| 1 | Excavation in trenches n. exc 1.5 m in depth and not exc 1.5 m wide for foundation or pole or laying of cable and getting out in hard/dense soil complate all as specified. |
| 2 | Returning & filling , including spreading, leveling, watering and well ramming of hard and dense soil in layers not exc. 25cm complete all as specified. |
| 3 | Removing excavated material /deberies n..exc 50m and depositing where directed at a level n. exc 1.5 above the starting point all as specified. |
| 4 | Supply and lay double walled corrugated DWC HDPE pipe 63 mm bore as per IS-16205 and including couplers and bend for cable protection laid in trenches complete all as specified and directed.Make : TELEREX 450N/ Rex Polyextrusion Ltd/ Finolex/ Prince Pipes and fittings ltd/Kisan/Supreme/JAIN IRRIGATION SYS/ Astral |
| 5 | Supply and lay double wall corrugated DWC HDPE pipe 40 mm bore, as per IS-16205 and including couplers and bend for cable protection laid in trenches complete all as specified and directed.Make : TELEREX 450N/ Rex Polyextrusion Ltd/ Finolex/ Prince Pipes and fittings ltd/Kisan/Supreme/JAIN IRRIGATION SYS/ Astral |
| 6 | Supply & laying, connecting and commissioning of LT under ground cable 1100 volts grade XLPE insulated armoured heavy duty electric cables with aluminium conductor of size 50 Sqmm x 3.5 core including connecting with suitable size of cable glands lugs etc. laid in trenches or fixed on walls including taking out old Unserviceable cable complete all as specified and directed.Note: Excavation and earth work, DWC HDPE pipe and GI protection pipe will be measured and paid separetely. Make: Cable Corporation of India (CCI)/ Asian Cable Co, Chattisgarh/ Finolex/ Polycab/ Gloster/Universal/ RPG Cables Ltd , Thane/ Havells India Ltd/ RR Kabel/ KEI Industries Ltd(KEI) |
| 7 | -do- same as Item no. 6 above but of size 70 Sqmm 3.5 Core |
| 8 | -do- same as Item no. 6 above but of size 120 Sqmm 3.5 Core |
| 9 | -do- same as Item no. 6 above but of size 25 Sqmm 3.5 Core |
| 10 | -do- same as Item no. 6 above but of size 16 Sqmm 4 Core |
| 11 | -do- same as Item no. 6 above but of size 10 Sqmm 2 Core |
| 12 | -do- same as Item no. 6 above but of size 10 Sqmm 4 Core |
| 13 | Material & Labour for earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the earth plate not less than 1.5M below normal GL, connected with galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with CI cover 10mm thick plate fixed to angle iron frame work and 15 mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, 20 kg of benjonit powder, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I, 2009 specification. |
| 14 | All as item No 13 above but strip 32 x 6 mm as earthing lead -ditto- |
| 15 | Supply & Fix GI strip 32X6 mm buried in ground/on wall, extension of existing earthing lead all as per specified and directed by Engr - in - charge. |
| 16 | Material & Labour for cutting the existing bituminous road/hard standing to size not exceeding 45cm wide and depth not less than 45 cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200mm thickness with plain cement concrete type C1 1:3:6 using 20mm graded stone aggregates complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply & Fix GI Tubing Medium grade 80mm dia for protection of cable on wall , road crossing all as spd and directed by Engineer in charge.Make: Tata / Jindal / Surya Prakash / Zenith |
| 18 | Material & Labour for painting the old Main LT panel board including scrapping and removing the old painted surfaces and painting /matching the same colour paint with two coats of super enameled paint ( Smoke grey) and without distrubing the existing electric system all as specified and directed by Engineer-in-Charge.Make : Asian Paints/ Nerolac Paints/ Dulux ( Akzonobel)/ Nippon Paint India Pvt Ltd/Birla Opus Paint |
| 19 | Material & Labour for labour for welding broken doors of LT Panel (front and rear door) including replacing the required new hinges, nuts and bolts, locking arrangement and refixing the covers without disturbing the existing electric system complete all as specified and directed by Engr-in-charge. |
| 20 | Material & Labour for undusting & cleaning of feeder pillars & LT panel with dry, lint-free cloth or a soft brush to eliminate dust, dirt, and debris from the panel's surface externally & internally comaprtment wise along with replacing of any unservceable MCCB/ Lugs/ Cables, refixing loose wires/ cables, redistrbution of load for balanced distribution, including cleaning of vegatation/plants around Feeder pillars and writing respective Fedderpillar Numbers,complete all as specified and directed by engineer Incharge.Note : MCCB/ Timer/ Cables will be paid and measured seperately. |
| 21 | Supply & Fix in repair DB vertical type 4 way TPN in repair, double door load line powder coated complete alongwith suitable size and capaciy of busbar fixed on wall duly grouted in solid block wall or on wooden board,including MCB TPN 100 Amps incoming and 12 Nos of MCB SP of 40 Amp outgoing with lugs/thimbles duly crimped for connection with all necessary fixing arrangement complete all as specified and directed. Make : Havells / Legrand / Schneider / MDS sample as approved by GE. |
| 22 | Supply and fix in repairs of voltmeter, 0 to 500 Volts, AC, suitable for three phase, digital type all as directed. Make: AE/Schneider/L&T |
| 23 | Supply and fix in repairs of Ammeter, digital type, 0-300 Amps, AC CT operated, suitable for three phase all as directed. Make: AE/Schneider/L&T |
| 24 | Supply & Fix outdoor 1.1 KV LT XLPE cable Heat Shrink straight through jointing kit of cable size upto 95 Sqmm including cable finding cable fault complete all as specified and as directed by Engineer-In-Charge.Make: Densons/ M Seal/ Raychem/ Siemens / Birla 3M/ Mahindra & Mahindra |
| 25 | Supply & Fix outdoor 1.1 KV LT XLPE cable Heat Shrink straight through jointing kit of cable size 120- 185 Sqmm including cable finding cable fault complete all as specified and as directed by Engineer-In-Charge.Make: Densons/ M Seal/ Raychem/ Siemens / Birla 3M/ Mahindra & Mahindra |
| 26 | Supply and fix Decorative pole, single arm with LED light Celesta 40W, warm white with automatic brightening, antiquely designed aesthetically appealing landscape cum street light, made from aluminium housing, clear polymer diffuser to provide uniform and pleasant light output & made from CRCA with decorative side arm compatible for LED post top range, plasma cut & mounting accessories 3.5 mtr height including necessary earth work and form work, cement concrete in foundation and coping of poles, fair finishing to exposed faces of concrete all as specified and as directed by Engr-in-charge. Make: Havells/WIPRO/BAJAJ/PHILIPS/ Shakti/Utkarsh as approved by GE Please Enable Macros to View BoQ information |
| 27 | Supply and fix Decorative pole, single arm with LED light Celesta 40W, warm white with automatic brightening, antiquely designed aesthetically appealing landscape cum street light, made from aluminium housing, clear polymer diffuser to provide uniform and pleasant light output & made from CRCA with decorative side arm compatible for LED post top range, plasma cut & mounting accessories 3.5 mtr height including necessary earth work and form work, cement concrete in foundation and coping of poles, fair finishing to exposed faces of concrete all as specified and as directed by Engr-in-charge. Make: Havells/WIPRO/BAJAJ/PHILIPS/ Shakti/Utkarsh as approved by GE Please Enable Macros to View BoQ information |