Tender For Special Repair Of Annexes, Hanging Lights And Wiring Of Hanger Bldg No To-260 Of Avn Unit Under Ge 865 Ews

BOQ

Name of Work:- SPECIAL REPAIR OF ANNEXES, HANGING LIGHTS AND WIRING OF HANGER BLDG NO TO-260 OF AVN UNIT UNDER GE 865 EWS
Sl. No. Item Description
1M&L for 9mm thick prelaminated particle board interior grade, prelaminated one side with decorated choice lamination & other side balancing white lamination fixed with nails to timber frame work as in wall panelling, shelves/boarding including dismantling existing one, complete all as specified and/or as as directed by Engr-in-Charge.
2All as per Srl item No 1.00 above, but in ceiling.
3S&F anodised aluminium snap grid of size 605 x 605 frame work of false ceiling including hanger 6mm dia GI (up to 1200 mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5 mm dia 40mm long, complete all as specified and/or as directed by Engr-in-Charge.
4M&L providing and fixing Gypsum board 12mm thick and 600 x 600 mm in size in ceiling fixed with screw or with staples on snap grid as per manufacturer's instructions including dismantlng existing ceiling, complete all as specified and directed by Engr-in-Charge.
5M&L for not less than 15mm thick wooden battens of 100mm wide fixed each other with male and female grooves fixed with screws to timber frame work as in wall panelling, shelves/boarding including dismantling existing one, complete all as specified and/or as as directed by Engr-in-Charge.
6All as per Srl Item No 5.00 above, but in ceiling.
7M&L French polishing on wood or wood based surface of any width or girth or any description, including cleaning and preparing the surface including a coat of wood filler on new surface with two or more coats to obtain required finish, complete all as specified and/or as as directed by Engr-in-Charge.
8M&L for 2nd class soft wood clean sawn as in battens for grids of ceiling & lining fixed with nails exc 13 sqcm and not exc 25 sqcm in section including dismantling existing one, complete all as specified and/or as as directed by Engr-in-Charge.
9M&L for 2nd class soft wood clean sawn as in beeding for edges of ceiling, lining or wooden flooring work fixed with nails exc 6 sqcm and not exc 13 sqcm in section including dismantling existing one, complete all as specified and/or as as directed by Engr-in-Charge.
10M&L for covered fillets of standard hard board not less than 6mm thick and up to 40mm wide and fixing with screws including dismantling, complete all as specified and/or as directed by Engr-in-Charge.
11S&F in repair aluminium (die cast) body door closer hydraulically regulated designation No 3 universal type suitable for door shutter of 851 to1000mm in width and weight 61 to 80 kg, complete all as specified and/or as directed by Engr-in-Charge.
12S&F in repair floor door stopper (length of cover plate) 150mm long of aluminium alloy body and tongue anodised with hard drawn steel spring fixed in floor, complete all as specified and/or as directed by Engr-in-Charge.
13S&F in repair 19mm dia mild steel, chromium plated curtain rods, with brackets, end bulbs, complete all as specified and/or directed by Engr-in-Charge.
14Taking down chowkat or frame with shutters (without taking off shutters from the frame) not exc. 1.5 sqm each any type of door (wooden, aluminium & steel etc.), complete all as specified and/or as directed by Engr-in-Charge.
15Taking down chowkat or frame with shutters (without taking off shutters from the frame) exc. 1.5 sqm and not exc. 4 sqm each any type of door (wooden, aluminium & steel etc.), complete all as specified and/or as directed by Engr-in-Charge.
16Taking down shutters of any description area exc. 1 sqm and not exc. 2 sqm each, complete all as specified and/or as directed by Engr-in-Charge.
17All as per Srl Item No 16.00 above, but not exc. 1.0 sqm each.
18Taking down shutters of any description area exc. 1 sqm each, resecuring or easing, adjusting and refixing in the same opening, complete all as specified and/or as directed by Engr-in-Charge.
19All as per item No 18.00 above, but area exc. 1 sqm and not exc. 2 sqm each.
20S&F Powder coated (minimum thickness of powder coating 50 micron) anodised aluminium frames for door, windows, ventilators with double rebates including joining cleat for fixing etc. complete all as specified and/or as directed by the Engr-in-Charge.
21M&L for powder coated aluminium door shutters, aluminium sections weighing 0.55 Kg/m including necessary joining cleats, glazing clips, rubber neoprene packing, anodised aluminium snap beading, screws etc., complete all as specified and/or as directed by Engr-in-Charge.
