Tender for Commissioning Of 200 Mm Non-Gravel Packed Production Well At Water Supply Scheme Dadsara Under Cdf (Tral Constituency).
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Installation, Testing & Commissioning of Submersible Pumping Unit of size V6 (150 mm) as per IS 8034 with following specification are as under:PUMP: Efficiency = Not less than 50% Speed = 2900 RpmType of pump = axil flow Type of fluid to be handled = Clear Water MATERIAL OF CONSTRUCTION:Impeller = Stainless SteelPump Shaft = Stainless Steel SS 410. Pump Casing = Cast Iron/Stainless steelIMPELLER: Impeller is of the enclosed type and properly balanced. Enclosed Impellers equipped with seal rings on their hubs.COUPLING: A suitable coupling arrangement provided with pump set.Non-Return Valve: Non-Return Valve of the suitable size provided above the pump discharge case.MOTOR: Method of starting = Star – Delta /DOL Speed = 3000 (Sync).Frequency = 50 ± 3 % HzWorking Voltage = 380-415 ± 15% V, 03 phase Efficiency = Not less than 90%Class of insulation = F/Suitable for above parameters Submersible motor should be water filled water lubricated squirrel cage type having capacity for above pumping parameters and working on 3 phase; AC supply ranging from 380 to 415 volts, 50Hz. The motor should be sealed by radial rings to avoid mixing of well water with motor filled water.a) The job includes providing and fitting of interlocking arrangement against any failure of coupling. It must be fabricated out of MS strips of suitable size and length.b) The job includes providing and fitting of appropriate size MS nipple 2 feet long threaded on one end and welded to same size MS flange of thickness (as per Table-17) at other end for column pipe as per site requirement. The threaded portion should be as per size of pumping out let for proper fixing.The job includes providing and fitting of R. I. cloth joints/rubber washers with nuts, bolts and washers for all joints of column pipe. The job also includes lowering of pumping unit in the well then proper testing and commissioning of pumping unit on full load at site.Note: Providing of test certificate & Characteristic Curve of pumping equipment is compulsory and pumping unit is to be approved from the concerned Sub Divisional office before procuring.Discharge = 5000 GPH, Head = 45 m Motor Rating: Not less than 7.5 HPSize of pumping unit : Not greater than V6 |
| 2 | Fabrication, providing, fitting and lowering of column pipe conforming to IS: 1239 of length 10 Rft into the 200 mm casing dia. production well up to the desired depth; The job includes Providing and welding of flanges conforming to IS: 6392, Table-5 and PN 16 to these pipes and welding of flanges in two layers to make the flanged joint strong and leak proof. The pipe of 10 ft length is to be weld on both sides with flanges using welding rod of reputed make. The job includes all types of skilled labours, arrangement of power supply/ diesel Generator set etc required for the job including P/F of suitable size nuts bolts and R.I Gasket in the flanged joints of column pipes. The job further includes cutting of 2 No. rectangular cable slots in each flange.Size : DN 65 Class: C (Heavy) |
| 3 | Providing/supplying and fitting of G.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16). The flanges shall be double welded both from inside and outside of the pipe using standard electrode of reputed make.Flanges (as per IS 6392/1997 Table:17) Thickness shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using reputed make electrodes to form strong welding joint.Welding Electrode: DC Arc Welding using welding electrode having diameter not less than 4mm.Nuts and Bolts: Nuts and Bolts (conforming to IS:1363 Part 1st)Rubber Insertion Gaskets: Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The rising main is to be laid as per the instructions of the engineer in charge and site requirement.Size : DN 80 mm Class: C (Heavy) |
| 4 | Earth work in excavation by mechanical means in trenches for foundation, drains, pipes, cables (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and reaming of bottom lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed.in all kinds of soil - 01 meter from cutting edge |
| 5 | Filling available excavated earth in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth,consolidating each deposited layer by reaming and watering, lead upto 50 m and lift upto 1.5m. |
| 6 | Providing and laying of stone soling including manual compaction . |
| 7 | Centering and shuttering including strutting, propping etc. and removal of form work for:Foundation, footings, bases for columns. |
| 8 | Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering, all work upto plinth level with 1: 2 : 4 mix (1 cement , 2 coarse sand , 4 graded stone aggregate 20 mmnominal size). |
| 9 | Fabrication, providing and fitting of long radius 90-120 degree bend/elbow to be fabricated out of G.I pipe, 1 m length and flanged on both ends a to make it leak proof. The flanges shall be M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) and welded on both sides. The job includes nuts, bolts, gaskets etc as per site requirement.Size : DN 80Class: C |
| 10 | Cutting of hot dip galvanized G.I, pipe across the section by dint of pipe cutter/ gas cutter. The job also includes Providing and welding of M.S flanges to the two ends of pipe. The Thickness of flange shall conform to IS 6392 Part 1st Table-17. The flange welding shall be carried out in double layers using Advani/Esab/L&T- SS Bond make electrodes to form strong welding joint by dint of DC arc welding. The job further includes Providing and Fitting of nuts and bolts (conforming to IS:1363 Part 1st) and Rubber Insertion Gaskets (conforming to IS: 638/79) to be used between flanged joints. The size of the pipe is given below:DN 80, Class-C. |
