| 1 | Survey, Supply, Installation , Testing and Commissioning for 33 kV Line BAY (LILO) of existing Chenani Line at proposed Receing Station Kulwanta |
| 2 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves, Electricfield or Equvalent . |
| 3 | 33kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 4 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 5 | 33 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase |
| 6 | 30 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less |
| 7 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 8 | 33 KV Potential transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase |
| 9 | 33 kV Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m station type |
| 10 | CONTROL CABLES : i) 12 Core 2.5mm2 control cable multistrand copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. a |
| 11 | ii) 4 Core 2.5mm2 control cable multistrand copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 12 | iii) 2 Core 2.5mm2 control cable multistrand copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 13 | Galvanised Steel Structures |
| 14 | Galvanised Nuts & Bolts |
| 15 | 33 KV yard concreting and metalling providing supply and laying 100 mm thick PCC1:4:8 using 20 mm normal course aggregating and spreading 100 mm three layer of 20 mm single size crushed / broken stone (One Line Bay) |
| 16 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay) |
| 17 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 18 | Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering |
| 19 | Survey, Supply, Installation , Testing and Commissioning for TRANSFORMER BAY at proposed Receiving Station Kulwanta |
| 20 | 33kV VCB (36KV,1250 A,26.2 KA, outdoor type Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 21 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 22 | 33KV Current Transformer (CTR 250/125-5A,1- phase multi-core, outdoor,1No. Per phase) on along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards. |
| 23 | 33 KV Potential transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase |
| 24 | 33 kV Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m |
| 25 | 33KV Lightening Arrestors(33 KV 10 KA Polymer, ZnO, Gapless) |
| 26 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA) along with fabricatioon ,laying MS Gantry includuing Civil foundation works etc as per REC standards. |
| 27 | 12 Core 2.5mm2 control cable multistrand copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc. |
| 28 | 4 Core 2.5mm2 control cable copper multistrand armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab, KEI etc. |
| 29 | 2 core 2.5mm2 Control Cable copper multistrand Armoured, 1.1KV Grade, ISI, FRLS of make Havells, Polycab, KEI etc. |
| 30 | Galvanised Steel Structures |
| 31 | Galvanised Nuts & Bolts |
| 32 | Providing & Fixing of of BusBar System with 200 sqmm A.C.S.R.Panther Conductor,including Aluminium tension/suspension fitting suitable for Panther Conductor,T Clamps/P.G.Clamps/P.I. Clamps./C.T. Clamps/Isolator Clamps/PT Clamps etc complete job (One No Line Bay+ One No Transformer Bay) |
| 33 | Providing of Lightening Protection System with Earthwire (7/4 sqmm) & allied Earthwire Tension Clamps.The Peak Tower shall be connected with independent raiser of G.I. Flat 25mm x 3 mm connected with main earth mat. |
| 34 | Providing & Welding of Raisers with G.I. Flat of Size 50 mm x 6 mm.Each Equipment structure shall be provided with two raisers connected with Earthmat.The Details of Raisers shall be finalised by Engineer Incharge in detailed engineering |
| 35 | SITC of POWER TRANSFORMER (6.3 MVA) |
| 36 | 33/11kV, 3 phase ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections (6.3 MVA) as per latest IS Standards |
| 37 | 12 Core 2.5mm2 control cable multistrand copper armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 38 | 6 Core 2.5mm2 control cable copper multistrand armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 39 | 2 Core 2.5mm2 control cable copper multistrand armoured, 1.1KV Grade ISI,FRLS of make Havells, Polycab,etc. |
| 40 | SITC of 11 kV INDOOR SWITCHGEAR OF 33/11 kV SUBSTATION |
| 41 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal, or equivalent :- For 6.3 MVA Power Transformer (1+5) including Smart meters Trivector. |
| 42 | 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (5 Sets Station type 1 for Power Tx)) |
| 43 | 11 kV 3- Core XLPE 185 mm² armoured, FRLS |
| 44 | 11 kV 3- Core XLPE 400 mm² armoured, FRLS |
| 45 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core(Indoor) |
| 46 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 185 sqmm single core (outdoor ) |
| 47 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (indoor) |
| 48 | 11 kV Indoor Heat Shrinkable Cable Termination Kits for 400 sq mm Cable (outdoor) |
| 49 | 11 kV Isolator, double break,3-pole, 600Amp, horizental mounting Type, with Earth Switch. |