22S&F anodised aluminium window and ventilator shutters, including aluminium jali fixed in one side, side hung type without sashbars, aluminium section weighing 0.55 Kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading screws, anodised aluminium fittings such as peg stays 150mm long (1 No) hinges type B-21 100mm long (2 Nos) suitable handle (1 No) etc. complete all as specified and/or as directed by Engr-in-Charge.
23Hacking out old broken glass (any thickness, size, quality or description) from wooden panes or stone, concrete or brick surrounds, glazed with oil putty or fixed with beads complete all as specified and/or directed by Engr-in-Charge.
24M&L sheet glass 3mm thick ordinary quality and glazing with oil putty or wooden beads in square not exc. 0.50 sqm in each pane, complete all as specified and/or as directed by Engr-in-Charge.
25M&L sheet glass 5.5mm thick ordinary quality and glazing with oil putty or wooden beads in square exc. 0.50 sqm in each pane, complete all as specified and/or as directed by Engr-in-Charge.
26M&L for hard wood 2nd class factory made wooden boarded floors 10mm thick and skirtings planed one side & edges tonged and grooved or rebated, including backing with thermocol sheets or as specified by manufacture including dismantling existing boarding, complete all as specified and/or as directed by Engr-in-Charge..
27Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) and removing rubbish off the premises, complete all as specified and/or as directed by Engr-in-Charge.
28Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for and removing debris off the premises, complete all as specified and/or as directed by Engr-in-Charge.
29M&L for 25 mm thick PCC 1:2:4 type B1 (using 20mm graded stone aggregate) as in sub base of floor, complete all as specified and/or as directed by Engr-in-Charge.
30M&L for joint free non-skid coloured ceramic tiles 7 to 8mm thick (square/rectangular) area of each tiles exceeding 0.11 sqm but not exc. 0.18 sqm in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over and including 15mm thick screed bed or bedding layer in CM 1:4, complete all as specified and/or as directed by Engr-in-Charge.
31M&L virified ceramic Coloured Tiles 10mm thick(square/rectangular) polished area of each tile not exceeding 0.36 sqm, in floors over 15 mm screed bed or bedding layer in cement mortar 1:4 set and jointed in neat cement slurry and pointed in colour cement to match, complete all as specified and/or as directed by Engr-in-Charge.
32M&L for glazed ceramic coloured tiles in vertical surfaces of size 450x350x7mm/ 350x250x7mm thick set and jointed in neat cement slurry and pointed with white or coloured cement to match over and including rendering 10 mm thick in cement mortar (1:4) in dado/skirting tiles, complete all as specified and/or as directed by Engr-in-Charge.
33S&F of 60mm thick insulated roof panel with 0.50mm thick PPGI sheet with micro ribs (Make -JSW) (RAL-9002) both side with PUF density 44 Kg/m3 +- 10% in metalic tongue and groove joint system with cut to size, with no loading of wastage with additional 90 degree bends in male & female groove to have proper sealing, strength & air tight joint panel to panel, CFC free & ozone friendly (Pentane Based) fixed at roof including dismantiling existing one, complete all as specified and/or as directed by Engr-in-Charge.
34M&L for preperation of old Steel / CGI sheet surface any description over 10cm in width or girth and applying two coats of synthetic enamel paint, complete all as specified and as directed by Engr-in-Charge.
35S&F 25mm dia 3 layer PP-R polypropylene random copolymer concealed pipes SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass threaded polypropylene random fittings fixed complete all as per manufacturer's instructions including taking up or down 25 mm bore steel tubing / PPR pipe and connections and set aside for re-use or removal to store, complete all as specified and/or as directed by Engr-in-Charge.
36All as per item No 35.00 above, but 32 mm dia pipe.
37S&F in repair 25mm outer dia PPR Gate valve (Brass insert) conforming to ISO 2000 high pressure with epoxy coated aluminium rod and high density plastic ball screwed for PPR pipe or for union and fixed as per requirement on site, complete all as specified and as directed by Engr-in-Charge.
38All as per item No 37.00 above, but 32 mm dia.
39S&F rotational moulded HDPE water storage tanks 1000 ltrs capacity and will be PUF insulated with 75mm thick PUF insulation of density 48 kg/Cum inner and out white two layers ISI marked (cylindrical vertical type/rectangular loft type closed top) hoisted with threaded cap and fixed in position all as specified in SSR Part I including all accessories (i.e. GI nipple etc.), including provn of 20/25 mm dia spout for connecting inlet, outlet, over flow and washout pipes including dismantling water tank and removing to store, complete all as specified and as directed by Engr-in-Charge.