| 11 | Fabrication, providing and fitting of washout Tee with arm length 1.2 feet each. The Tee shall be fabricated out of G.I pipe with M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) fastened with weld joints on three ends. Size: 80 mm Class: C class |
| 12 | Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts.Size: 80 mm. |
| 13 | Providing and fitting of Ductile Iron double flanged, non- rising spindle soft seated glandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units.The body and bonnet of the valve shall be of ductile iron, wedge with fully vulcanized EPDM rubber (Approved for drinking water) and NBR seal. The Gate/Sluice valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positionsIt shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve. The valve shall be supplied along with hand wheel.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 Nos. M.S flanges perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with rising main of the pumping unit at appropriate spots as per site requirement.Size: DN 80 PN: 1.6/16 |
| 14 | Providing and fitting of Ductile Iron double flanged, Slanted seat swing check valve( NRV) as per IS 5312. The body shallbe of ductile cast iron with fully encapsulated vulcanized EPDM rubber (Approved for drinking water). The valve shall be compatible for buried applications and shall be safe to install in both horizontal and vertical positions.It shall have electrostatic epoxy coating (approved for drinking water) both inside and outside of the valve.Cost on account of Nuts, bolts, gaskets, etc required for the job is included in the scope of work.The job includes providing and fitting of 02 nos. M.S flanges (Table flanges) perfectly adaptable to the inbuilt flanges of the valve which shall be fitted with Rising main of the pumping unit at appropriate spots as per site requirement. The job includes the cost on account of P/F of nuts, bolts and gasket required for the job.Size DN-100 , PN-1.6/16 |
| 15 | Providing, installation and testing of manual type triple spur gear chain pulley block along with monorail geared travelling trolley having following features.Gears: - The hoist shall have precision machine case Hardened alloy steel gear mounted on bearings and housed in a dust proof gear box. The lubrication of gears should be of high viscosity and temperature for longer life of gears.Load Chain: - The load chain be made of high tensile alloy steel having wear resistance and greatest mobility. The chain should be accurately collaborated, tested and have adequate in built factor of safety for safer operation.Load chain wheel:- the load chain well should be double ball bearing supported and Specially designed, perfectly machined wheel providing correct grip of load chain to makes the hoist most safe and reliable against any failure. The main specifications of C.P Block are given below:Make = Reputed make No. of load chain falls = 2 or above Min. Height of lift = 6 M Capacity = 3 ton |
| 16 | Fabrication of gantry mechanism , sanitry protection of production well etc. by way of providing Structural steel in built up sections , trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer all complete welded |
| 17 | Providing, fitting, testing and commissioning of 30 KVA voltage stabilizer as per specifications below:Type of voltage controller: Manually operated copper wound, 3-phase, AC power supply multi step.Type of Regulator : Double plate type with electrolytic copper contacts.Input voltage : 250-400 volts.(3 phase) Output voltage : 415 ±10% volts.Frequency : 50 ±3 C/S.Windings : Electrolytic grade copper of adequate section, vacuum impregnated and Oven-dried.Insulation : Fiber glass insulations to tested parameters. Cooling : Naturally, Oil cooledTemp. Rise (Max) : 30°C above ambient Mounting : On Uni-directional wheels. Correction rate : 30 volts per stepWave form distortion : virtually nil Duty cycle : 100% continuous.Enclosure : MS sheet enclosure in pressed CGR Sheet powder coated with suitable type of radiators.Core laminates : High grade, low eddy loss, grain oriented silicon steel laminations.Load : Three phase induction motor load. Load Amperes (continuous)Overload in 24-hours operation: 10% above continuous Ampere rating.The voltage stabilizer shall have T-oil level indicator gauge preferably glass type tube or otherwise visible to naked eye. The top of the container to have a display panel for housing 02 numbers Digital voltmeters (0-500V) along with 4-way selector switch and set of neon indicators for incoming and outgoing phases (06 No’s).Insulating media (T. Oil) of 11 KVA grade to be provided and filled up to top level, with dielectric strength of 5 KV at 4m air gap. The T-Oil of specific grade should be provided in separate barrels and filled at site up to top level.The voltage Stabilizer shall be accepted with manufacturers dully stamped test certificate and shall have name plate withspecifications. |
| 18 | Providing and fitting of 3-Core flat submersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964 for Submersible Pumping Unit and other electrical equipment. The cable connections terminal shall be fitted with copper thimbles of required size.Size : 10 sqmm Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jun 30, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 09, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysJul 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 days