| 50 | 11kV DO set , AB Switch 3-Phase, 3-Pole, 200 Amp |
| 51 | Galvanised iron of sorts |
| 52 | 09 Mtr. Long Pole(ST-410 SP33) |
| 53 | 95 mm² PVC LT Cable 4 Core, armoured, FRLS |
| 54 | Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole |
| 55 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI strip for ST poles |
| 56 | 33KV/440V 100 KVA Auxillary Transformer Level II |
| 57 | Earthing for 33KV/440V Auxillary Transformer (complete as per REC standards) |
| 58 | MCCB 200 Amp with box |
| 59 | COMMON MISCELLENOUS WORKS |
| 60 | HDPE Pipe Outer Dia 180 mm Inner Dia 152 mm for laying of 11kV XLPE Cable from Power Transformer to Control Room |
| 61 | Providing & Laying of Earthmat by Using G.I. Flat of Size 50 mm x 8mm as grounding Conductor.The mesh Size shall 2 m x 2 m.The Burial Depth of G.I. Flat Shall be minimum 600 mm.The work involves the excavation of trenches for burial of grounding flat,Laying of G.I.Flat including welding & Backfilling of Trenches (840 RM) |
| 62 | Earthing Electrode ( 3m long 40mm dia GI pipe) through GI Strip. |
| 63 | Supply, Errection, Testing & commisioning of Battery Bank 32v 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant of make Exide Amaron or Tata etc. |
| 64 | Supply, Errection, Testing & commisioning of Float-Cum-boost Charger with full wave rectification for 220v, 1 Phase 50HZ AC input supply suitable for charging of Battery Bank 32V, 100AH of 15+1 No. cells of 2V each, sealed maintenance free VRLA type, Hgh Impact Polyprophelene copolymer container flame retardant. |
| 65 | Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories |
| 66 | Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A),Rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories |
| 67 | Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room (with ISI mark) |
| 68 | 3 Sand Bucket Fire Extingiusher including MS stand |
| 69 | Civil /Misc Works |
| 70 | Earth work in bulk excavation by mechanical means (hydraulic excavator) over areas(exceeding 30 cm in depth, 1.5 m in width as well as 10 m2 on plan) includingndisposal of excavated earth lead upto 50 meters and lift upto 1.5 m, as directed by Engineer-in-Charge.80% All kinds of soil + 20% Oridnary rock |
| 71 | Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts,struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchors blocks, plain window sills, fillets etcupto floor V level, including curing , the cost of centring, shuttering and finishing with.1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 72 | Construction of crated walls by way of filing of stones and making kneeted wire crates of mesh size 100 mm by 100 mm (6x1.2 x1.2) m3 including weaving, binding sides and partitions and binding top after filling of stones including cost of filling, stones and weaving GI material |
| 73 | Repair of exisiting path / approach road for carriage of various equipments / Power Transformer at proposed receiving station Kulwanta |
| 74 | Providing and fixing on wall face un-plasticized Rigid PVC rain water pipes 110 mm dia for weep holes |
| 75 | Laying of Interlocking tiles M 40 grade cement tiles(125 mm thick) after providing and laying of cement concrete of specified grade below tiles and band for locking of tiles as per the direction of site engineer at R/Stn Battal |
| 76 | Development of Side drains of road 300 mm x 300 mm section with side walls & floor 150 thick P.C.C. 1:3:6 & 12 mm thk plaster 1:4 complete finished job |
| 77 | Ornamental Landscapping of Free land/space along with Plantation of ornamental trees & Grass complete job to the satisfaction of engineer in charge |
| 78 | Compound Walling of identified land by way of Mass Concrete in Foundations and 228 mm bricks of 2 metre height and plastering |
| 79 | Galvanized Chain link Fencing of 33 kV Yard of Substation by way of Mass Concrete in Foundations and chain link fencing of 6 ft height (Size 75 mm x 75 mm made of G.I.Wire 3.15 mm in diamond pattern) using Fencing posts of M.S.angle size 65x65x6mm embedded in 1:2:4 C.C. Block of Size 400 mm x 400 mm x1000m at an average spacing of 2.5 m c/c.The chain Link mesh fencing shall be secured to M.S.Angle post with flat iron strip of size 50x6 mm on both sides.There shall be a provision of 3 rows of 2 strand Barbed wire on top of fencing post. at KUlwanta Receiving Station. |
| 80 | Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required-In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.(As per direction of site incharge) |
| 81 | Construction of R.C.C. Pillars for holding of gate including cost of material & labour.(Design of Reinforcement & sizing shall be finalised by Enginer incharge |