40S & F in repair 15 mm Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high density plastic ball screwed for iron pipe and fixed. (Minimum weight 15mm-142gms), complete all as specified and/or as directed by Engr-in-Charge.
41S&F in repair fancy type, chromium plated 20mm dia bore stop valves, cast copper alloy (concealed type), screwed down high pressure, screwed both ends for iron pipes or for unions, complete all as specified and/or directed by Engr-in-Charge.
42S&F in repair fancy type, chromium plated 15 mm bore pillar taps, cast copper alloy screwed down high pressure, screwed both ends for iron pipe or for unions, complete all as specified and directed by Engr-in-Charge.
43S&F in repair Vitreous China wash hand basin fancy type pedestal pattern, white, flat back, size 550 x 400mm including cutting for and pinning in ends of brackets or erecting stand but exclusive of fixing of supply and waste pipe, complete all as specified and/or directed by Engr-in-Charge.Make : Jaquar / Cera or equivalent as approved by GE.
44S&F 750 mm long, 32/ 40 mm dia, PVC plain waste pipe for sinks / wash hand basins, complete all as specified and/or as directed by Engr-in-Charge.
45S&F in repair vitreous China wash down water closet (pedestal pattern), white (EWC) including plastic seat cover of same colour of WC, closed pattern with flat bottom and cover and mild steel chromium plated hinging device complete all as specified and/or directed by Engr-in-Charge.Make : Cera / Jaquar / Kohler or equivalent as approved by GE.
46Supply only flushing cistern of PVC 10 ltr. cap. with dual flushing system, white colour, valveless symphonic action type, low level, with inlet, ball valve, float and including brackets and connection to pipe etc. incl all necessary accessories like rag bolts/ gel gasket etc. as recommended by manufacturer for fixing, packing complete.
47S&F in repairs 15mm bore, PVC connection pipe 600 mm long with PTMT nuts at both ends, complete all as specified and as directed.
48S&F in repair CP toilet jet spary ABS with double lock 1.2 mtr CP tube stainless steel flexible hose complete all as specified and/or directed by Engr-in-Charge.
49S & F in repair CP floor gratings 150mm dia, all as directed by the Engr-in-Charge
50S&F in repair PVC (SWR) 75 mm dia floor trap with plain with grating including jointing with solvent cement complete all as specified and directed.
51S&F in repair Chrominum plated brass soap dish (Oval shape fixed) to walls (size not less than 125mm) complete all as specified and/or as directed by Engr-in-Charge.
52S&F in repairs 20mm bore angle stop valves, fancy type chromium plated with long shank and cast copper alloy (concealed type), screwed down high pressure, screwed both ends for iron pipes or for unions, complete all as specified and/or directed by Engr-in-Charge.
53S&F in repairs fancy type 15 mm bore chromium plated bib taps, cast copper alloy, screwed down high pressure, screwed both ends for iron pipes or for unions, complete all as specified and/or directed by Engr-in-Charge.
54S&F in repairs vitreous china urinal half stall type, white complete including providing and fixing plugs, bedding urinal against wall in CM 1:2 securing urinal to plugs with and including 60 mm brass screws, pointing around urinal back in white cement, fixing grating and union for discharge pipe excluding flushing cistern, flush pipe but including CP waste coupling, PTMT urinal spreader, etc. complete all as specified and as directed by the Engr-in-Charge.Make : Jaquar / Hindware or equivalent as approved by GE.
55M&L for Cement concrete 1:4:8, type D-2, (using 40mm stone graded aggreate) 75 mm thick as in sub -floors, sub- bases, floors and pavings etc., complete all as specified and as directed.
56Demolition of stone slabs and tiles of any description or thickness in floors aprons etc. laid bedded and pointed in any mortar, complete all as specifed and directed.
57M&L for Chequred cement concrete tiles (glazed) 20cm X 20cm X 25mm thick, set , pointed & jointed in neat cement slurry in floors polished with grey cement & pigments, laid over 20mm thick cement screed base (1:6), complete all as specified and/or as directed by Engr-in-Charge.
58M&L for 75 mm thick PCC 1:3:6, type C-2 (using 20mm graded aggregate) as in plinth protection finished even and smooth with out using extra cement, complete all as specified and/or as directed by Engr-in-Charge.
