Tender For Repair/Replacement Of Earthing Alongwith Connected Works At Hq Cif (R ) And Signal Regt Under Age(I) Cif (R ).
Tender Value
9 Lakhs
Estimated cost
Bid Submission
18 Jul 2026
17 days left
EMD
18000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Rajouri → Jammu and Kashmir
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Replacement Of Earthing Alongwith Connected Works At Hq Cif (R ) And Signal Regt Under Age(I) Cif (R ).
BOQ
| Sl. No. | Item Description |
| 1 | M&L for Earthing complete with galvanised steel earth plate electrode 600×600×6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point including necessary excavatioon for earth pit and PCC earth chamber with RCC pit cover complete all as specified or indicated including testing on completion. |
| 2 | M&L for Earthing complete with galvanised steel earth plate electrode 600×600×6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point including necessary excavatioon for earth pit and PCC earth chamber with RCC pit cover complete all as specified or indicated including testing on completion. |
| 3 | M&L for Earthing complete with galvanised steel earth plate electrode 600×600×6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4.0 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point including necessary excavatioon for earth pit and PCC earth chamber with RCC pit cover complete all as specified or indicated including testing on completion. |
| 4 | All as per item No. 2 above but for Earthing of machinery/ equipment installed at power house/substation, using 25 x 3 mm copper strip and copper plate of size 600×600×3.15 mm, as earth electrode. |
| 5 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/ pipe or any other indicated situation for loop earthing etc. as required 20x3 mm copper strip complete all as specified. |
| 6 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/ pipe or any other indicated situation for loop earthing etc. as required 32x6 mm GI strip complete all as specified. |
| 7 | S&F Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/ pipe or any other indicated situation for loop earthing etc. as required 25x4 mm GI strip complete all as specified. |
| 8 | S&F Earth continuity conductor or main earthing wire fixed to wall or batten or recess or chases or burried in ground or drawn in coduit/ pipe or any other indicated situation for loop earthing etc. as required 4 mm GI wire complete all as specified. |
| 9 | Supply and fixing in replacement of Air termination, single pointed aluminium rod 12 mm dia and 300 mm long complete all as specifed and directed complete. |
| 10 | Supply and fixing in replacement Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 Nos. 8 mm dia 25 mm long hex. head screw |
| 11 | Supply and fixing in replacement of Aluminium strip 25 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified and directed. |
| 12 | S&F PVC insulated multistranded copper conductor 1 x 16 sqmm as Earth continuity conductor or main earthing lead fixed to wall or batten or recess or chases or burried in ground or drawn including fixing materials like copper thimbles, saddles and screws in rigid PVC coduit/ pipe 20 mm dia or any other indicated situation for loop earthing etc. as required complete all as specified. Note : PVC rigid conduit shall be measured and paid under relevent item. |
| 13 | Supply and Fixing of sheet metal enclosure, SPN type with two pin & earth plug and socket (Industrial type DB) with and including one MCB SP, C Curve type of capacity 20 Amp, 10 kA complete all as specified and directed. |
| 14 | Supply and Fixing of 2 Way sheet metal enclosure with MCB SPN 6 Amps 6 kA, 'B' type, complete including fixing arrangement to PCC /steel tubular pole any type all as specified and directed. |
| 15 | M&L of Wiring for circuit/submain wiring alongwith earth wire of FRLSH PVC insulated copper conductor,single core cable in surface/recessed of size 2X6.0 Sqmm and 1X6.0 Sqmm earth wire including suitable size of PVC conduit concealed/casing caping and lugs/thimbles with nuts, bollts and washers etc complete. |
| 16 | M&L of Wiring for circuit/submain wiring alongwith earth wire of FRLSH PVC insulated copper conductor,single core cable in surface/recessed of size 2X4.0 Sqmm and 1X4.0 Sqmm earth wire including suitable size of PVC conduit concealed/casing caping and lugs/thimbles with nuts, bollts and washers etc complete. |
| 17 | M&L in replecement of Wiring for circuit/submain wiring for industrial socket alongwith earth wire of FRLSH PVC insulated copper conductor,single core cable in surface/recessed of size 2X2.5 Sqmm and 1X2.5 Sqmm earth wire including suitable size of PVC conduit concealed/casing caping and lugs/thimbles with nuts, bollts and washers etc complete |
| 18 | Supply and laying in replacement of GI pipe medium grade in replecement of 50 mm dia laid in trenches for protection of UG cable complete |
| 19 | Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles (SP) and current carrying capacity 5 to 32 AMP, in the MCB DB/Junction box etc. complete with connection testingcomplete all as specified. |
| 20 | Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles & neutral (SPN) and current carrying capacity 40 AMP, in the MCB DB/ Junction box complete with connection testingcomplete all as specified. |
| 21 | Supply and fixing 240V, 10 KA 'C' curve miniature circuit breaker (MCB) of single poles & neutral (SPN) and current carrying capacity 63 AMP, in the MCB DB/ Junction box complete with connection testingcomplete all as specified. |
| 22 | Excavation in tranches in hard/dense soil not exceeding 1.5m depth not exceeding 1.5m in width over energised LT cables for carrying out brick work for preparation of cable duct including for taking out and relaying of LT Cables in hard standing surfaces ,Road cutting etc complete all as specified and as directed. |
| 23 | Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm in any type of soil. |
| 24 | Removing surplus excavated materials to a distance n.exc 50m and depositing where directed at a level n exc 1.5 m above the starting point. |
| 25 | M & L for PCC (1:3:6) type C1 using 20 mm graded stone aggregate for foundation of pole around pole all as specified and as directed by Engineer-in-Charge. |
| 26 | M&L for fixing in replacement of Earthing Pit cover readymade, PCC with cover complete suitable for existing earthing pit size as per site requirement including funnel including necessay brick masonary & plaster work complete all as directed by engr-in-charge. |
| 27 | Supply & fix Rigid non-metallic PVC conduit 32 mm exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. |
| 28 | All as per item No. 27 above but Rigid non-metallic PVC conduit 25 mm. |
| 29 | All as per item No. 27 above but Rigid non-metallic PVC conduit 20 mm. |
| 30 | Supply & fix in replacement of PVC flexible Spiral pipe 32 mm dia complete |
| 31 | All as per item No. 30 above but PVC flexible Spiral pipe 20 mm dia . |
| 32 | Deduction to be made from BOQ for schedule of credit (Sch 'A' Part - II) Amount of ₹ 26630.00 during AOCNote:- Tenderers shall not quote for this Schedule Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Jun 27, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedJul 18, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysJul 25, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 days