| 82 | RCC Cable trench (1:2:4) including excavation and disposal of un-wanted soil. for laying of 11 KV XLPE Power Cable and control cable from power transformer, VCB and other equipments to control room and for outgoing cables from control room to outgoing structures including cable duct covers (cable duct covers should be covered with Angle Frames using angle 45x45x5 mm and 8 mm Tar Steel @ 200 c/c & M-20 Concrete) |
| 83 | BUILDING: A. Control Room Building on ground floor complete with Column, beam structure and plinth protection with 1 no J.E. Room , 1 Store room, 1 Battery Room and a main hall including aluminium windows, cable ducts for power and control cable, Toilet (complete with WC, Washbasin and fittings), electric fittings (fans, LED tubelights, leds powerpoints and other fixtures of Make Havells,Anchor,RR,Philips) Painting/white washing of entire control room building by way of applying white putty 1 mm thick 2 coat, sand papering preparing the surface smooth,distempering including primer and finishing with emulsion paint 2 coat (Nerolac/Asian) brand , painting of doors and windows etc. Overhead (2Nos. 1000Ltr)/undergroung water Storage tanks (10000 ltr) . 2 nos of office tables (2'6\\"x5') and 2 nos of office chairs and 6 Nos of Plastic chairs , staircase . Water Supply . Septic Tank (10'x10'x8') complete with Sanitary Fittings including kota stone floor .complete in all respects |
| 84 | BUILDING:B .Staff Quarters on 1st floor with Column and Beam structures including Toilet (complete with WC, Washbasin and fittings), electric fittings(fans, LED tubelights, leds powerpoints and other fixtures) Painting/white washing of entire control room building by way of applying white putty 1 mm thick 2 coat, sand papering preparing the surface smooth,distempering including primer and finishing with emulsion paint 2 coat (Nerolac/Asian) brand Complete in all respect painting of doors and windows etc. Overhead water Storage tanks . Pantry Room with all the Fittings. Water Supply,Furniture(including 2 single Beds, 4 Chairs, 2 table, Matress, Curtains) including Double Vitrified flooring tiles (Kajaria, Somany, Johnsons) complete in all respects(Note: The Contractor shall submit the building drawing in all respects i.e. structural / architectural prepared by authorised Architect for approval from the dept for execution of works.) |
| 85 | 33/11 kV Power Transformer Foundation as per REC standards |
| 86 | Auxillary Transformer Foundation as per REC standards |
| 87 | 33 kV Equipment Foundation & Gantry foundation as per REC standards (for LILO and Power Transformer Bay) |
| 88 | 33 KV Yard Concreting with 1: 4 :8 with 20 mm nominal stone aggregate 4 inch thick & RCC 1 :2 :4 with 20 mm nominal stone aggregate 4 \\" thick. |
| 89 | 33 kV Yard Lighting ( 4 nos of 100 Wt LEDs, 11 mtr ST poles with Ring on top) complete with earthing , cement bottoming GI brackets, control box , cable etc with centrally controlled Switch. 4 nos. for R/Stn (R/Stn Kulwanta) |
| 90 | safety tool kit |
| 91 | Crimping Tool Kit complete set for cable of different sizes upto 630 sqmm |
| 92 | Rubber Mats( 2 mtr x 2 mtr x 25 mm) |
| 93 | Providing and Fixing of CCTV cameras 6 nos with specifications IP camera 4 MP IR 30 mtr range with 8 channel NVR, POE switch , Hard Disc 4 TB, Fibre / Outdoor CAT6 whichever is required as per site conditions and LED Monitor 32 inch, Wifi /airfiber with 2 Years subscription and connection with all allied accessories like media convetrors, supporting wire, 4U Rack etc and electric connections at sites as required. |
| 94 | Conventional Earthing -GI Plate Earthing with 600mm X 600 mm X 6 mm, GI Plate, GI Flat 50 x 6 mm, GI Pipe, 40 mm Dia with Charcoal salt & good earth 10 ft deep pit etc. as per REC standards . Complete job |
| 95 | 33 KV Hand Gloves(set of 2) |
| 96 | 11 KV Hand Gloves(set of 2) |
| 97 | RainCoats |
| 98 | Safety Belt |
| 99 | Gum boots |
| 100 | Safety Helmet for electrician |
| 101 | Digital Meggar 5000 mega Ohm |
| 102 | Earth Resistance Tester |
| 103 | Emergency light/ Torch 5 Watt chargeable |
| 104 | Multimeter |
| 105 | 33KV high voltage live phase detector |
| 106 | Extendable Aluminium Ladder 25 feet |
| 107 | Aluminium Bus Bar 75 x 10 mm |
| 108 | GI Flat 50 x 6 mm and 20 x 5 mm for risers and earthing of cable trenches and yard fencing. |
| 109 | Earthing Rod (set of 3) |
| 110 | Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 33 kV LINE ON 11 and 13 METER ST POLES |
| 111 | Supply, Transportation, Erection of 11 Mtr Long ST Poles (ST410-SP56) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 112 | Supply, Transportation, Erection of 13 Mtr Long ST Poles (ST410-SP69) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 113 | GI Channel iron X-arm of size 100*50*6 and GI angle iron brace of size 65*65*6 mm of different sorts including clamps,Ties and braces for multi pole structures |
| 114 | 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 115 | 33kV Polymeric composite Disc Insulator with fitting 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm |
| 116 | PG clamps for 150 mm2 ACSR Conductor |
| 117 | Galvinized Nuts and Bolts of sorts |
| 118 | Danger Plates with Clamps |
| 119 | Anti-Climbing Device with Clamps |
| 120 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 121 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 122 | Cement bottoming 1:2:4 mix as per REC standards .6cum/pole (to be done during erection of poles) including 5 No existing Poles |
| 123 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete |
| 124 | 100 mm2 ACSR conductor |
| 125 | Guard netting |
| 126 | Creation of Isolation points along existing / new line by way of 33 KV Isolators without earthing blades on ST 11 Mtr Poles double Pole Structure and MS Steel etc. Complete job. |
| 127 | Survey, Supply, Installation , Testing and Commissioning for ERECTION OF 11 kV LINE ON 9 METER ST POLES (8 ckt KM approx) to be vetted by AEE Electric Sub-Division Ramnagar |
| 128 | Supply, Transportation, Erection of 9 Mtr Long ST Poles (ST410-SP33) including excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 129 | GI Channel iron X-arm of different sizes including clamps,Ties and braces |
| 130 | 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 131 | 11V Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 132 | PG clamps for 50 mm2 ACSR Conductor |
| 133 | Galvinized Nuts and Bolts |
| 134 | Danger Plates with Clamps |
| 135 | Anti-Climbing Device with Clamps |
| 136 | Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI Strip. |
| 137 | Painting of Poles with Red Oxide and aluminium paint (min 2 coats each) |
| 138 | Cement bottoming 1:2:4 mix as per REC standards .45cum/pole (to be done during erection of poles) |
| 139 | Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 140 | 30 mm2 ACSR conductor |
| 141 | Guard netting |
| 142 | Creation of Isolation points along the line Complete job. |
| 143 | Survey, Supply, Installation , Testing and Commissioning for Improvement of Existing 33/11 KV R/Stns Running on 33 KV Ramnagar Line) |
| 144 | 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) SCADA compatible Make Megawin, Crompton Greaves, Electricfield or Equvalent . |
| 145 | 33kv Isolator with Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 146 | 33kv Isolator without Earthing Blade (36kv , 1250A,outdoor,3 poles, 25KA ). |
| 147 | 33 kV Current transformer (33kv,1 phase multi ratio multi core, outdoor) 1 no per phase |
| 148 | 30 kv Lightening arrestors (30kv,10KA, Polymer, station class, ZnO)gap less |
| 149 | 33 kV C&R Panel along with O/C, E/F and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible.Make Megawin, Crompton Greaves Pascal, Stelmec, Yamuna ,etc . |
| 150 | 33 KV Potential transformer(33kv/110 V, 1 phase, multicore, outdoor)1 no per phase |
| 151 | Providing and fixing of 1.5 Ton 5-star Split Inverter AC 2026 Model (make Diakin,O-General) with stablizer for R/Stn Kulwanta |
| 152 | Providing 1 No 11\\" Ipad Pro 512 GB Wifi+ Cellular M4 Chip for monitoring the activities of Sub Stations |
| 153 | Providing 1 No Photocopier Machine ir2224n with duplex and ADF for Sub Stations |
| 154 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Electric Field :- For 3.15 MVA Power Transformer at Majouri including Smart meters Trivector. |
| 155 | 11 kV VCB Panel Board Set (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port SCADA Compatible etc MAKE :- Seimens, Megawin, Pascal, or Stelmac :- For 3.15 MVA Power Transformer at Basantgarh (1+5) including Smart meters Trivector. |
| 156 | OUTSOURCING of Manpower for Manning/Operation of proposed R/stn. For 02 years 07. nos Skilled staff Please Enable Macros to View BoQ information Compatibility Report for DhunaBOQ.xls Run on 10-07-2021 14:05 The following features in this workbook are not supported by earlier versions of Excel. These features may be lost or degraded when you save this workbook in an earlier file format. Significant loss of functionality # of occurrences This workbook contains data in cells outside of the row and column limit of the selected file format. Data beyond 256 (IV) columns by 65,536 rows will not be saved. Formula references to data in this region will return a #REF! error. 6.0 'BoQ1'!L40 'BoQ1'!F40 Any effects on this object will be removed. Any text that overflows the boundaries of this graphic will appear clipped. 3.0 'BoQ1'!A1:II42 Minor loss of fidelity Some formulas in this workbook are linked to other workbooks that are closed. When these formulas are recalculated in earlier versions of Excel without opening the linked workbooks, characters beyond the 255-character limit cannot be returned. 5Defined Names Some cells or styles in this workbook contain formatting that is not supported by the selected file format. These formats will be converted to the closest format available. 14.0 |