59M&L forming contraction (Dummy) joints 65 mm deep x 10mm wide, filled with sealing compound Grade 'A' in plinth protection, complete all as specified and/or as directed by Engr-in-Charge.
60Dismantling plain or corrugated steel /fibre sheeting any guage thickness including nanital or similar pattern complete all as specified and as directed
61S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and/or directed by Engr-in-Charge.
62Dismantling wrought iron or mild steel work of any description not otherwise provided for angle iron or flat iron as in post and guard bars or grating, complete all as specified and as directed.
63S&F rolled section as in main and cross beams, hip and jack rafters, purlins where connected to common rafters and running rails and guide, for sliding doors fixed with angle cleats or other connecting plates and similar work conforming to Fe -290 Gde E-165, complete all as specified and/or directed by Engr-in-Charge.
64Taking down carefully copper/aluminium point wiring (light, fan, socket and power point) complete fittings such as switches, ceiling rose, regulators, socket etc. and removing material from site and making good disturbed surfaces of walls, floors/ceiling to match the existing surface, complete all as specified and/or as directed by Engr-in-Charge
65Point wiring complete with 1.5 sqmm nominal area of copper conductor multi stranded PVC insulated and unsheathed 1100 volts cable drawn through & including PVC casing & caping with standard accessories such as elbows, tees, junctions etc. and PVC moulded terminal box with top cover of including PVC insulated unsheathed solid 1.5 sqmm copper conductor cable as continuous earth lead complete all as specified and/or directed by Engr-in-Charge for the following:-
66One light/exhaust fan point controlled by one way switch.
67One switch socket outlet 6 Amps, 230 volts on same board.
68One switch socket outlet 6 Amps, 230 volts on independent board.
69All as per srl item No 65.00 above, but using cables 4 sqmm size.
70S&F in replacement of switch piano flush button single pole 6 Amps 230 volts one way complete all as specified and/or directed by Engr-in-Charge.
71S&F of socket outlet two in one, 5 pin 6 Amps flush type 230 volts complete all as specified and/or directed by Engr-in-Charge.
72S&F of switch Socket combination outlet multi purpose 5 pin 6 Amps and 16 Amps 230 volts complete all as specified and/or directed by Engr-in-Charge.
73S&F in replacement of sheet metal enclosure for DBs double door when MCB's to be used single pole & neutral 240 Volts 12 Ways complete all as specified and/or directed by Engr-in-Charge.
74S&F in replacement of LED light fitting 1X20 W, 220 V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and/or directed by Engr-in-Charge. Make : Havells /Crompton/ Bajaj or equivalent as approved by GE.
75S&F in replacement LED light fitting mirror type with high output diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed .
76S&F 1x1 feet surface light 18/20 watt 220 V AC decorative type copper conductor cable of suitable size complete all as specified and directed. Make : Havells / Crompton / Bajaj or equivalent as approved by GE.
77S&F in replacement LED high bay light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and/or directed by Engr-in-Charge.
78S&F in replacement LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and/or directed by Engr-in-Charge.
79M&L for sub main wiring with two runs of FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 2.5 sqmm 1100 volts grade and including non metalic rigid suitable size PVC conduit with all fitting and fixing accessories and including PVC insulated, unsheathed, multistranded copper conductor cable of size 1 x 2.5 sqmm for earth continuity conductor including taking down old unserviceable sub main wiring, complete all as specified and/or as directed by Engr-in-Charge.
80M&L for sub main wiring with four runs FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 16 sqmm 1100 volts grade and including non metalic rigid 25 mm dia in DLP PVC Trunk with all fitting and fixing accessories and including PVC insulated, unsheathed, multistranded copper conductor cable of size 1 x 16 sqmm for earth continuity conductor and including taking down old unserviceable sub main wiring, complete all as specified and/or as directed by Engr-in-Charge.
81S&F in replacement 4 way double door Tripple Pole Neutral vertical load line Distribution Board suitable for Flush mounting and suface mounting with 160 A & 250 A copper bus bar with neutral bars and earth bars including MCCB 160 Amps TPN as incomer and SP/TP MCBs as outgoing and making good disturbed surfaces of walls, floors, etc. complete all as specified and/or as directed by Engr-in-Charge.
82S&F MCCB 3 pole, 415V, fixed type, 160 Amps with breaking capacity 16 KA, complete all as specified and/or as directed by Engr-in-Charge.
