| 1 | Supply and fixing ceiling fans (28-32 watt) complete with blades, copper winding ,down rods, regulator(5 step micro switch control ,voltage range 220-240 volt suitable for BLDC fan) and accessories, 230 V, 1200mm sweep. Min air delivery (210-240) CFM with service value greater than 6.5 BEE. Five star rated with brushless direct current motor (BLDC) including taking down of u/s fan and deposited to MES store yard complete all as specified and directed complete all as specified and directed etc all as specified and directed by EIC. |
| 2 | Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300mm sweep with,copper winding , 1380 RPM ,70 watt carbon powder coated body ,double ball bearing with bird guard , blades, and frame including taking down of u/s exhaust fan and deposited to MES store yardcomplete all as specified and directed etc complete all as specified and directed by EIC. |
| 3 | Supply and fix PVC body exhaust fan size 250mm sweep , 5/6 blades with built in auto matic gravity louvers ,220 volt AC , 30-45 watts power consumption , 1200 RPM , including taking down of u/s exhaust fan and deposited to MES store yardcomplete all as specified and directed complete all as specified and directed by EIC. |
| 4 | Supply and fixing wall mounted fan, 400mm sweep complete with all stanrad accessories ,oscillation 60 to 90 degree auto matic jerk free horizantol movement ,3 speed control with pull cords ,vertical tilt adjustment ,ABS plastic blade ,safty gaurd ,copper winding ,heavy duty air flow including taking down of old u/s wall fan any size and deposited to MES store yardcomplete all as specified and directed complete all as specified and directed by EIC. |
| 5 | Supply & Fix including taking down for replacement of 3 core PVC insulated and sheathed cable with copper conductor of size 40/0.076 complete all as specified. |
| 6 | M & L for complete point wiring with 1.5 Sqmm single core multi stranded copper conductor FRLSH insulated and unsheathed heavy duty cable in colour code including continuous earth wire with cable of size 1.5 sqmm copper conductor flexible FRLSH insulated drawn in and including concealed PVC rigid conduit medium grade ISI marked after cutting chases in wall , plastering after concealing conduit , including modular galvanised flush boxes of suitable size and white cover plate with frame as per relevant IS for mounting modular switches, sockets, fan regulators etc and including making good the disturbed surface as per existing complete all as specified and as directed by Engr In Charge for the following :- |
| 7 | S&F ceiling rose 6 amp, 3 phase polycarbonate body 240 volts ISI marked complete all as specified and directedcomplete. |
| 8 | S&F in repair of Modular switch 1 module 6A,1 module , with gang box I module 240 volts ISI marked complete all as specified and directed |
| 9 | Material & labour for earthing complete with galvanised steel copper plate electrode 600x600x3.15 mm thick burried directly in ground. ( earth pit not less than 2.25 mtr depth below ground level at any type of strata ) with top edge of the earth plate not less than 1.5mtr below normal ground level connected by 4 mm solid copper wire with earth lead by means of brass nuts and bolt,thimbles check nuts, washers including concrete chamber of PCC 1:3:6 type C-1 using 20mm graded stone aggregate with fair finish, internal surface of concrete chamber shall be given internal dia 300mm x300mm, 15mm thick plaster in CM 1:4 funnel with wire mesh, RCC pit cover of 320x320x80mm size (1:2:4) Type B1 using 20mm graded stone aggregate rainforced with XPM and charcoal, dust and common salt all as shown in electrical plate No 3 of MES SSR Part-1(2009) and specified including and provision of GI wire upto 7.5 mtrs long with 15 mm dia light grade Gi pipe protection and watering pipe of GI 20 mm bore, medium grade, including all excavation and earth work and connecting the earthing strip to panel, including testing on completion complete all as specified and directed by Engr-in-charge. Note:- (i) RCC pit cover shall be precast of RCC(1:2:4) type B1, 80mm thick rainforced with XPM weighting not less than 4kg/sqm in lieu of CI cover.(ii) Cost of additional copper wire more than 7.5 mtrs will be measured and paid seperately under relevant items. |
| 10 | NOTES :-1. For the items for which specifications not mentioned any where in the tender, the BIS specifications shall be followed. Please Enable Macros to View BoQ information |