| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 2 | Medium point (up to 6 mtr.) |
| 3 | Long point (up to 10 mtr.) |
| 4 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 5 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 6 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 7 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 8 | Single pole MCB (With B / C curve tripping characteristics) |
| 9 | 6 A to 32 A rating |
| 10 | Double pole MCB (With B / C curve tripping characteristics) |
| 11 | 40 A rating |
| 12 | Four pole MCB (With B / C curve tripping characteristics) |
| 13 | 40 A rating |
| 14 | 50/63 A rating |
| 15 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 16 | 4 pole MCCB With Thermal Magnetic release |
| 17 | 125 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 18 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 19 | 63 mm |
| 20 | Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular/ Conical cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, The base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have hinged lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 for Octagonal & P-02 for Conical with base plate and foundation bolt on the Existing cement concrete foundation. To ensure quality of product it's entire manufacturing process starting from sheet cutting to galvanization sould be done under one premises. |
| 21 | Poles with Octagonal/Conical Cross Section |
| 22 | 9 Mtr. |
| 23 | Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap ( 250x 88.9 / 114.3 x 3.25 mm) over the existing poles. |
| 24 | Single arm overhang |
| 25 | Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles as per Drawing attach at Table P-05 with Following Procedure |
| 26 | A) Excavation of Pit for Foundation Size upto required depth from Ground level |
| 27 | B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. |
| 28 | C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness |
| 29 | D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. |
| 30 | E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal |
| 31 | F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. |
| 32 | G) Providing and Laying Reinforce cement Concrete of M-20 grade in Footing and Pedestal including Curing the foundation for minimum 7 days. |
| 33 | H) Providing and Fixing Nosing Angle 25 mm x 25 mm x 3mm with 2 no. of 100 mm long, 6 mm dia fastener |
| 34 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 35 | Supply and Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 36 | 1.5 Sq.mm 3 core flat / Round |
| 37 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing and secondary lens on each LED/ integrated lens diffuser without cover & should be High power LED of 3 to 5 watt each . The System efficacy >=135 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 38 | LED Street Light fixture with Minimum lumen output 8100 lm |
| 39 | SITC of Grid interactive Solar Photovoltaic Power Plant of required capacity having specifications as per A, B, C, D, E, F and G |
| 40 | A. Solar Photovoltaic module : MNRE approved and ALMM listed, SPV module of capacity 580 Wp or above, Anodized Aluminium Alloy Framed Topcon N- type Bifacial, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. , 2 mm Low Iron ARC semi-tempered glass, IP-68 PPL Junction box, 4.0 sq.mm cable with MC4 solar connector, conversion efficiency shall not be less than 21.0 % on STC, performance warranty for their output peak watt capacity > 90 % at the end of 10 years and > 80% at the end of 25 years. |
| 41 | 10 KWp |
| 42 | Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. |
| 43 | 25 mm |
| 44 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 45 | ADD 18%GST Please Enable Macros to View BoQ information |