| 1 | Taking down the existing defective LT UG cable from trenches / pipes / pole for fault finding / replacement, all as specified and directed of any size between 10 Sqmm 4 Core to 50 Sqmm 3.5 Core. Note-Excavation and earth work will be measured and paid seperately under respective items. |
| 2 | Same as item No. 1.00 above but size 70 Sqmm 3.5 core to 185 Sq mm 3.5 core. |
| 3 | Supply, laying, jointing and testing XLPE insulated extruded PVC outer sheath and inner sheath galvanized steel armoured cable with aluminium conductor suitable for rated voltage of 1100 Volts grade conforming to IS 7089 (Pt I of 1988) laid in tranches/ pipe/duct/pole complete all as specified and directed size 10 Sqmm 2 core. |
| 4 | All as item No 03 above but size 10 sq mm 4 core. |
| 5 | All as item No 03 above but size 50 Sqmm 3.5 core. |
| 6 | All as item No 03 above but size 70 Sqmm 3.5 core. |
| 7 | All as item No 03 above but size 120 Sqmm 3.5 core. |
| 8 | All as item No 03 above but size 185 Sqmm 3.5 core. |
| 9 | Excavation in trenches n.exc. 1.5 m wide and n.exc.1.5 m deep in any type of soil and forming bottom surfaces for laying of cable complete all as specified and directed. |
| 10 | Supply & laying sand cushioning for cable protection in trenches 8 cm before laying cable and 15 cm thick over the cable complete all as specified and ditected. Note: Punned down thickness shall be measured for payment purposes. |
| 11 | Supply & laying bricks for protection of cable sub class 'B' laid dry flat across the cable with width equal to the length of whole bricks complete all as specified and ditected. |
| 12 | Returning filling in including spreading leveling watering and well ramming in layers n. exc. 25 cm complete all as specified and directed. |
| 13 | Removal of surplus soil to a distance n. exc. 50 m and deposited where diredted at a lavel not exc. 1.50 m above the starting pont complete all as specified and directed. |
| 14 | Labour only for boring, holes for insertion of 40/50/80 mm bore GI pipe under the road/hard standing or any other location not less than 1200 mm deep complete all as specified and ditected. |
| 15 | M & L in repair GI pipe 40 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 16 | M & L in repair GI pipe 50 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 17 | M & L in repair GI pipe 80 mm bore light grade fixed on pole/under road/on wall for protection of cable including all fittings complete all as specified and directed. |
| 18 | Taking down existing old defective LT Panel / FP Box by disconnectiing its all elecetrical connections and by dismantlling foundation complete all as specified and directed at site. |
| 19 | Supply, install, connect & testing cubical outdoor type factory made double door , powder coated LT bus bar feeder pillar box having alluminium bus bar suitable for 400 Amps 3 phase and neutral arrangement of size 600mm x 600mm x 200mm with MCCB 4 pole 250 Amp as incoming including provision of LED Indicating lamps (RYB) 01 set of 3. complete weather proof and vermin proof conforming to IP-54 made out of 3.15 mm thick CRCA sheet including provisions for ventilation and cable termination alley & two Nos suitable size of aluminum strip for body earthing all as per IS. It should be mounted on 40 x40 x 6mm angle iron frame with a clearance of at least 0.50 mtrs above GL and 0.50 mtrs below ground including required PCC for foundation complete all as specified and directed. |
| 20 | Supply, install, connect & testing cubical outdoor type factory made double door , powder coated LT bus bar feeder pillar box having alluminium bus bar suitable for 200 amps 3 phase and neutral arrangement of size 500mm x 500mm x 200 mm with MCCB 4 pole 63 Amp as incoming including provision of LED Indicating lamps (RYB) 01 set of 3. complete weather proof and vermin proof conforming to IP-54 made out of 3.15 mm thick CRCA sheet including provisions for ventilation and cable termination alley & two Nos suitable size of aluminum strip for body earthing all as per IS. It should be mounted on 40 x40 x 6mm angle iron frame with a clearance of at least 0.50 mtrs above GL and 0.50 mtrs below ground including required PCC for foundation complete all as specified and directed. |