83S&F ceiling rose, surface Bakelite three terminals complete all as specified and/or directed by Engr-in-Charge.
84S&F in replacement of sheet metal enclosure for DBs double door when MCB's to be used single pole & neutral 240 Volts 08 Ways complete all as specified and/or directed by Engr-in-Charge.
85S&F MCB SPN 40/63 Amp 240 Volts AC ISI marked complete all as specified and/or directed by Engr-in-Charge.
86S&F MCB SP 6-32 Amp 240 Volts 50 Hz AC ISI marked complete all as specified and/or directed by Engr-in-Charge.
87M&L for Earthing complete with galvanised steel earth plate electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and including 4 mm dia GI wire as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 3 of MES SSR Part I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and/or as directed by Engr-in-Charge.
88Taking down old unserviceable fan of capacity upto 300 mm sweep from site and shifting to civil workshop for removing burnt winding, ball bearing, bushes, broken wings, condenser and deteriorated louver and rewinding with new super enamalled fine copper gauge of same size and replacing with new ball bearings, bushes, condenser of 2.5mfd, wings, louvers and bring back to site and refixing the same in its original position and testing , complete all as specified and/or as directed by Engr-in-Charge.
89Taking down old unserviceable industrial plug & socket and supply and fix industrial socket with box for capacity 63 A, 3P+N+E, 415 volts with IP 66 protection, complete all as specified and/or as directed by Engr-in-Charge.Make : Havell / Crompton / Bajaj or equivalent as approved by GE.
90Taking down old unserviceable industrial plug & socket and supply and fix industrial socket with box for capacity 32 A, 2P+N+E, 230 volts with IP 66 protection, complete all as specified and/or as directed by Engr-in-Charge.Make : Havell / Crompton / Bajaj or equivalent.
91S&F in replacement off load change over of 400 Amps with enclosure, complete all as specified and/or as directed by Engr-in-Charge.
92M&L for sub main wiring with four runs of FRLSH PVC insulated, unsheathed, multistranded copper conductor cable of size 25 sqmm 1100 volts grade and including non metalic rigid 25 mm dia in DLP PVC Trunk with all fitting and fixing accessories and including PVC insulated, unsheathed, multistranded copper conductor cable of size 1 x 25 sqmm for earth continuity conductor and including taking down old unserviceable sub main wiring, complete all as specified and/or as directed by Engr-in-Charge.
93S&F in replacement of MCCB 3 pole, 415 volts, fixed type, 200 Amps with breaking capacity 16 KA, complete all as specified and/or directed by Engr-in-Charge.
94Supply and laying in replacement of XLPE insulated, armoured, heavy duty electric cables, with stranded aluminium copper conductor rating 1100 volts grading of size 240 sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls / poles, complete all as specified and/or directed by Engr-in-Charge.
95M&L for earthing complete with galvanised steel earth plate electrode 600 X 600 X 6mm thick buried directly in ground vertically to a depth not less than 2.25 meters deep below ground level with top edge of the earth plate not less than 1.5 meter deep below normal ground level, connected with and including galvanised iron strip of size 25 x 4mm connected to main test point as directed as earthing lead by means of nuts, bolts and washers of galvanised iron protected by 40mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe, including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350 x 350 x 50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size for lifting of cover slab, charcoal and salt in alternate layers including necessary excavation and earth work in soft/loose soil all as shown in Electrical plate No 3 of SSR Part-I and testing on completion, complete all as specified and/or as directed by Engr-in-Charge.Note : (i) GI earth strip will be measured and paid separately beyond 7.5 mtr length. (ii) The rates of funnel with GI pipe for watering is deemed to be included in this item.
