression, heavy duly nickel plated brass cable glands as per IS: 12943 & having three metal washers and one rubber ring, including pre- paration of cable and drilling of corresponding holes in gland plate etc. including cost of cable gland if required, for each end of cable of size.g) 75/76 mm for 3half core x 300 sq.mm cable with material |
| 43 | LAYING AND TERMINATION OF CABLESL.T POWER CABLESiii) Termination of wires of cables with aluminium conductors using ISI marked tubular aluminium terminal ends as per IS:8309 duly crimped with crimping tool, including making cable ends ready for crimping and providing insulation tape with colour code pressing of wires, etc, including cost of terminal ends if required for each end of cable (4 nos. per end) for the following sizes of cables.g) 3 half core x 300 sq.mm cable with material |
| 44 | OIL FILTERATIONDehydration / filtration of Transformer Oil (Electricity shall be supplied by the RVPN) of New 132/33 KV 31.5 MVA transformer at under construction 132 KV GSS Nasirda as per norms in presence of Work In-Charge. |
| 45 | Part B- Yard LightP & F Normal / High Output High pressure sodium vapour/ Metal halide / Halogen lamp as required complete in all respect. All as per pre approved by Engineer inchargeHPSV Tubular lamp Normal Output250 Watt 28000 Lumens |
| 46 | Part B- Yard LightP & F IP -65 protected integral flood light luminaire suitable for HPSV/ Metal halide lamp comprising of powder coated die cast aluminium housing, electrochemically brightened and anodized stippled aluminium reflector, covered with suitably gasketed heat resistant and toughened glass, porcelain holder, integral control gear box having copper ballast, capacitor, electronic ignitor prewired with pvc insulated copper conductor up to terminal block including making connection testing etc. as required. (with out lamp)1 X 250 Watt |
| 47 | Part B- Yard LightP & F flush/surface type plastic enclosure for housing MCB/Isolator with Din rail including making connections with lugs, repairs etc. as requiredTwo way |
| 48 | Part B- Yard LightProviding & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRSingle pole MCB (With B/C curve tripping Characteristics)i) 6 A to 32 A rating |
| 49 | Part B- Yard LightProviding & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947- 2, low watt losses, trip free mechanisum , energy limiting of class 3 as per IEC, minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRDouble pole MCB (With B/C curve tripping Characteristics)ii)40 A rating |
| 50 | Part B- Yard LightProviding & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRMetal door (Three phase) IK-09 and IP-43 with Metal end boxi) 4 Way |
| 51 | Part B- Yard LightProviding & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp. insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set of suitable rating and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. OEM shall have submit NABL / CPRI / ERDA accrediated lab type test reports & All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure 'A' attached with this BSRGlaze door single phase) IK-09 and IP-43 with Metal end boxi) 4 Way (4+2) |
| 52 | Part B- Yard LightProviding & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR4 Sq. mmi)2 core |
| 53 | Part B- Yard LightProviding & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR6 Sq. mmi)2 core |
| 54 | Part B- Yard LightProviding & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-Arrmoured Aluminium cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810. For additional technical parameters of product / work refer Annexure 'A' attached with this BSR16 Sq. mmi)4 core Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jul 01, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysJul 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