| 21 | Supplying,installation,testing,commissioning of outdoor type LT panel board 3 phase 4 wire system ,415 Volts ,50 Hz factory made free standing , floor mounting dust and vermin proof cubical type interlocking arangement (IP- 55 protection) fabricated with 3.16 mm CRCA sheet with Anti corrosion coating & finally powder coate painting having thickness not less than 100 microns of finite grey, fully compartmentalized with providing two Nos suitable size of aluminum strip for body earthing and including suitable PCC foundation all as specified for the following :- |
| 22 | (a) Incomming :- |
| 23 | MCCB 200 AMPS 4 pole 415 Vollts 36 KA -01 No. |
| 24 | On load changeover switch 200 AMPS 4 pole 415 Vollts -01 No. |
| 25 | Digital type Amp Meter 0-300 Amp with CT's 03 Nos. |
| 26 | Digital type voltmeter 0-500 Volts -01 No. |
| 27 | Indicating lamps (RYB) 01 set of 3. |
| 28 | Alluminium bus bar rating 400 Amps 3 phase neutral-01 set |
| 29 | Chamber for incoming & outgoing cable. |
| 30 | (b) Outgoing :- |
| 31 | MCCB 125 AMPS 25 KA 415 Volts 4 pole -01 No. |
| 32 | MCCB 100 AMPS 25 KA 415 Volts 4 pole -01 No. |
| 33 | MCCB 63 AMPS 16 KA 415 Volts 4 pole -03 No. |
| 34 | Supplying,installation,testing,commissioning of outdoor type LT panel board 3 phase 4 wire system ,415 Volts ,50 Hz factory made free standing , floor mounting dust and vermin proof cubical type interlocking arangement (IP- 55 protection) fabricated with 3.16 mm CRCA sheet with Anti corrosion coating & finally powder coate painting having thickness not less than 100 micronsof finite grey, fully compartmentalized with providing two Nos suitable size of aluminum strip for body earthing and including suitable PCC foundation all as specified for the following :- |
| 35 | (a) Incomming :- |
| 36 | MCCB 125 AMPS 4 pole 415 Vollts 36 KA -01 No. |
| 37 | Digital type amp meter 0-200 Amp with CT's 03 Nos. |
| 38 | Digital type voltmeter 0-500 Volts -01 No. |
| 39 | Indicating lamps (RYB) 01 set of 3. |
| 40 | Aluminium bus bar rating 200 Amps 3 phase neutral-01 set |
| 41 | Chamber for incoming & outgoing cable. |
| 42 | (b) Outgoing :- |
| 43 | MCCB 63 AMPS 16 KA 415 Volts 4 pole -02 No. |
| 44 | MCB TPN 40 Amps 415 volts, 10KA \\"C\\" curve.-04 No. |
| 45 | M&L in repar earthing complete with galvanised steel earth plate 600X600X6.3 mm thick buried directly in ground (earth pit not les than 2.25 M deep below GL with top edge of plate not less than 1.5 m below GL) connected with GI earth strip of 32X6 mm as earthing leads by means of bolts, nuts, check nuts and washers beside Welding / brazing at all joints as shown on drawings and including excavation, earth work. GI pipe light grade 40 mm bore for protection of GI earth strip from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt PCC (1:2:4) type B1chamber and MS angle iron frame of 40mmx40mm x3 mm and RCC cover 40 mm thick (1:2:4) type B1 using 20 mm graded stone aggregate reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with MS handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No 3 of SSR Part -I and conected to earth test point including testing complete all as secified and directed. |
| 46 | Supply and fix in repair LED Flood light 70 W IP 66 including necessary electric connection with twin core twisted flexible copper conductor cable of suitable size complete all as secified and directed. |
| 47 | Supply & Fixing in replacement split type air conditioner of capacity 2.0 TR 4 star rating and EER 3.2. with cordless remote control unit and in built air ioniser ,plasma filter for better indoor air quality, suitable for wall mounted,single phase, 230/250 volt AC including breaking necessary hole in wall for fixing indoor and outdoor unit and making good to disturbed surfaces with cement mortar to match with existing after commissioning as required at site, making necessary connections and M & L for unplasticised PVC pipes medium duty 20 mm dia for draining out condensed water all as required and directed including necessary connection through voltage stabilizer,testing of AC complete all as specified and directed.Make LG/Carrier /Hitachi / OGeneral. |
| 48 | Supply & Fixing in replacement split type air conditioner of capacity 1.5 TR 5 star rating and EER 3.2. with cordless remote control unit and in built air ioniser ,plasma filter for better indoor air quality, suitable for wall mounted,single phase, 230/250 volt AC including breaking necessary hole in wall for fixing indoor and outdoor unit and making good to disturbed surfaces with cement mortar to match with existing after commissioning as required at site, making necessary connections and M & L for unplasticised PVC pipes medium duty 20 mm dia for draining out condensed water all as required and directed including necessary connection through voltage stabilizer,testing of AC complete all as specified and directed.Make LG/Carrier/Hitachi /OGeneral. |
| 49 | Supply , installation, testing and commissioning refrigerator electric driven single phase 230 Volt AC, 50 Hz free standing, single door, inverter, direct cool 5 star rating of capacity 242 Ltrs. Make LG model LG 242 L or equivallent model in Samsung / Whirlpool with latest specifications. |
| 50 | Supply , installation, testing and commissioning refrigerator electric driven single phase 230 Volt AC, 50 Hz free standing, double door, inverter, convertible 2 star rating of capacity 325/340 Ltrs. Make LG model LG 340 L or equivallent model in Samsung / Whirlpool with latest specifications. |
| 51 | Supply, installation, testing and commissioning of Water cooler fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity 40/80 Ltrs Make: LG/Usha/Samsung |
| 52 | Supply and fixing voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 1 KVA suitable for refrigerator copper wound complete for refrigerator all as specified and directed. |
| 53 | Supply and fixing wall mounting voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 4 KVA copper wound complete all as specified and directed. |
| 54 | Supply and fixing wall mounting voltage stabilizer for automatic operation single phase naturally air cooled indooor type and designed for input voltage between 130 volt to 280 volts with output voltage stabilized at 230 V +/- 2.5% with time delay relay and suitable for fixing / mounting on wall of capacity 5 KVA complete all as specified and directed. |
| 55 | Supply & fixing in repair factory made,universal bracket / wall mounting stand ,made with galvanized structural steel,high strenth,weather proof,powder coated,modular construction and weight not less than 5 Kg and suitable upto 2 TR capacity split type AC. |
| 56 | M & L in repair for power/sub main wiring with two runs of single core 4 sqmm size and one run of single core 4.0 sqmm (green colour as earth continuty conductor ) PVC insulated unsheathed multi stranded copper conductor cables drawn through and including 20 mm dia rigid PVC concealed conduit complete all as specified and directed.( Note - two runs of 4 sq mm single core copper conductor and one runs of 4.0 Sq mm copper conductor shall be measured as one unit length.) |
| 57 | Supply & fixing in repair earth plug enclosure (plug and socket ) with one MCB, SP 20 Amps complete all as secified and directed. |
| 58 | Supply & Fixing in repair sheet metal enclouser MCB DB double door bus bar neutral link,earth bar and din rail SPN 8 way complete all as secified and directed. |
| 59 | Supply & Fixing in repair MCB SPN 32 Amps 240 volts, 10 KA, \\"C\\" curve complete all as secified and directed. |
| 60 | Supply & Fixing in repair MCB SP 5 to 32 Amps 240 volts, 10 KA, \\"C\\" curve complete all as secified and directed. Please Enable Macros to View BoQ information |