96Supply, installation, testing and commissioning in replacement of factory made cubical out door LT panel floor mounted weather proof totally enclosed confirming to IP-54, CPRI approved fabricated from 3.15 mm thick CRCA sheet powder coated and angle iron complete with bus bar of copper of suitable size for capacity 600 Amps 3 Phase and Neutral 415 Volts 50 Hz mounted on epoxy type insulators with PCC flooring and angle iron base frame, cmolpete all as specified and/or as directed by Engr-in-Charge including following accessories :-(i) MCCB 4 pole 400 Amp 36 KA, 415 Volts - 01 No for I/C. (ii) MCCB 3 pole 160 Amp 25 KA, 415 Volts - 02 Nos (iii) MCCB 3 pole 100 Amp 25 KA, 415 Volts - 02 Nos (iv) MCCB 3 pole 63 Amp 16 KA, 415 Volts - 01 No (v) Digital Volt meter with selector switch (0-500V) - 02 Set(vi) Digital Amp meter with selector switch with necessary CT (0-500) - 02 Set(vii) LED indicating lamp - 01 SetNote : (i) The make of change over switch and MCCB considered are Havells / Standard/Indo Asian/HPL(ii) The rates deemed to be inclusive of suitable size copper wiring / copper strips from main I/C MCCBs to Change over switch, change over switch to Main bus bar and Bus bar to outgoing MCCBs, complete all as specified and/or as directed.(iii) The design of panel, make of complete accessories and drawing of the LT Panel should be submitted by the Contractor for pre-approval from Engr-in-Charge before order and execution at site.
97Taking down old unserviceable strip of any type and supply and fix insulated copper strip of size 25 x 3 mm on DM insulator, complete all as specified and/or as directed by Engr-in-Charge.
98Taking down old unserviceable earthing of any type and supply, erect and install maintenance free, low carbon copper coated earth rod of 3 meter length 3 Nos connected to each other triangally with copper strip of 25 x 3mm for better result and electrode having diameter of 17.2 mm with copper coating thickness of 250 micron tested as per IEC 6256-2, including earth chamber to ensure safety of earthing system, complete all as specified and/or as directed by Engr-in-Charge.
99S&F in replacement air termination, single pointed copper rod 12mm dia 300 mm long on GI pipe medium grade duly fixed/secured on existing GI pipe/angle of hanger duly fixed including suitable insulators to avoid contact from hanger, complete all as specified and/or as directed by Engr-in-Charge.
100Excavation in trenches not exc. 1.5 m wide and not exc. 1.5 m in depth, for foundation etc. in hard/dense of soil and getting out, complete all as specified and as directed.
101M&L for hardcore of broken stone gauge not exc. 63 mm, deposited, spread and levelled in layers not exc. 15cm thick watered and rammed to a true surface. complete all as specified and as directed.
102M&L for PCC 1:4:8, type D2 (using 40mm graded crushed aggregate) as in mass concrete and filling of foundation, complete all as specified and/or as directed by Engr-in-Charge.
103M&L precast cement concrete 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) as in block masonry, set in cement mortar 1:4, complete all as specified and/or directed by Engr-in-Charge.
104M&L for rendering 15mm thick cement plaster fair face of brick work or concrete surfaces finished even and smooth without using extra cement in cement mortar 1: 4 including mixing of liquid water proofing compound as per manufacturer's instructions complete all as specified and as directed by Engineer-in-Charge.
105Returning, filling in (soil), including spreading, levelling, watering and well ramming in layers not exc. 25 cm, complete all as specified and directed by Engr in Charge.
106Removing excavated surplus soil to a distance not exc. 50 m and depositing where directed at a level not exc. 1.5 m above the starting point, complete all as specified and directed by Engr in Charge.
107S&F mild steel plates, plain or chequered, 5mm thick or over in thickness in required sizes including welding work, complete all as specified and directed by Engr in Charge.
108M&L for two coats of synthetic enamel paint over one coat of red oxide priming including preparation of new steel surfaces over 10 cm width or grith not otherwise described.
109M&L for sand cushioning to under ground cables 8 cm below the cable before laying & 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I, 2009. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 56240008
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 1.08 Crore
LAST DATE 28-07-2026
Authority
Authority Name Military Engineer Services
Work Description Tender For Special Repair Of Annexes, Hanging Lights And Wiring Of Hanger Bldg No To-260 Of Avn Unit Under Ge 865 Ews
Basic Detail
Tender No 138WE/L-28/2026-27
Bidding Type Tender
Location
City leh
State Ladakh
Key Dates
Publish Date 30 Jun 2026
Submission Date 28 Jul 2026
Open Date 04 Aug 2026
Finance
Tender Value 1.08 Crore
Tender Fee 1000
EMD 1.83 Lakhs
Exemption Available
Document List
95fe0879-944c-4b23-b0a3-3bb5adcceeff.html
BOQ_868214.xls
TenderL282627.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jun 30, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 28, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 18 days
Aug 04, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 25 days

Tender Documents

Download All (ZIP) ↓
html

95fe0879-944c-4b23-b0a3-3bb5adcceeff.html

xls

BOQ_868214.xls

pdf

TenderL282627.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders